Tender For Providing 11 Kv H.T. Metering Panel, 500 Kva Transformer, 11 Kv Vcb, Apfc Panel, Main Lt Panel, Power Cables, Lt Cables And All Other Contingent Items Thereto In Hsvp Office Building Sector-12 At Faridabad. Including 6 Years Defect Liabili
Tender Overview
Project Description
Tender for Providing 11 Kv H.T. Metering Panel, 500 Kva Transformer, 11 Kv Vcb, Apfc Panel, Main Lt Panel, Power Cables, Lt Cables And All Other Contingent Items Thereto In Hsvp Office Building Sector-12 At Faridabad. Including 6 Years Defect Liability Period Of Transformers And 3 Years Defect Liability Period Of All Other Items Free Of Construction A/Cost Rs.82.44 Lacs E/Money Rs.164880.00 Time Limit : 4 Months
BOQ
| Sl. No. | Item Description |
| 1 | [11.5.3]12 mm cement plaster of mix : 3. 1:4 (1 cement: 4 fine sand) [Through Rate] |
| 2 | [11.6.1]15 mm cement plaster on the rough side of single or half brick wall of mix : 1. 1:4 (1 cement: 4 fine sand) [Through Rate] |
| 3 | [13.28]Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. [Through Rate] |
| 4 | [13.32]Providing and fixing bolts including nuts and washers complete. [Through Rate] |
| 5 | [20.71.1]Supply, erection, testing of Ceiling fans IS marked (as per IS code 374) with suitable GI pipe complete in all respects complete as per directions of Engineer-in-charge 1. 48\\" (1200mm) [Through Rate] |
| 6 | [20.76.12]Design, Supply, Erection, Testing and Commissioning outdoor type 3 phase transformer (input) 11KVA /433 V (3phase output) -250 V (single phase output) Oil immersed naturally cooled, energy efficiency level-2 including cost of earthlings as per DHBVN/ UHBVN norms, inspection charges, Connecting material i.e. lugs thimbles complete in all respect satisfaction to Engineer-in-Charge(Inspection certificate will be issued by Chief Electrical Inspector of Nigam & inspection charges will be borne by agency. 12. 500 KVA [Through Rate] |
| 7 | [23.22.1.5]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.5. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 200 to 250 Amp, 25 KA [Through Rate] |
| 8 | [23.22.1.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 1.7. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. TRIPLE POLE MCCB 400 Amp, 50 KA [Through Rate] |
| 9 | [23.22.5.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.3. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Double POLE [Through Rate] |
| 10 | [23.22.5.6]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.6. Supply and erection of miniature circuit Breaker 240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs TRIPLE POLE [Through Rate] |
| 11 | [23.23.6.3]MISCELLANEOUS 6.3. Supply and erection of MS cable tray , duly pained as required including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. MS perforated cable tray painted with powder coating 375 X 50 X 2 mm [Through Rate] |
| 12 | [23.23.6.4]MISCELLANEOUS 6.4. Supply and erection of MS cable tray , duly pained as required including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. MS perforated cable tray painted with powder coating 600 X 50 X 2 mm [Through Rate] |
| 13 | [23.23.7.3]MISCELLANEOUS 7.3. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 375 X 50 X 2 mm metre [Through Rate] |
| 14 | [23.23.7.4]MISCELLANEOUS 7.4. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 600 X 50 X 2 mm [Through Rate] |
| 15 | [23.24.4.4]MS STAND, BUS BAR CHAMBER AND PANELS 4.4. Supply, installation, testing and commissioning of load bank with digital meter module cost of digital Amp. / volt meter with selector switch wiring ( but EXLUDING COST of incoming and outgoing MCCBs ) etc.suitable for operation of 240/415 volts A.C. Supply with both side cable allay, inter connection and fixing the same in existing MS pedestal/wall complete with all labour and material required for the same up to the entire satisfaction of Engineer-in-Charge of work. Load Bank 8 way 400 amp. [Through Rate] |
| 16 | [23.28.13.13]Supplying, installation, Testing and Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency )85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency )85%,THD ( 10% as per IEC 61000-3-2 , P. F.=0.95, IP- 66,IK-10, CRI )80, under voltage and over voltage protection, EMI- EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver and electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) (5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy =120 (135 lm/Watt output . LM79 and LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). 13. 72 watt [Rate] |
| 17 | [23.28.7.10]Supplying, installation, Testing and Commissioning of Panel light 2x2 ft., offollowing body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency )85%, Operating voltage AC 140- 270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short and Open circuit protection ,THD ( 10% , P. F.=0.95, IP20, CRI )80, UGR (Unified Glare Rating) ( 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver and electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) (3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy =120 (135 lm/Watt output . LM79 and LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) 10. CRCA Sheet Body (Thickness >= 0.50 mm) 36 Watt [Rate] |
| 18 | [23.32.1.1]Automatic Power Factor Correction (APFC) SystemSupply, Installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel, indoor type floor mounted free standing totally enclosed, extendable, IP 42, of following capacity for 3 phase, 415 V plus 10 %, 50 Hz AC System for Ambient temperature -5°C to plus 40°C, fabricated in compartmentalized designed made of CRCA sheet steel of 2.0mm thick for framework and covers, 3 mm thick for gland plate i/c cleaning and finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section capacitor and reactor, front and rear access, having suitable current carrying capacity, extensible TPN Aluminum alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 and 2) APFC Panel shall be in compliance with IS :16636 and CPWD Specifications etc. as per below details(A) Incomers Suitable capacity MCCB Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set along with required Instruments and accessories with extended rotary handle and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.(B) Instruments and Indications i) 3-Phase current sensing APFC microprocessor relay/controller , advance 8/12 stages (8 stages for capacity below 100 KVAR and 12 stages 100 KVAR and above) with Communication Ethernet/RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge and having display of Phase wise V, A, PF, Cos-Phi, Kw, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. 3 nos of dual core CT`s accuracy class 1, 15VA at incomer of PCC Panel for APFC relay.i) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode.ii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V and I, Frequency.iii) Suitable rating control transformer shall be provided for control and indication circuit.i) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB`s.ii) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS 1100 V grade, PVC insulated multi stranded copper control wire.(B) Bus Bars1.3 Amp per Sq.mm, TPN, Electrolytic grade Aluminum bus bar of capacity 1.25 times of incomer rating as per CPWD specification.(C) Outgoings (APFC Section)Selection of the capacitors combinations shall be for continuous rating and each capacitor bank shall have suitable capacity Heavy Duty ISI Marked Capacitor, capacitor duty contactor, the capacitor shall be mounted on channel with base of perforated M S Powder coated sheet, connections inter connections etc. and other features as per CPWD Specifications and relevant IS Code having following:(i) Capacitor bank ratings and stages shall be as per(ii) Capacitor will be MPP self healing type with discharge resistor, pressure release mechanism.(iii) Since Capacitor Voltage is 525 Volts, thus higher KVAR has to be considered to get rated output at 415 Volts.(iv) 14% Detuned Reactor of class H insulation and 150% linearity in series with Capacitor. 1. 50 KVAR [Rate] |
| 19 | [23.32.1.7]Automatic Power Factor Correction (APFC) SystemSupply, Installation, testing and commissioning of Automatic Power Factor Correction (APFC) panel, indoor type floor mounted free standing totally enclosed, extendable, IP 42, of following capacity for 3 phase, 415 V plus 10 %, 50 Hz AC System for Ambient temperature -5°C to plus 40°C, fabricated in compartmentalized designed made of CRCA sheet steel of 2.0mm thick for framework and covers, 3 mm thick for gland plate i/c cleaning and finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section capacitor and reactor, front and rear access, having suitable current carrying capacity, extensible TPN Aluminum alloy bus bar of high conductivity, DMC/SMC bus bar supports, bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 and 2) APFC Panel shall be in compliance with IS :16636 and CPWD Specifications etc. as per below details(A) Incomers Suitable capacity MCCB Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set along with required Instruments and accessories with extended rotary handle and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.(B) Instruments and Indications i) 3-Phase current sensing APFC microprocessor relay/controller , advance 8/12 stages (8 stages for capacity below 100 KVAR and 12 stages 100 KVAR and above) with Communication Ethernet/RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge and having display of Phase wise V, A, PF, Cos-Phi, Kw, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. 3 nos of dual core CT`s accuracy class 1, 15VA at incomer of PCC Panel for APFC relay.i) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode.ii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V and I, Frequency.iii) Suitable rating control transformer shall be provided for control and indication circuit.i) All components like control transformer, meter, relay and indicating lamp shall be protected by using suitable rating individual MCB`s.ii) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS 1100 V grade, PVC insulated multi stranded copper control wire.(B) Bus Bars1.3 Amp per Sq.mm, TPN, Electrolytic grade Aluminum bus bar of capacity 1.25 times of incomer rating as per CPWD specification.(C) Outgoings (APFC Section)Selection of the capacitors combinations shall be for continuous rating and each capacitor bank shall have suitable capacity Heavy Duty ISI Marked Capacitor, capacitor duty contactor, the capacitor shall be mounted on channel with base of perforated M S Powder coated sheet, connections inter connections etc. and other features as per CPWD Specifications and relevant IS Code having following:(i) Capacitor bank ratings and stages shall be as per(ii) Capacitor will be MPP self healing type with discharge resistor, pressure release mechanism.(iii) Since Capacitor Voltage is 525 Volts, thus higher KVAR has to be considered to get rated output at 415 Volts.(iv) 14% Detuned Reactor of class H insulation and 150% linearity in series with Capacitor. 7. 200 KVAR [Rate] |
| 20 | [24.13.48]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 48. 50 Sq mm 4 core (Arm.) [Through Rate] |
| 21 | [24.13.62]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 62. 95 Sq mm 3.5 core (Arm.) [Through Rate] |
| 22 | [24.13.88]LT CABLES (Aluminium Conductor, Armoured and Unarmoured) PROVIDING& ERECTION/ LAYING OF PVC/ XLPE INSULATED UNDERGROUND ALUMINIUM CONDUCTOR UNDERGROUND CABLE LOOSE IN EXISTING PIPE OR TRENCHES COMPLETE IN ALL RESPECT WITH NECESSARY CONNECTION UPTO THE ENTIRE SATISFACTION OF ENGINEER IN CHARGE OF THE WORK 88. 240 Sq mm 3.5 core (Arm.) [Through Rate] |
| 23 | [24.16.4]HT CABLES (Aluminium Conductor, Armoured and Unarmoured) Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 4. Providing and erection/ laying of XLPE (E) 11 KV HT Aluminium Conductor Armoured Cable ISI Mark Laid in Existing Pipe/Trenches/Surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-In-Charge of the Works 95 Sq mm 3 core [Through Rate] |
| 24 | [24.2.7.3]LT CABLE 7.3. Supply and erection of suitable compression type brass cable glands for underground Cable :- 25 sqmm to 50 sqmm Cable 2 to 4 Core [Through Rate] |
| 25 | [24.2.7.4]LT CABLE 7.4. Supply and erection of suitable compression type brass cable glands for underground Cable :- 70 sqmm to 95 sqmm Cable 3 to 3½ Core [Through Rate] |
| 26 | [24.2.7.6]LT CABLE 7.6. Supply and erection of suitable compression type brass cable glands for underground Cable :- 240 sqmm to Cable 3 to 32 Core [Through Rate] |
| 27 | [24.2.8.7]LT CABLE 8.7. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 50 sqmm [Through Rate] |
| 28 | [24.2.8.9]LT CABLE 8.9. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 95 sqmm [Through Rate] |
| 29 | [24.3.3.1]HT CABLE 3.1. Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm [Through Rate] |
| 30 | [24.3.4.1]HT CABLE 4.1. Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm [Through Rate] |
| 31 | [25.11.2.3]HI - WALL SPLIT SYSTEMS Supplying, Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low and high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 °C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS:1391 Part II 2023. The system shall be able to operate up to 50 °C (out door ambient temperature). 3. Inverter Type- Cooling only 1.5 TR with 5 Star BEE Rating [Rate] |
| 32 | [4.12.1]Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead up to 50 m and lift up to 1.5 m, as directed by Engineer-in-charge. 1. All kinds of soil [Through Rate] |
| 33 | [6.1.2]Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work below plinth level and up to Floor IV level: 2. 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) [Through Rate] |
| 34 | [6.1.4]Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work below plinth level and up to Floor IV level: 4. 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size) [Through Rate] |
| 35 | [7.20.1]Brick work with common burnt clay modular bricks of class designation 10.5 in foundation and plinth in: 1. Cement mortar 1:4 (1 cement : 4 coarse sand) [Through Rate] |
| 36 | Supply and erection of PCC pole 11 mtr long as per IS: 1678-1960 specifications, 140mm x 200mm at top and 140mm x 400mm at bottom with working load of 400Kg buried 2.20M in ground or as per DHBVNL specification (Rate without GST) |
| 37 | Supply and erection of 11 KV pin insulator polymeric type 10 KN with GI pin as per latest specification and approved make by DHBVN. (Rate without GST) |
| 38 | Supply and erection of 2.5 Sqmm 3-core copper flexible cable , FRLS PVC insulated and round sheathed, bright annealed copper conductor heavy duty industrial flexible cable for voltage grade 1100 volts confirming to IS: 694:2010 complete in all respect up to entire satisfaction of the Engineer-in-Charge of the work. (Rate without GST).Make – Havells/ polycab/ KEI or make approved by DHBVN. |
| 39 | Supply and erection of 32 mm dia G.I. pipe bracket 1.0 mtr long made out of 32mm nominal dia (B-class) suitable for street light fitting including 2 nos. Clamps of M.S. Flat size 50x6mm, 6 nos. Nutt and Bolts of size 50x16mm with application of primer and painting complete in all respect up to the entire satisfaction of Engineer-in-Charge. (Rate without GST). |
| 40 | Supply, erection , testing and commissioning of Exhaust fan 300mm (12 inch) with bearing complete with necessary connections complete in all respect up to the Entire satisfaction of Engineer-In-Charge. (Rate without GST)Make- Crompton/ Bajaj/Orient |
| 41 | Supply and erection of cable holding wooden cleat set with single grove suitable to hold cable of size 50 sqmm to 400 sqmm, made out of best quality of wood to withstand the load tension of cable and outdoor atmosphere complete with all labour and material complete in all respect. (Rate without GST) |
| 42 | Supply and erection of 630 sq mm x 1 core L.T. underground cable Unarmored PVC insulated and PVC sheathed made out of aluminum conductor, 650/1100 Volt, as per IS 7098(part 1) 1988 with latest amendments loose in existing pipe or trenches complete with necessary connections. ( RATE WITHOUT GST) Make - As per list attached |
| 43 | Supply and Erection of 11 kV G.O. Switch vertical mounted with heavy duty 6 Nos. post insulators suitable, for copper male and female contacts fixed on GI angle frame with G.I. Nut and Bolts including G.I. pipe and operating handle and complete in all respect (Rate Without GST). |
| 44 | Supply and erection of Danger Plates (Enamelled) with clamp and all other allied items complete in all respect up to the entire satisfaction of Engineer-in-charge. (Rate without GST) |
| 45 | Supply erection testing and commissioning of chemical earthing with 3 mtr. long 75 mm dia G.I pipe filled with chemical, the chemical compound should have a low resistivity, ideally below 0.2 ohm-meter, to facilitate efficient grounding. complete in all respect up to entire satisfaction of Engineer-in-charge of the work. (Rare without GST) |
| 46 | Supply only of HDPE pipe PE63, PN4 of size 63 mm dia for use in trenchless boring as per IS4984, ISO: 4427 and suitable for electrical cables complete in all respect up to the entire satisfaction of Engineer-in-Charge. Make: - as per list attached (Rate without GST) |
| 47 | Supply only of HDPE pipe PE63, PN4 of size 90 mm dia for use in trenchless boring as per IS4984, ISO: 4427 and suitable for electrical cables complete in all respect up to the entire satisfaction of Engineer-in-Charge. Make: - as per list attached (Rate without GST) |
| 48 | Supply only of HDPE pipe PE63, PN4 of size 160 mm dia for use in trenchless boring as per IS4984, ISO: 4427 and suitable for electrical cables complete in all respect up to the entire satisfaction of Engineer-in-Charge. Make: - as per list attached (Rate without GST) |
| 49 | Laying only of HDPE pipe of size 63 mm dia by using of trenchless technology 1.5 meter below ground level including scanning of underground services before laying the pipe for protection of the existing services like underground cable, gas pipe, water pipe, oil pipe, sewerage pipe or any other service (excluding the cost of HDPE pipe) complete in all respect up to the entire satisfaction of Engineer-in-Charge. (Rate without GST) |
| 50 | Laying only of HDPE pipe of size 90 mm dia by using of trenchless technology 1.5 meter below ground level including scanning of underground services before laying the pipe for protection of the existing services like underground cable, gas pipe, water pipe, oil pipe, sewerage pipe or any other service (excluding the cost of HDPE pipe) complete in all respect up to the entire satisfaction of Engineer-in-Charge. (Rate without GST) |
| 51 | Providing and fixing 1.8 meters high G.I. wire mesh fencing with wire mesh made out of 8 SWG/4.0 mm G.I. wire of size 50mm x 50 mm, with2.50 meter angle iron posts 50 mm x 50 mm x 6 mm placed every 1.0 meters center to center founded in M15 grade cement concrete 0.7 meter below ground level, and 2 nos. horizontal angles 1.5mtr long and vertical flats 50mm x 6 mm of length 1.8mtr, 2 nos. horizontal channel 1.5mtr long with one entry gate of 1.0 mtr wide and 2.0 mtr.High, including priming and painting complete with all material, labour, welding, machinery charges complete in all respect up to entire satisfaction of engineer in charge of work (Rate Without GST) |
| 52 | Supply and erection of G.I. strip of size 35 mm x 5 mm made out of hot dipped galvanized flat as earth electrode for use of earth electrode for Chemical earhings/ Pipe earthing/ plate earthing complete with G.I nuts, bolts, washers including welding charges and labour charges. (Rate Without GST) |
| 53 | Supply, erection, testing and commissioning of H.T. metering panel cubical type made out of CRCA sheet of approved size of DHBVNL duly painted after pretreatment and comprising of following approved make accessories as per DHBVNL / UHBVNL, 11 KV danger plate, Inscription plate, metering CT / PT of rating etc. 11 KV indoor dry type epoxy resin cast vacuum impregnated single phase C.T. or 11 KV effectively arched system conforming to IS 2705 with insulation level of one minute power frequency 2.5 KV and CTs shall be of class 0.5 accuracy with burden 5KVA ratio 30/5A of Make Zenith/concord or approved by DHBVN /UHBVN, 1 set of 3 Nos. (The ratio of C.T. can be altered on requirement of UHBVNL) PTs 11 KV indoor potential transformer dry type epoxy raisin case vacuum impregnated 3 phase suitable for 11 KV effectively unearthed system suitable for secondary 3 phase 4 wire system with insulation level of one minute power frequency with stand test 3156 of 10 KVA burden ratio 11 KV/110V of Make Zenith/concord or as approved by DHBVNL. ENERGY METER. The digital type energy meter of approved make of UHBVN duly tested from State HVPN / UHBVN laboratory of accuracy class 0.5 on full scale with VA burden not more than 4 VA suitable to operate in ambient temperature of as high as 50ºC with C.T. ratio as per UHBVNL. Rate without GST |
| 54 | Supply, installation, testing, commissioning of Combined Unit i.e. a set of CTs and PT complete in all respect complete as per DHBVN latest specifications and make as per list attached (Rate without GST) |
| 55 | Supply, erection, testing and Commissioning of 11 kV, 630 Amp VCB Panel indoor type having one incoming and one outgoing, non-extensible type, with highest system voltage of 12 kV, with a rated continuous current of 630 Amps at a 50 Hz frequency, manual and motorized charged, including powerpack, all type of control wires, protection relays with protection system to protect the transformer from all type of faults. Some technical specifications include a symmetrical breaking capacity of around 40 kA or 350 MVA, an impulse withstand voltage of 75 kVp, and a power frequency withstand voltage of 28 kV. The breaker is designed for 3-phase AC systems, typically indoor, metal-clad, 11 KV and equipment with: -Electrical Parameters • Nominal System Voltage: 11 kV (rms)• Highest System Voltage: 12 kV (rms)• Rated Frequency: 50 Hz ± 1.5 Hz or ± 3%• Number of Poles: 3• Rated Continuous Current: 630 A at 40°C reference ambient temperature• Symmetrical Breaking Capacity: 40 kA or 350 MVA at 11 kV• Rated Making Capacity: 46-83 kA• Power Frequency Withstand Voltage: 28 kV for 1 minute• Basic Impulse Withstand Voltage (BIW): 75 kVp• Opening Time: Less than 40 millisecondsMechanical and Construction• Type: Vacuum Circuit Breaker (VCB) • Design: Totally enclosed, metal-clad, horizontal draw-out • Operation: Manual and Motor operated spring charging with 230V AC motor • Components: Includes trip and close coils (24VDC), auto safety shutters, and manual push buttons • Enclosure: Modular construction housed in a single enclosure with distinct compartments for the circuit breaker, busbar, CT/cable, and LT instruments• Make- Siemens/ Havells/Schneider Electric/ LandT (Larsen and Toubro)/ ABB |
| 56 | Supply, erection, testing and commissioning of cubical type panel dust and vermin proof Main L.T. panel made out of 1.6 mm thick CRCA sheet with powder coated paint as per detail given below. 1 ACB 1600 AMP 4P 50KA MDO of make Siemens/ Havells/Schneider Electric/ LandT (Larsen and Toubro)/ ABB=1No.2 MCCB 250A/4P/25KA of make Siemens/ Havells/Schneider Electric/ LandT (Larsen and Toubro)/ ABB =14 Nos 3 ROTARY HANDLE 100/250 of make Siemens/ Havells/Schneider Electric/ LandT (Larsen and Toubro)/ ABB =14 Nos 4 SPREADER LINK 100/250 of make Siemens/ Havells/Schneider Electric/ LandT (Larsen and Toubro)/ ABB =28 Nos 5 METER VAF TRINITY= 1 no.6 CT 1600/5 TRINITY =3 nos.Earthing alum. Bus bar of cross section 32mmx6mm duly and insulated through the length of panel. The panel will be complete with all internal wiring with PVC copper wire, inter connection etc. in all respect with all labour and material require to complete the job in all respect without cost of MCCB up to the entire satisfaction of the Engineer-in- charges. Rate without GST |
| 57 | Supply and erection of 11 KV voltage Level Insulating mats for protection from 11 KV voltage level 1 meter wide complete in all respect complete as per DHBVN latest specifications and make as per list attached (Rate without GST) |
| 58 | Supplying and fixing of Bucket stand with 5 nos. fire buckets in each set of approved quality, red painted from outside and white from inside conforming to IS : 2546/1974 with additional handle at the bottom, filled with fine sand and fixed on an angle iron frame including MS pedestal stand suitable for supporting five buckets as per the requirement of local authorities. (Rate without GST) |
| 59 | Providing and fixing fire extinguisher of carbon dioxide type consisting of brand-new high-pressure steel cylinder bearing IS:7285 mark and having the approval of controller of explosives Nagpur, wheel type valve bearing IS:3224-mark internal discharge tube, 1-meter-long high-pressure discharge hose, non-conducting horn, suspension bracket, fully charged bearing IS: making fixed to wall as directed. 4.5 kg capacity cylinder. (Rate without GST) |
| 60 | Supply and fixing in position the approved shock treatment / restoration charts written in Hindi and English duly framed in teak wood frame and covered with 2.8mm glass as required. (Rate without GST) |
| 61 | Supplying and fixing of caution Boards of 16 S.W.G., M.S. sheet of 300 mm x 150mm size, duly painted and having `MAN ON LINE` and `DO NOT SWITCH ON` written in Red complete with hanging arrangement as required. (Rate without GST) |
| 62 | Supply and Erection of Battery for Inverter of capacity 150/155 AH, 12-volt, Tubular type, (With 3 years free replacement warranty free of cost) complete in all respect up to the entire satisfaction of the engineer in-charge of the work. (Rate without GST) Make- Exide/ Luminous/Amaron |
| 63 | Supply and Erection of 2000/2200 VA UPS 24 Volt/230-volt, Pure Sine Wave Inverter, Efficiency )80 %, Output Voltage 180V-265V, Output Frequency 50Hz plus 0.5Hz, Overload )105% / )300%, (With 2 years free replacement warranty at site including labour charges free of cost) complete in all respect up to the entire satisfaction of the engineer in-charge of the work. (Rate without GST) Make- Microtek/ Luminous/ Su-kam Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender