Tender For Upgradation / Improvement Of Existing Electric Network (Wiring, Luminaries, Floor Panels Etc.) With Allied Works At Various Areas At Skims Mch Bemina (Phase - I)
Tender Value
39.97 Lakhs
Estimated cost
Bid Submission
31 Aug 2026
4 days left
EMD
79960
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Budgam → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Upgradation / Improvement Of Existing Electric Network (Wiring, Luminaries, Floor Panels Etc.) With Allied Works At Various Areas At Skims Mch Bemina (Phase - I)
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.bacterial/anti-fungal)(Havells / Polycab / KEI) |
| 2 | Group B |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.bacterial/anti-fungal)(Havells / Polycab / KEI) |
| 4 | 2 x 1.5 sq. mm + 1 x1.5 sq. mm earth wire(in minimum 20mm) |
| 5 | 2 x 2.5 sq. mm + 1 x 2.5 sq. mm earth wire(in minimum 20mm) |
| 6 | 2 x 4 sq. mm +1 x 4 sq. mm earth wire(in minimum 20mm) |
| 7 | 2 x 6 sq. mm +1 x 6 sq. mm earth wire(in minimum 25mm) |
| 8 | 2 x 10 sq. mm +1 x 6 sq. mm earth wire |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 25 mm |
| 11 | 32 mm |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.(Havells / Polycab / KEI) |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.bacterial/anti-fungal)(Havells / Polycab / KEI) |
| 14 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(Havells / Polycab / KEI) |
| 15 | 6 way (4 + 18), Double door |
| 16 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB SP, DB and MCB TPN complete with connections, testing and commissioning etc. as required.(Havells / Polycab / KEI) |
| 17 | Single pole |
| 18 | Double pole |
| 19 | Supplying and fixing following rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(Havells / Polycab / KEI) |
| 20 | 63A TPN |
| 21 | Supplying and fixing following size / modules, Gl box alongwith modular base & cover plate for modular switches in recess etc. as required |
| 22 | 6 Module (200mmx75mm) |
| 23 | 8 Module (125mmx125mm) |
| 24 | 12 Module (200mmx150mm) |
| 25 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) material and construction as per IS : 10322 with driver as perthe requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standardand trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respects40 Watt(Havells / Crompton / Bajaj) |
| 26 | Surface type LED luminaries 15-20 Watt circular/square type slim decorative aluminium casted and separate electronic driver with system temperature 5500/6000/6500 K and robust construction in combination with flat diffuser with minium system Lumens 1200 with burning hours greater than 40000 Hours having system lumens =110 lm/watt, Industrial Type(Havells / Crompton / Bajaj) |
| 27 | Supply, installation, Testing & Commissioning of 60KVA/60KW, True Online, DSP Controlled, double conversion online UPS with 3 phase AC input and 3 phase AC output with backup of 30min on 12V SMF batteries Bank with Rack (min. VAH required = 48000VAH) in parallel redundant system with load sharing. The UPS should be with IGBT Based Rectifier and IGBT based Inverter and with LCD/LED touch/semittouch screen display for monitoring of its status along with same OEM Make identical Galvanic Isolation Transformer at Input side. UPS should be with inbuilt Phase sequence correction & protection feature, Cold start feature and emergency power off (EPO) feature, static & Maintenance By-Pass inbuilt & dust filters. Ac-Ac Efficiency min 96% without isolation transformer, ISO 9001 & 14001 certification, IP 20 protection & design as per “IEC EN 62040 standards, CE, ROHS, PEP & REACH Compliances. Noise Level Less than 65 dBA. 7” touch screen, Input Voltage window 320 VAC - 478 VAC based on % age of load.The Job includes supply, testing, laying, connecting & commissioning of 35 sq. mm, Single - Core, HRFR, PVC - insulated, Copper Conductor, Flexible Cable for the Input as well as Output connections of the UPS as per the instructions of the site engineer. |
| 28 | Fabrication, supply, installation, testing & commissioning of Electrical Panel of cubical construction, having 6 Nos. Angle-iron legs of suitable dimensions, to be sufficiently grouted in 1:2:4 concrete mix, into the existing floor or with the wall of the UPS room, as per site requirement, fabricated out of 2mm thick sheet steel, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated, cable alley, inter-connection with suitable size solid Aluminium strip, having switchgears and accessories, mountings and internal wiring, earth terminals and earthing, numbering etc. complete in all respects with following Incoming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz, AC Supply with enclosure protection class IP42 as required alongwith Digital Voltmeters / Ammeters / CT Coils of requisite Ratio / Selector Switches / LED Indications / locking arrangement etc. as per the instructions of the Site Engineer:Incoming:(i) 100A, 35-36kA, 4Pole, MCCB with rotary handle with Adjustable Thermal Rating:: 3 Nos.(ii) 125A, 4P, Onload Manual, Front-operated, Changeover Switch: 2 Nos.(iii) 200A, TPN, Aluminium Busbar: 1 Set.Outgoing:(i) 63A, 10-40kA, TPN, MCB : 3 Nos(ii) 32A, 10-40kA, DP, MCB : 10 Nos(iii) 20A, 10-40kA, SPN, MCB : 10 Nos |
| 29 | Earthing with copper earth plate 600 mm × 600 mm × 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal coke and salt as required. The Job includes providing, laying and fixing of 25 × 5 mm Copper strip to be laid from the earth plate (gas-welded with the plate) upto a height of 300 mm above the ground level. |
| 30 | Providing and fixing 25 mm × 5 mm copper strip in 40 mm dia PVC conduit from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 31 | Supply, Installation, testing & commisioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch |
| 32 | Providing and erection of 11 Mtr. Long Pole (ST-410 SP56) with Base Plate and Top Cap cover confirming to IS 2713 with up to date amendments |
| 33 | Providing and fixing of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 34 | Providing and fixing of Galvanised iron of sorts |
| 35 | Cement bottoming 1:2:4 mix as per Standards 0.70 cum / Pole |
| 36 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25×3mm |
| 37 | Providing and applying Red Oxide |
| 38 | Providing and applying Aluminium Paint |
| 39 | Providing and fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting |
| 40 | Providing and fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 41 | Providing and fixing of GI Channel/Angle/Flat of sizes including clamps for L.A Set/G.O Set/Horn Gap |
| 42 | Providing and fixing of Galvanized Nuts and Bolts. |
| 43 | Providing and fixing of GI V cross-arm with top Bracket including clamp |
| 44 | Providing and laying of 100 mm² ACSR Conductor (Dog) |
| 45 | Providing and fixing of GI Barbed Wire for Anti Climbing including clamps |
| 46 | Sundry items like Aluminium lugs, Jumpers, binding Tape Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 18, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 31, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysSep 01, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender