Tender For Special Repair And Replacement Of Ht Cable With Connected Item And Transformer In All Location , Ht Line From Ascon Node To Rmu Chowk And Provn Of Ring Maintenance Unit (Rmu) Nearby Gate No 1 At Gandhidham Military Station Under Ge (A) Bhu
Tender Overview
Project Description
Tender for Special Repair And Replacement Of Ht Cable With Connected Item And Transformer In All Location , Ht Line From Ascon Node To Rmu Chowk And Provn Of Ring Maintenance Unit (Rmu) Nearby Gate No 1 At Gandhidham Military Station Under Ge (A) Bhuj
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CWE (A) AHMEDABAD NAME OF WORK: SPECIAL REPAIR AND REPLACEMENT OF HT CABLE WITH CONNECTED ITEM AND TRANSFORMER IN ALL LOCATION , HT LINE FROM ASCON NODE TO RMU CHOWK AND PROVN OF RING MAINT UNIT (RMU) NEARBY GATE NO 1 AT GANDHIDHAM MILITARY STATION UNDER GE (A) BHUJ Contract No: CWE (A)/BHUJ/ OF 2026-2027 SERIAL PAGE NO Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # SL NO ITEM DESCRIPTION Item Code / Make QTY UNITS Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Supply, installation, testing & commissioning of Outdoor (IP54) 11kV 630Amps 21KA/3 sec. One side Extensible 5 Way Ring Main Unit Compact switchgear consisting of 5 nos. fixed motorized Vacuum Circuit Breaker Module and Copper Busbar in SF6 insulated stainless steel enclosure (2.5 mm thick, SS304 grade). The complete RMU must be type tested for Internal arc 21KA for 1 sec with AFLR Classification for Gas tank & Cable Chamber. RMU shall be supplied completely including Aux .powered relay,Aux.Transformer & other standard Accessories.HT RMU Shall preferably have site replaceable bushings to have very less downtime in the event of bushing breakage and restoration can be done immediately without sending the RMU to OEM Works. The Vaccum Interrupter must RMU manufacturer's own make. All modules shall be in a single gas tank.Make of RMU shall be limited to : ABB/ SIEMENS/ SCHNEIDER INFRASTRUCTURE [ Channel partner / System Integrator / Authourized Partner/ License partner make RMU shall not be accepted. The complete RMU shall be consisting of followings:All VCB module shall have Auxiliary powered numerical protection relay (RMU manufacturer's own make) having Over Current, & earth fault protection with Modbus protocol (RS485) complaint with programable 6 DO, 4DI & 8 front LED with additional 3 nos fixed front LED. Relay shall have CB ON-OFF function key & 20 nos disturbance recording. Capacitive voltage indication fixed type system with LED for all feeder and FPI in all load break switch feeder.SF6 Gas pressure indicator on the gas tank.Operating sequence of VCB must be O-0.3Sec-CO-3 Mins-CO amd suitable for 10000 mechanical operation.CT shall be minimum 40/1A ,2.5VA , 5P20 - 3 nos. for protectionRight angle boot to be provided in each module . 2X12V, 26AH Battary with Charger - 1 SetAuxiliary VT shall be 11KV/230V, 500VA for AC supply input to Battary Charger. PCC 1:2:4. type B1 using 20 mm graded aggregate for foundation of RMU as per recommendations of manufacturers of directed by EIC.Note :- (i) Any other parts/items not specified above but have been required essential for smooth and safe functioning of the RMU system shall be deemed included in quoted rate. Make: AREVA /CROMPTON /SIEMENS /SCHNEIDER(ii) The RMU will be tested at site by primary injection test system and submit the test report (iii) The quoted rates shall be deemed to include charges for factory inspection before dispatch the RMU and testing of RMU after installation. |
| 3 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)11000 Volts grade with stranded aluminium conductor of size 95Sqmm 3core and all as directed by Engineer-in-Charge. |
| 4 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 95 Sqmm, 3.5 core laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 5 | Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm complete all as specified and as directed by Engineer-in-Charge.Note :Include excavation and refilling |
| 6 | Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination Heat shrink type joint (End joint) complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm 95 sq mm complete all as specified and as directed by Engineer-in-Charge. |
| 7 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out |
| 8 | Returning, filling in including spreading levelling watering well ramming in layers not exceeding 25cm each complete all as specified and directed. |
| 9 | Removing surplus soil to a distance outside MD land and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. |
| 10 | Material and labour for dry clean river sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning complete all as specified in SSR Part-I and as directed. Note :- Only compacted thickness of sand will be measured and paid separately. |
| 11 | Supplying and laying un-reinforced precast concrete cable cover, class HV Type I, flat, size 300 mm x 180 mm x 40 mm. laid in trenches complete all as specified and directed. |
| 12 | Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type 1, flat as per size 250mm x 150mm x 40mm for LT cable and laid dry in trenches over underground cables complete all as specified and directed |
| 13 | Material and labour , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth strip 32X6 mm by means of bolts, nuts, washerws and check nuts all shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on completion all as per directed.Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II.(ii) Earthing strip and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule.Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge. |
| 14 | Supply and fix of air break gang operated device triple pole mechanically operated witch mounted on 09 Nos insulators and steel frame with GI operating rod of suitable length and size with operating mechanism worked from ground level for current rating up to 200 Amp, 11000 volts vertical type complete. |
| 15 | Supply and fix of expulsion type drop out fuse unit 11 KV, 3 phase fiited with above 25 and upto 50 amp baral fuse 11000 volts and two no of post insulators mounted on channel and vertically mounted complete all as specified and directed by EIC. |
| 16 | Supply and erect Prestressed concrete pole, 11.0 metres long. 152mm x 152mm at top and 152mm x 260mm at bottom, class 9 and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30cm in between 2 bands and numbering of poles, and numbering of the poles shall be done with synthetic enameled painted letter of shape & size complete( Material and labour )all as specified and directed..(Note :including removing all parts /ACSR conductor/HT Cable from repairing pole ) |
| 17 | Material and labour Cross arms, bracings, supports, MS clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint |
| 18 | Material and labour for anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole |
| 19 | Material and labour for PCC (1:3:6) type C-2 using 40 mm graded crushed stone aggregate in foundation, filling and mass concrete for poles/struts etc including necessary formwork as required complete all as specified and directed. |
| 20 | Material and labour for PCC 1:2:4 type B-1 using 20 mm graded aggregates as in copings, kneelers, apex stones, bed plates, kerbs etc., water troughs and the like including weathering, slightly rounded for chamfered angles and throating including necessary form work complete all as specified and as directed. |
| 21 | Material and labour for cable route indicator shown \\"HT UG cables\\" painted in brown colour and root of cable with aero made of CI in suitable eleiptical shape and fixed in MS rod 12mm dia 70 cm long ( all word embosed) and embaded in PCC block of size 30 x 30 x 60cm in ground complete all as specified |
| 22 | Excavation in trences not exc 1.5 m wide and exceeding 1.5 m in depth in hard / dense in hard /dense soil for laying of cable /GI pipe and getting out complete all as specified and directed |
| 23 | Supply and fixing medium grade GI tubing 100 mm bore all as directed by EIC. |
| 24 | Dismantling and removing of existing unserviceable air break switch (GOD) 11 KV with all fittings and fixtures complete from two/ Four pole structure complete. |
| 25 | Dismantling and removing of existing unserviceable expulsion/drop out fuse unit with all fitting complete from the 11 KV two / four pole structure complete. |
| 26 | Supply and fix street light timer panel of capacity 3 phase, 5KW , IP 65, made of polycarbonate,UV ray protected, and contactor of capacity 40A all as specfied and directed (Note : suitable bracket of pole with nut and bolt include) |
| 27 | Supply install testing,commissioning of CRI tested Copper earthing electrode of length 3 metres, 40mm dia and back fill compound of 50kgs ,and conductive gel to retain moisture should be filled layer wise and inter connceted by exothermic brazing & copper strip of size 32x6mm should be suppllied and fix upto testpoint protected by GI pipe of size 50mm dia up to test point including disconnection of old earth strip and fix to new chemical earthing, PCC earth pit of standared size as per SSR part-1 and submmision of earth results and painting of Date of test , value obtain at site and all specified and as directed .(Note;A colour photographe of earthing pit and test report of earthing will be submitted alongwith RAR shall be permitted for that items & Earth pit size 50cm*50cm*30cm (outer measurement) earth pit cover 50cm*50cm*7cm top of cover write MES) |
| 28 | Disconnecting of HV / LV cable from transformer 1MVA 33/11KV /415V at site , and loading and unloading of Transformer at both side from gandhidham all location and repair work premises ,Including hiring of crane and transportation charges all as specfied and directed |
| 29 | Material and labour for comprehensive maintanence of following transformer any type, Opening the top cover of the transformer carefully at site/ workshop and draining of transformer oil, and removing the core and windings for finding out the fault and refixing the same after repairs, refilling and or topping up with new transformer oil confirming to IS-335 of 1993 having suitable dielectric strength ,including all tests of transformer to be done as per standared, cleaning of transformer & its parts using proper cleaner if transformer can not be repaired, the same shall be transported to workshop for carry out repair & rewinding and back to MES as approved by Engineer-in-Charge complete of the follwing sizes:- Note : 1) Transformer oil shall be measured and paid separetely.2) Spare parts will be measured & paid in appropiate item of schedule.3) Opening and assembling of transformer shall be carried out at the presense of JE/AGE.4) Labour charges shall be deemmed to be included for replacement of parts mentioned here-in-before/ here-in-after.5)Test Report after concluding all test shall be submitted with duly signed by licensed technician.6) Transporation shall be deemed to be include in quoted rate.(a) 100 KVA |
| 30 | Removal of burnt HT coil winding and replacement of the same with new copper wire coil including necessary insulation material like impregnated paper or super enamelled and keeping the core and windings in to the hot air oven till the moisture evaporate and achieving proper insulation resistance complete all as directed.(Note: only weight of copper used in winding is measured) |
| 31 | Removal of burnt LT coil winding rewinding of the same with new copper strip including necessary insulation materials and keeping the core and windings in to the hot air oven till the moisture evaporate and achieving proper insulation resistance results complete all as directed.(Note: only weight of copper used in winding is measured) |
| 32 | Supply only HT bushing any type and size complete |
| 33 | Supply only LT bushing any type and size complete |
| 34 | Supply only cracked/wornout synthetic rubberized cork gasket 10 mm thick for top cover of transformer capacity upto 250 KVA complete all as specified and directed |
| 35 | Supply only cracked/wornout synthetic rubberized cork gasket 10 mm thick for tank etc complete all as specified and directed |
| 36 | supply only tap changer switch including all accessories of any capacity |
| 37 | supply only paint from approved brand |
| 38 | supply only temperature gauge any type and size |
| 39 | Supply and replacement of transformer oil confirming to IS 335,having dielectric strength 60 KV completely including opening of top plate of transformer and refixing all as specified and directed by Enginner-in-Charge. |
| 40 | Supply and demo of 3 phase highly insulated FRP telescopic earth discharge rod 11KV and HV test of 110KV, 15 feet length , each rod contain 3 section of total length 15 feet , push button type locking system, Automatic pultrusion plant, FRP pulruded with 4 sqmm copper cable complete all as specified and directed. |
| 41 | Cutting /removing of hurbs,shurbs,upto 25 mm dia girth of bhushes from ground level and grass in the entire area of installation /perimeter around a transformer typically a substation or distrbution point area and deposited outside 100 Mtrs from sub stn ,complete all as specified and directed by Engineer in charge . Note : All Cutting tools shall be provided by contractor and finish work timely. |
| 42 | Dismantaling of any type and size ACSR conductor complete all as specified and directed by Engr-in-Charge. |
| 43 | Dismantaling of stay assembly including demolition of concrete etc complete all as specified and directed by Engr-in-Charge. |
| 44 | Dismantaling of insulator any size and any type complete all as specified and directed by Engr-in-Charge. |
| 45 | Dismantaling of cross arm of MS channel or angle sections any type any size etc complete all as specified and directed by Engr-in-Charge. |
| 46 | Supply and Fixing cable route indicator for HT cable 6 mm thick cast iron plate of size 100 mm dia welded to MS angle iron of size 50 x 50 x 6 mm and embedded in PCC 1:3:6 type C-1 block size 150 x 150 x 150 mm duly painted with brown synthetic enamelled paint complete all as specified and as directed. |
| 47 | Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm complete all as specified and as directed by Engineer-in-Charge |
| 48 | Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm complete all as specified and as directed by Engineer-in-Charge |
| 49 | Supply, fabricate, test and commissioning of factory made HT out door feeder pillar box single door of size 1000x1000x600 mm Including locking arrangement cubical type dust proof, weather proof, vermin proof aesthetically designed, having atleast IP-65 degree of ingress protection, fabricated from 3.15 mm thick CRCA sheet with front & rear opening including bus bar chamber, continuous GI strip earth bus bar, 3 strips of copper bus bar of 400 Amps capacity, insulated color sleeves, porcelain/epoxy insulators, rail channels cable alloy, danger notice board(11000 Volt) including made out of 14 guage MS sheet over angle iron frame of size 50x50×6mm, 60 cm grouted in ground floor and 60 cm above GL including necessary excavation foundation.PCC etc complete duly powder coated of approved color all as directed. |
| 50 | Material and labour Cutting existing road surface or hard standing and repair it after passing the cable through PCC topping 1:2:4 and making good disturbed surface to match with existing levels of road complete all as specified. |
| 51 | Supply and fixing light grade GI tubing 150 mm bore all as directed by E-in-C. Total in Figures 0.0 0.0 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 27 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender