Tender For Repair Maintenance Of Internal Electrification Including Fittings And Fixtures For All Central Institutes And Various Em Installations Under Ge Dinjan
Tender Overview
Project Description
Tender for Repair Maintenance Of Internal Electrification Including Fittings And Fixtures For All Central Institutes And Various Em Installations Under Ge Dinjan
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 25-Aug-2026 | CORRIGENDUM | BOQ | 03-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed. |
| 2 | M&L for point wiring with 1100 volts for One light point or one fan point or bell point controlled by one switch grade PVC insulated FRLSH multistranded copper conductor cable 1.5 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 1.5 sqmm (Green) drawn into and including casing capping 20mm ISI marked ivory colour with all fittings/fixing accessories and terminal boxes of thickness not less than 1.0 mm covered with and including 3mm thick phenolic laminated white sheet cover/ PVC gang box for mounting sheet cover for mounting switches, sockets, fan regulators etc for one light point controlled by one switch complete all as specified and directed. |
| 3 | All as per Ser item No. 02 above but for socket outlet 6 Amps controlled by one switch on independent board complete all as specified and directed. |
| 4 | All as per Ser Item No 02 above but for socket outlet 6 Amps controlled by one switch on the same board with other swithces complete all as specified and directed. |
| 5 | All as per Ser item No 02 above buit for wire 2.5 sqmm size alongwith one earth continuity conductor 2.5 sqmm size complete all as specified and directed. |
| 6 | M&L for point wiring with 1100 for One light point or one fan point controlled by one switch volts grade PVC insulated FRLSH multistranded copper conductor cable 1.5 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 1.5 sqmm (Green) drawn into and including concealed rigid non matalic PVC conduit medium grade size not less then 20mm dia ISI marked ivory colour with all conduit fittings/fixing accessories and unwelded sunken galvnised pressed steel terminal boxes of thickness not less than 1.0 mm covered with and including 3mm thick phenolic laminated white sheet cover/ PVC gang box for mounting sheet cover for mounting switches, sockets, fan regulators etc for one light point controlled by one switch complete all as specified and directed.Note : Rate for cutting chasing and making good the disturbed surface to be include in the quoted price. |
| 7 | All as per item No. 06 above but for socket outlet 6 Amps controlled by one switch on independent board complete all as specified and directed. |
| 8 | All as per Ser item No. 06 above but for socket outlet 6 Amps controlled by one switch on the same board with other swithces complete all as specified and directed. |
| 9 | All as per Ser item No 06 here-in-before but for wire 2.5 sqmm size alongwith one earth continuity conductor 2.5 sqmm size. |
| 10 | S&F Switch piano, flush type single pole, one way 5 Amp,230 V complete all as specified and directed . |
| 11 | S&F Socket outlet 2 in 1, 3 pin, 5 Amp,240 V complete all as specified and directed by . |
| 12 | S&F Switch socket combination 2 in 1, 5 Amp flush type, 240 V complete all as specified and directed by . |
| 13 | S&F Switch socket combination 5A/ 16A, 5 in 1flush type,240V complete all as specified and directed . |
| 14 | S&F Bell push, flush type, 5 amp,230V complete all as specified and directed by . |
| 15 | S & F Bell , AC, 230 Volts, single pole complete all as specified and directed . |
| 16 | S&F Ceiling rose, 3 way PVC insulated body complete all as specified and directed . |
| 17 | S & F stepped type ( five steps), 230 V electronic fan regulator flush type (Socket Type) complete all as specified and directed . |
| 18 | S&F 18 W surface and wall mounted LED Batten with aluminium housing and intigrated. Make:Havells/philips/Bajaj/wipro/crompton complete all as specified and directed. |
| 19 | S&F in repair of LED inverter type batten (1.2M) made of PVC housing sheet housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficiency of 115 lumen per watt and total power consumption not more than 18/20 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete all as specified and directed. Make - Havells Cat Part No. LHEXASP7IN1W020 or equivalent to make as specified in PS. |
| 20 | S&F in repair of LED batten Essential SmartBright MW batten is an Intelligent Standalone solution with micro wave sensors for movement detection. With factory set dimming profiles of 50% and 100%, light dims to these levels in case occupacy is not detected.Type HSN(1.2M) made of PVC housing sheet housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficiency of 115 lumen per watt and total power consumption not more than 18/20 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a colour temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete all as specified and directed. Make - Havells Cat part No. LUMILINESMART20WLED666PCWH or equivalent to make as specified in PS. |
| 21 | S&F in repair 12 W surface mounted downlight with white powder coated polycarbonate housing and pressure die cast heat sink having high efficiency elegantly designed sleek surface mounted including taking down complete all as specified and directed . |
| 22 | S&F in repair 25 W LED building security new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminum housing with hight power LED as lighting source and lens imbedded PC Cover having TOP OPENING seperate driver cmpartment with IP 65 protection and inpact resistance of IK07 including all fixing arrangemengt including taking down. |
| 23 | S&F in repair 9/10W surface and wall mounted LED Batten and taking down . |
| 24 | S&F in repair 15 W surface mounted downlight 1x1 feet with white powder coated polycarbonate housing and pressure die cast heat sink having high efficiency Aesthetically designed 1x1 feet LED Flat panel for surface mounting including taking down complete all as specified and directed. |
| 25 | S&F in repair Decorative city light any type and S & F LED wall bracket light aesthetically designed with B22d & E27 lamp holder made up of Polycarbonate suitable for 9/10 W including suitable LED Bulb complete with all accessories internally pre-wired and including connecting up with twin core twisted flexiblecopper conductor cable with suitable size complete all as specified and directed. |
| 26 | S&F in repair Recess/Surface 42 watt mounted deep drawn PLANO 2X2 feet CRCA housing with higher power LED Seamless front frame with flat white hight transmission acrylic cover all as specified and directed. |
| 27 | S&F in repair Lamp holder , PVC / Polycarbonate type with back plate suitable for batten fitting including taking down complete all as specified and directed. |
| 28 | S&F in repair LED Lamp 9 Watt complete all as specified and and directed. |
| 29 | S&F in repair PVC ractangular block for mounting MCB DB's with 3 mm thick plastic laminated sheet cover of size 250 x 200 x 50 mm deep including taking down complete all as specified and directed. |
| 30 | S&F in repair PVC ractangular block for mounting MCB DB's with 3 mm thick plastic laminated sheet cover of size 175 x 100 x 50 mm deep including taking down complete all as specified and directed. |
| 31 | S&F in repair PVC ractangular block for mounting MCB DB's with 3 mm thick plastic laminated sheet cover of size 100 x 100 x 50 mm deep including taking down complete all as specified and directed. |
| 32 | M & L for Sub main wiring with two runs of 6 sqmm (Nominal area) single core FRLSH cable PVC insulated, multistranded, unsheathed, copper conductor cables 1100 Volts grade drawn through PVC conduits/casing-caping of suitable size, fixed to wall/ceiling etc including 6 sqmm (nominal area) single core, FRLSH PVC insulated, multistranded, unsheathed, FRLSH copper conductor as earth wire and duly connected to common earth point including PVC conduits/casing-caping of suitable size complete all as specified and as directed by Engr-in-charge. (Note : PVC Conduits/Casing-caping, two run wiring cables and one run of earth wire will be measured as one length.) complete all as specified and directed. Please Enable Macros to View BoQ information |
| 33 | M & L for Sub main wiring with two runs of 6 sqmm (Nominal area) single core FRLSH cable PVC insulated, multistranded, unsheathed, copper conductor cables 1100 Volts grade drawn through PVC conduits/casing-caping of suitable size, fixed to wall/ceiling etc including 6 sqmm (nominal area) single core, FRLSH PVC insulated, multistranded, unsheathed, FRLSH copper conductor as earth wire and duly connected to common earth point including PVC conduits/casing-caping of suitable size complete all as specified and as directed by Engr-in-charge. (Note : PVC Conduits/Casing-caping, two run wiring cables and one run of earth wire will be measured as one length.) complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 6 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender