Tender For Interlinking Janatha Feeder And Mamngalam Feeder Constructing 130 Mtr Ht Ug Cable And Cccc Rmu Under Ele. Sec. Palarivattom (Electrical Division, Ernakulam).
Tender Value
11.33 Lakhs
Estimated cost
Bid Submission
02 Sep 2026
15 days left
EMD
28400
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ernakulam → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Interlinking Janatha Feeder And Mamngalam Feeder Constructing 130 Mtr Ht Ug Cable And Cccc Rmu Under Ele. Sec. Palarivattom (Electrical Division, Ernakulam).
BOQ
| Sl. No. | Item Description |
| 1 | Doing one cable end termination on HT XLPE UG cables of sizes beyond 3x185 sqmm and upto and including 3x300 sq mm using the cable jointing kit supplied departmentally after making fencing,caution board and all other safety measures including charges for cable jointer etc. complete as per the direction of the departmental officers. |
| 2 | Loading HT PSC pole to Hand cart from the stacking place and unloading the same at work site (excluding transportation). |
| 3 | Transporting one HT PSC pole by Hand cart - normally limited to 4km (excluding loading and unloading). |
| 4 | Fitting and erecting one HT PSC Single Pole in position, including fitting cross arm, digging and back filling pit in ordinary soil (as per standards), drawing sufficient length of GI earthing leads from F clamp through V cross arm to the ground for earthing (excluding provision of earthing). |
| 5 | Additional rate for excavation of one Pit for HT Pole/HT Stay in Hard Laterite. |
| 6 | Mounting and connecting HT XLPE UG cable ends of all sizes upto and including 3x300 sq mm with special type cable clamps, bolts, nuts, terminal protectors etc.including cost of extra materials if needed and giving necessary jumper connections. |
| 7 | Laying of 11KV UG Cable by Horizontal Directional Drilling method |
| 8 | Transporting Transformers by hired vehicle to a distance upto 5km and carrying upto 2 numbers of 63/100/160/250kVA Transformers / Ring Main Units excluding loading& unloading charges. |
| 9 | Cost of construction of foundation, base plates, fixing anchor bots, loading & unloading, handling, erection, allignment and allied works for the installation of Data Aquisition compatible Extensible type Ring Main Units with terminal protector boots & extension modules, actuators for remote operatios, communicable FPIs, CTs, PTs & relay contacts for SCADA, giving power & control wiring and connections, providing terminal protector, interconnecting RMU bus bar and control cables, providing metered LT supply from nearest LT pole, providing earth leads, cable mounting & terminations, giving connections after ascertaing proper phase sequence, providing location name & warning boards, burying cables & refilling, conducting all precommissioning tests as required, complete, except cost of conveyance. RMUs with two nos load break switches & one VCB |
| 10 | Dismantling three limbed 11kV RMU (CTC, CCC, etc) after disconnecting interpanel busbars (if any), disconnecting cables and packing cable for safety (for lifting), removing cable clamps, bottom plate, removing RMU from foundation bolts,lifting RMU from foundation, unloading to ground/loading to vehicle etc not including transportation cost) |
| 11 | Cost of construction of foundation, base plates, fixing anchor bots, loading & unloading, handling, erection, allignment and allied works for the installation of Data Aquisition compatible Extensible type Ring Main Units with terminal protector boots & extension modules, actuators for remote operatios, communicable FPIs, CTs, PTs & relay contacts for SCADA, giving power & control wiring and connections, providing terminal protector, interconnecting RMU bus bar and control cables, providing metered LT supply from nearest LT pole, providing earth leads, cable mounting & terminations, giving connections after ascertaing proper phase sequence, providing location name & warning boards, burying cables & refilling, conducting all precommissioning tests as required, complete, except cost of conveyance. Additional rate for RMUs with one additional Load Break switch / VCB |
| 12 | Providing one Earth using GI earth pipe of size 38.1mm dia, 2.5m length including digging separate pit (0.45x0.45x2.5m) at a minimum distance of 1.5m away from the pole/structure and maintaining standard distance between different earth pipes in ordinary soil & backfilling. |
| 13 | Additional rate for excavation of one Earth Pit (2.5m depth) in Hard Laterite. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysSep 07, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender