Tender For Maintenance Of Street Lights, High Masts On Delhi Pwd Roads Under Pwd M-South Division During 2026-27. (Sh : Supply Installation Testing and Commissioning of Street Light Fittings And Miscellaneous Electrical Works At Devli Road Under M-So
Tender Overview
Project Description
Tender for Maintenance Of Street Lights, High Masts On Delhi Pwd Roads Under Pwd M-South Division During 2026-27. (Sh : Supply Installation Testing and Commissioning of Street Light Fittings And Miscellaneous Electrical Works At Devli Road Under M-South Division)
BOQ
| Sl. No. | Item Description |
| 1 | Fabrication, Installation, Testing and Commissioning of floor mounting double door minimum 300 mm depth with locking arrangement front and rear openable, totally enclosed, compartmentalized, dust, vermin proof and outdoor type Feeder Pillar (IP54) fabricated out of 2mm thick cold rolled carbon annealed sheet steel, (minimum) surface area 1.50 Sq.Mtr, with 300 Amp 4 strip AL. bus bar, cable alley on both sides, powder coated paint of approved shade after 7 tank cleaning process and 1 no 20x3mm GI strips throughout the width of feeder pillar consisting two earth studs on each strip complete with provision for incoming and outgoing switchgears including making connections/ inter connections with lugs/ thimble for switchgears and control wiring with 2.5 sq.mm PVC insulated FRLS copper conductor cable, including providing 50mm X 50mm X 6 mm thick (NS) 90 cm long legs out of which 45 cm duly grouted in existing cement concrete 1:2:4 etc complete as reqd. (Drawing shall be got approved from Engineer-incharge before fabrication) |
| 2 | Incomer:- |
| 3 | 200A TP 25KA MCCB WITH SPREADER LINK (Ics=100%Icu) : 01 No. |
| 4 | Metering:- |
| 5 | DIGITAL AMMETER (0-200) WITH SELECTOR SWITCH: 01 No. |
| 6 | DIGITAL VOLT METER (0-500) WITH SELECTOR SWITCH : 01 No. |
| 7 | INDICATION LED LAMP RYB : 03 No. |
| 8 | 2A SP MCB : 03 No. |
| 9 | 200/5A CT CLASS-1: 03 No. |
| 10 | Out going :- |
| 11 | 100A TP 16KA MCCB WITH SPREADER LINK (Ics=100%Icu) : 03 Nos |
| 12 | 110A TP POWER CONTACTOR 220V: 01 No. |
| 13 | DIGITAL TIMERS: 01 No. |
| 14 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required: 01 Set |
| 15 | Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 16 | 150 watt |
| 17 | Supplying and fixing of Following sizes PVC Round Sheathed Multi Core Industrial Flexible unarmoured Aluminium conductor Cable in the surface of wall/ceiling/ in street light poles etc with the help of suitable size clamps etc complete as reqd.a) 3 core 2.5 sq. mm |
| 18 | Supplying & laying of one number 4 x 16 sq.mm XLPE insulated and PVC sheathed Aluminium conductor armoured power cable of 1.1 KV grade in the follwing manner etc as complete reqd.. |
| 19 | a. On wall surface as required. |
| 20 | Supplying & laying of one number 4 x 25 sq.mm XLPE insulated and PVC sheathed Aluminium conductor armoured power cable of 1.1 KV grade in the follwing manner etc as complete reqd.. |
| 21 | a. On wall surface as required. |
| 22 | Supplying & laying of one number 3.50 x 50 sq.mm XLPE insulated and PVC sheathed Aluminium conductor armoured power cable of 1.1 KV grade in the follwing manner etc as complete reqd |
| 23 | a. On wall surface as required. |
| 24 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 25 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. |
| 26 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 27 | 4 X 25 sq. mm (28mm) |
| 28 | 3½ X 50 sq. mm (35mm) |
| 29 | Suppyling, Installation, Testing and commissioning S.M.C junction box 185x165x60 complete with terminal block suitable for 25 sq. mm conductor, DIN bar, SP MCB with suitable. M.S. clamp on the existing pole for light fixture etc as required |
| 30 | Fabricating supplying and fixing wiremesh frame work made out of 40x40x6mm thick angle iron having 40x6mm flat strip & wiremesh 6 swg dia m.s wire with 25mmx75mm space in between mesh & top covered for rain protection by 16 SWG MS Sheet and making main door gate having suitable locking arrangement with godown lock (Frame size shall not be more than 60 cm x 90 cm) i/c grouting with cement concrete & primer and spray painting with super synthetic enamel paint of approved colour quality etc as reqd. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender