Tender For Repair/Maintenance Of Lt External Electric Supply At installation Pallava Under Ge (Navy) Chennai
Tender Value
8 Lakhs
Estimated cost
Bid Submission
02 Sep 2026
9 days left
EMD
16000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Chennai → Tamil Nadu
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Maintenance Of Lt External Electric Supply At installation Pallava Under Ge (Navy) Chennai
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.5 mtrs wide and not exceeding 1.5 mtr deep in hard /dense soil for laying underground cables, laying pipes etc. complete all as specified and directed. |
| 2 | Returning filling in including spreading levelling watering and well ramming in layres not exceeding 25 cm thick in hard/ dense soil complete all as specified and directed. |
| 3 | Removing surplus soil to a distance not exceeding 50 m and depositing at a level not exceeding 1.5m above the starting point all as specified and directed. |
| 4 | Supply and fixing in replairs High density poythelyne (HDPE) pipes of pressure rating 6kgf/ sq/ m of size 50 mm for cable protection laid in trenches complete all as specified and directed |
| 5 | Supply and fixing in replairs High density poythelyne (HDPE) pipes of pressure rating 6kgf/ sq/ m of size 75 mm for cable protection laid in trenches complete all as specified and directed |
| 6 | Supply and fixing in replacement of High density poythelyne (HDPE) pipes of pressure rating 6kgf/ sq/ m of size 100 mm for cable protection laid in trenches complete all as specified and directed |
| 7 | Taking up or down steel tubing size 25 or 32 and connections,and taking into credit complete all as specified and as directed by the Engineer-in-Charge complete. |
| 8 | Supply and lay in trenches, fixed to wall / pole/ tray including connecting cable with cable termination end sockets into terminal switches etc UG cable XLPE insulated armoured heavy duty electric UG cable with aluminum conductor 1100 volts grade of cross sectional area of following size all as specified and as directed. |
| 9 | 3 Core 16 Sqmm |
| 10 | 4 core 16 Sqmm |
| 11 | 3.5 Core 25 Sqmm |
| 12 | 3.5 Core 50 Sqmm |
| 13 | 3.5 Core 70 Sqmm |
| 14 | 3.5 Core 95 Sqmm |
| 15 | Disconnecting taking out from trenches / pole out lived LT UG cable of size as mentioned under Item No.8.1 to 8.6 above.and taking old unserviceable LT UG into credit complete all as specified and as directed by the Engineer-in-Charge complete.Note : Excavation and earth work will be measured and paid separately. |
| 16 | Repair/Replacement of UG Cable Gland size 1/2 Inch (12mm) |
| 17 | Repair/Replacement of UG Cable Gland size 3/4 Inch (18mm) |
| 18 | Repair/Replacement of UG Cable Gland size 1 Inch (25mm) |
| 19 | Repair/Replacement of UG Cable Gland size 1 1/2 Inch (38mm) |
| 20 | Repair/Replacement of UG Cable leg size 2.5mm to 6mm |
| 21 | M/L for Cable route indicator CI disc of size 100mm dia x 3mm thick marked as \\"MES LT Cable\\" or \\"MES HT Cable\\" including angle iron pedestal and grouting complete |
| 22 | M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanized iron strip 25 x 4 mm as earthing lead connected by means of bolts, nuts, check nuts and washer of galvanized iron or steel, provision of 40 mm dia GI pipe light grade for protection of GI strip upto 7.5 meter long and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, GI funnel, wire gauge, 50 mm thick RCC 1:2:4, type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance not exceeding 50 metre, provision of charcoal and salt, lifting handle, GI funnel, wiremesh, lugs etc.. as shown in electrical plate No 3 of SSR Part-I (2009) complete all as specified and directed. |
| 23 | Supply and fix MCCB four pole 415 volts, 50 Hz, 25 to 100 amps, with rupturing capacity 16 KA complete all as specified and as directed including taking down old unserviceable MCCB for taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
| 24 | Supply and fix MCCB four pole 415 volts 50 Hz , 160 amps, with rupturing capacity 36 KA complete all as specified and as directed including taking down old unserviceable MCCB for taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
| 25 | Supply and fix MCCB four pole 415 volts, 50 Hz , 250 amps, with rupturing capacity 36 KA complete all as specified and as directed including taking down old unserviceable MCCB for taking into credit complete all as specified and as directed by the Engineer-in-Charge . |
| 26 | Supply and fix in repairs RCBO 4 Pole,100mA, 415 volts 63 Amps with Front face indication for earth leakage fault IP 20 protected terminals 35 sq mm terminals Sliding shutters. Complete all as specified and as directed by Engr-in-charge.Make:- Legrand Cat Part No 4113 35. or its equivalent in Havells/L&T/C&S. |
| 27 | Supply and fix in replairs ON load change over switch having current rating 200 Amps, 415 volts, 50 Hz, 4 pole with steel sheet encls conforming to IS :13947 (part-3), IEC : 60947-3, complete all as specified and directed. |
| 28 | Supply and fix in repairs Hot Press Moulded SMC boxes size 195 X135 X90 mm internal size with hinged door(L) with and incl one No MCB SP 6 Amps, connector 4 way 16 Amps including fixing clamps, nut bolts etc complete as street light terminal boxes |
| 29 | S&F Terminal strip RYB 4 way Flat or ribbon cable Nut & bolt connector Suitable 4 core 10 sqmm cable. complete all as specified and as directed |
| 30 | Supply and fix in repairs SP 63 amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) fixed in the MCB DB complete with connection testing and commissioning |
| 31 | Supply and fix in repairs of SP 6 to 32 Amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) fixed in the MCB DB complete with connection testing and commissioning |
| 32 | Supply and fix in replacement of r 415V 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning (i) TPN 40 to 100 Amp |
| 33 | Supply and Fix in replacement 2.2 sqmm industrial cable with copper conductor PVC round sheathed (flexible) |
| 34 | M&L for painting the Panel boards/DB Boxes/covers/DG Set/Accoustic Enclosures as required at site after scraping out completely the old paint and applying one coat of redoxide primer and two coats of synthetic enammel paint including carrying out minor welding works if required as directed by the Engineer in chargeNOTE:Colour of paint shall be decided by the Engineer-in-charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysSep 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender