Tender For maintenance of electrical installation & Fans And repair maintenance Drinking Water Supply Pump Sets, Sub-Station & Distribution System Dg Sets & Ac Equipments Including Heating System Installed At Igdtuw, Kashmere Gate, Delhi. (Sh:- Renov
Tender Overview
Project Description
Tender for maintenance of electrical installation & Fans And repair maintenance Drinking Water Supply Pump Sets, Sub-Station & Distribution System Dg Sets & Ac Equipments Including Heating System Installed At Igdtuw, Kashmere Gate, Delhi. (Sh:- Renovation Of Toilet At Admin Block & Joint Admission Council Room Near The Ncc Block, Igdtuw, Kashmere Gate).
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.(a) Group C |
| 2 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 3 | (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 4 | (c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. (a) Group C |
| 6 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 & 5/6 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required. |
| 7 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. (a) 6 Module (200 mmX75 mm) |
| 8 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.(a) 15/16 A switch |
| 9 | (b) 6 pin 15/16 A socket outlet |
| 10 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(a) 8 way |
| 11 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) Single Pole |
| 12 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. As required. (a) 40A |
| 13 | Earthing with G.I. earth pipe 4.5 meters long, 40 mm diameter including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 14 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 15 | Providing and fixing of 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 16 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 17 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness >0.50 mm)14.01) 18-22 watt |
| 18 | Supplying and installation following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. (a) 100 mm width X 50 mm depth X 1.6 mm thickness |
| 19 | b) 150 mm width X 50 mm depth X 1.6 mm thickness |
| 20 | Supplying, Installation, Testing and Commissioning of 250 mm Sweep metal body Heavy Duty ISI Marked Exhaust fan including making good the same, connection, testing, commissioning etc. as reqd. |
| 21 | Supplying, Installation, Testing and Commissioning of 250 mm sweep plastic body fresh air fan working on 230 +/- 10 V single phase 50 Hz Frequency complete with shutter in existing hole of suitable size making good the same i/c connections, interconnections etc. complete as reqd. |
| 22 | Supplying, laying and fixing of following sizes XLPE insulated PVC sheathed aluminum conductor armoured cable of 1.1 KV grade on surface etc complete as required.a) 3 X 16 Sq.mm |
| 23 | Supplying, Installation, Testing and Commissioning of Stainless Steel wall mounted Automatic Hand Dryer with Fast-dry, energy efficient, rust proof, water proof and ISI & BIS certified etc. complete as reqd. |
| 24 | Less credit/buy back of following electrical accessories to contractor etc. complete as required.(a) Assorted copper wire/cable/pipe |
| 25 | (b) Scrap iron/ conduit/ box |
| 26 | (c) DBs (assorted size) |
| 27 | (d) MCBs (assorted size) |
| 28 | (e) Switch/Socket (assorted size) |
| 29 | (f) Fresh Air Fan (assorted size) |
| 30 | (g) Batten Lights (assorted size) |
| 31 | (h) Assorted XLPE aluminum cable Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender