Tender For Certain Repair/ Maintenance To Main Reciving Stations At Aundh Military Complex And At Range Hills Area, Including Replamcenet Of Lt Ari Cicuit Breakers/ Mccbs, Replacement Of Old Ug Cables At Sub Station Aor Of Ge (Mh & Rh) Khadki And Rep
Tender Overview
Project Description
Tender for Certain Repair/ Maintenance To Main Reciving Stations At Aundh Military Complex And At Range Hills Area, Including Replamcenet Of Lt Ari Cicuit Breakers/ Mccbs, Replacement Of Old Ug Cables At Sub Station Aor Of Ge (Mh & Rh) Khadki And Repair/ Maintenance & Replacement Of Lt Pannels/ Sutters, Replacement Of Controls, Replacement Of Old Jointed Ug Cables, Replacement Of Of Submersible Cables, Replacement Of Star Delta Starter Including Replacement Of Butterfly Valve/Sluice Valve Of Any Dia Located At Stp Installation Under Aor Of Ge (Mh & Rh) Khadki
BOQ
| Sl. No. | Item Description |
| 1 | Supply & fixing , testing and commissioning of ACB 4 pole , 415 Volts, 630 Amps, 50KA Manual Draw out type with microprocessor based LSIG & inbuilt temprature rise protection consisting of digital LCD display with battery back up,Current Metering and RS 485 Port. conforming to IS/IEC 60947-2 complete with all accessories , including dismantling old ACB from the existing panel , complete all as specified and as directed by Engr-in-charge. Make :- Legrand/Havells/ABB/L&T |
| 2 | Supply & fixing , testing and commissioning of ACB 4 pole , 415 Volts, 800 Amps, 50KA Manual Draw out type with microprocessor based LSIG & inbuilt temprature rise protection consisting of digital LCD display with battery back up,Current Metering and RS 485 Port. conforming to IS/IEC 60947-2 complete with all accessories , including dismantling old ACB from the existing panel , complete all as specified and as directed by Engr-in-charge. Make :- Legrand/Havells/ABB/L&T |
| 3 | M& L for trimming of tree branches with in 2.0 mtr on either side of the electric line/ poles with suitable T & P and depositing the waste as directed . |
| 4 | M&L for cleaning of MES electric supply installations/campus/complaint cell area by surface dressing or trimming of natural ground to remove small unequalities (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete for the various sub stations. |
| 5 | Material and labour of Synthetic insulating mat confirming to IS 15652:2006 of size 2mx1m ,3 mm thick for voltage up to 22 kv all as specified and directed by Engr in charge. |
| 6 | M&L for hardcore of gauge n.exc 63 mm ,deposited, spread, and levelled in layers n.exc 15 cm thickness (below or above ground level) ,water and rammed to a true shape with broken bricks and making good all as specified and directed by Engr-in-Charge. ( Sub Station Yard) |
| 7 | Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable in replacement with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugs of appropriate size, pvc sleeve etc including dismantling of old LT cables complete all as directed by Engineer in -Charge for following sizes . Make :- Havells / Gloster / Finolex / PolycabNOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schdule . |
| 8 | 70 sq mm 3.5 core |
| 9 | 50 sq mm 3.5 core . |
| 10 | 35 sq mm 3.5 core |
| 11 | 25 sq mm 3.5 core |
| 12 | 16 sq mm 4 core |
| 13 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed. |
| 14 | Ditto item no 8 but in hard/dense soil. |
| 15 | Removing excavated material soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed |
| 16 | Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed. |
| 17 | M & L for riddled earth for cushioning to under ground electric cable including spreading , levelling and hand punning complete all as directed. Note - Punned thickness shall only be measured & paid . |
| 18 | M& L for road cutting / foot path and making good with PCC 1:3:6 TYPE C-2 ( using 40 mm graded stone aggregate ) of 150 mm |
| 19 | M&L un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mm for Under ground cable all as specified and directed. |
| 20 | Supply and laying GI tubes light grade, galvanized, 40 mm bore in repair ,laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed |
| 21 | Ditto item no -15 but 80 mmm bore. |
| 22 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size 25 to 50Sqmm 3.5/4 core cable complete all as directed . |
| 23 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 70 up to 120 sq mm3.5/4 core cable complete all as directed . |
| 24 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 150 to 185 sq mm 3.5/4 core cable complete all as directed . |
| 25 | Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 240 to 300 sq mm 3.5/4 core cable complete all as directed . |
| 26 | M&L for replacement of PVC insulated, PVC round sheathed multistranded copper, unarmoured copper cable round in shape of size 2.5 Sqmm 3 core with multistanded copper conductor inluding taking down complete all as specified and directed by Engineer-in- charge. . |
| 27 | M&L for replacement of submersible cable round/flat of 4 core 6 Sqmm with multistanded copper conductor including taking down complete all as specified and directed by Engineer-in- charge. . Please Enable Macros to View BoQ information |
| 28 | M&L for replacement of submersible cable round/flat of 4 core 6 Sqmm with multistanded copper conductor including taking down complete all as specified and directed by Engineer-in- charge. . Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender