Tender For Electrification Of Construction Of Building For Animal House For Department Of Zoology At New C Us,University Of Jammu.
Tender Value
26.18 Lakhs
Estimated cost
Bid Submission
31 Aug 2026
0 days left
EMD
52361
Bank guarantee accepted
Document Fee
1180
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jammu → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Electrification Of Construction Of Building For Animal House For Department Of Zoology At New C Us,University Of Jammu.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point/fan point/ceiling fan point/exhaust fan point/call bell point with 1.5 Sq. mm FRLS PVC insulated, copper conductor cable in surface/recessed medium class PVC conduit, with piano type switch, phenolic, laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq mm. FRLS PVC insulated copper conductor single core cable etc. as required. (Wire Make ISI Marked Havells/Anchor /HPL /KEI/Polycab Conduit Make - ISI Marked Anchor/High Power /AKG/Equivalent make of required specification to be approved by the Engineer In charge (Group ‘B’) |
| 2 | Wiring for circuit/sub-main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.(Wire Make ISI Marked Havells/Anchor/HPL/KEI/polycab/) Equivalent make of required specification to be approved by the Engineer In charge) i.2x1.5 Sq mm + 1x1.5 Sq mm |
| 3 | ii.2x2.5 Sq mm + 1x2.5 Sq mm |
| 4 | iii.2x6 Sq mm + 1x6 Sq mm |
| 5 | iv.4x6 Sq mm +2x6 Sq mm |
| 6 | v.4x10 Sq mm +2x6 Sq mm |
| 7 | Supplying and fixing of following sizes of medium class PVC conduit along with the accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required- ISI Marked Anchor/High Power /AKG/) Equivalent make of required specification to be approved by the Engineer In charge 25 mm dia |
| 8 | Supplying and fixing 5 Amp to 32 amps rating, 240/415 volts, 10 KA C curve miniature circuit breaker of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. i. Single pole (Make Havells /Anchor/ C&S/HPL/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 9 | Supply and Fixing following ratings, Four pole, 415 volts, isolator in the existing MCB DB Complete with connections, testing and commissioning etc. as reqd. 63 Amp ratings (Make Havells /Anchor/ C&S/HPL/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 10 | Supply and Fixing following ratings, four pole, 415 volts, isolator in the existing MCB DB Complete with connections, testing and commissioning etc. as reqd. 100Amp ratings (Make Havells /Anchor/ C&S/HPL/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 11 | Supplying and fixing 3 pin, 5 A Ceiling Rose on the existing junction box/wooden block including connection etc. as required. (Make Havells/ Anchor / Sanchi Major Equivalent make of required specification to be approved by the Engineer In charge) |
| 12 | Supply and drawing UTP 4 Pair Cat 6 LAN Cable in the existing surface/recessed steel/PVC conduit as required (Make Legrand /Havells / Anchor/D Link /HPL/L&T Equivalent make of required specification to be approved by the Engineer In charge)1 run of cable |
| 13 | Supply and fixing of metal Box of following size on the surface/recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. 200mm x 125mm x 60mm deep |
| 14 | 100mm x 100mm x 60mm deep |
| 15 | Supply & fixing 15/16 amp piano type switch on the existing switch box or cover including connection as required. (Make: Anchor/Havells /HPL/Great White/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 16 | Supply & fixing 6 pin 15/16 amp socket outlet on the existing switch box or cover including connection as required (Make: Havells/ HPL/ Anchor/Great White/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 17 | Supply & fixing 5/6 amp piano type switch on the existing switch box or cover including connection as required (Make :Havells/ HPL / Anchor /Great White/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 18 | Supply & fixing 3 pin 5/6 amp socket outlet on the existing switch box or cover including connection as required(Make: Havells/ HPL / Anchor /Great white/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 19 | Supplying and fixing following ways horizontal type three pole , and Neutral, sheet steel MCB Distribution Board 415V on surface/in recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections including powder painted earthing etc. as required (But without MCB/RCCB/Isolators. i.8 way(4+18), Double door Havells/Anchor /I.A /HPL/ Equivalent make of required specification to be approved by the Engineer In charge |
| 20 | Supply & fixing two module stepped type electronic fan regulator on the existing modular plate/switch box including connections but excluding modular plate etc. as required. (Make Havells/ HPL / Anchor /SSK/ C&S/Great White/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 21 | Supplying and fixing brass batten/Angle holder including connection etc. as required. (Make Havells/ HPL / Anchor / C&S/Great White/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 22 | Providing and fixing following rating and breaking capacity MCCB with Thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Make Anchor /Havells /HPL/I.A/ Equivalent make of required specification to be approved by the Engineer In charge) 630 AMP 50K FP MCCB |
| 23 | 400 AMP 50K FP MCCB |
| 24 | 100 AMP 16K TP MCCB |
| 25 | Supplying and drawing of following sizes of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required (Wire Make ISI Marked Havells/HPL/Anchor/KEI/Polycab/ Equivalent make of required specification to be approved by the Engineer In charge) i.1x1.5 sqmm |
| 26 | iii.2x6 sqmm |
| 27 | Earthing with Copper earth plate 600mm x 600mm x 3mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/coke and salt as required. |
| 28 | Providing and fixing 4mm dia copper wire on surface or in recess for loop earthing as required. |
| 29 | Part-B (Non Schedule items) Supply &Installation of following type of surface mounted/recessed mounted decorative Indoor Linear energy saving , energy efficient LED Lumainiers complete with connection testing and commissioning. Make (Halonix/ Havells/ Syska/Bajaj/ Greatwhite/ Philips/HPL/ Equivalent make of required specification to be approved by the Engineer In charge)a. 18 to 22watt, 220volts, 50Hz, 1200mm with rated input 140V to 270V,lumen efficiency 100 lumens/watt,driver efficiency 90%,starting voltage 90v,Thd<20,CRT>80, CT6500K,Life 25000 hours,surge 2.5 KV,P.F=0.95,made of high grade polycarbonate body LED batten complete. |
| 30 | 2X2 Recess Led Panel 595X595mm 36W +/- 1W Recess mounted fixture with minimum system efficiency of 100lm/W and minimum 3800 lumens, P.f is 0.9 with THD 10% CRI 80 the Led with life of 50000hrs.the LEDs used in the luminaries shall have CCT of 5700K to 6500K with CRI of minimum 80 Protection of 3kV. Make (Halonix/ Havells/Bajaj/HPL/Compact) Equivalent make of required specification to be approved by the Engineer In charge) |
| 31 | Supply, testing and commissioning of PVC sheathed Aluminum conductor 1100 volts graded PVC AA Armoured/unarmoured XLPE Cable including end termination, crimping, cost of thimbles, nuts bolts, glands, connection, testing and commissioning complete job. (Make: Havells / General/Polycab / Gloster/Klick Equivalent make of required specification to be approved by the Engineer In charge)3 ½ core 25 sq mm armoured cable |
| 32 | 3 ½ core 150 sq mm armoured cable |
| 33 | 2 core 16 sq mm armoured round cable 3 1/2 core 95 sqm |
| 34 | Supply, installation, testing, commissioning of 1200 mm sweep ceiling fans complete with blades BEE 3 to 5 star rated energy efficient .(Make: Havells /Anchor/Orient/Crompton/USHA Equivalent make of required specification to be approved by the Engineer In charge) |
| 35 | Supply, installation, testing, commissioning of heavy duty 300 mm sweep BEE 3 to 5 star rated energy efficient exhaust fan.Make: ( Anchor/Havells/Bajaj/Crompton/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 36 | Providing/fixing 40 amp rating , 230 volts SPN MCB in the existing MCB DB or enclose complete with connection testing and commissioning complete Job. (Havells/Anchor/HPL/ Equivalent make of required specification to be approved by the Engineer In charge) |
| 37 | Supplying and fixing following ways horizontal type MCB Distribution Board 415V on surface/in recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections including powder painted earthing etc. as required (But without MCB/RCCB/Isolators. i.4 way, For A.C Havells/Anchor /I.A /HPL/ Equivalent make of required specification to be approved by the Engineer In charge |
| 38 | Supply/installation, testing and commissioning of the following type of outdoor LED type floodlight /Street lights with Operting Voltage 110v to 270v AC,50 Hz,IP65/IP67/IP68, PF.0.95,Lumen 110lumen/watt,Life 50,000hours,beam angle greater than 120 degree,CCI 30000 to 65000K,housing in non corrosive hardware made up of Aluminium. Make (Bajaj/Anchor/Surya /Havells/ HPL/ Equivalent make of required specification to be approved by the Engineer In charge)A.45 to 60 Watt LED. |
| 39 | Supply and fixing of following rating onload I-O-II Four pole with advanced neutral on load change over switch confirms to IS 13947 (Part-3) IEC:609473) (Make I.A/Havells/HPL/Crompton200 Amp |
| 40 | Providing/fixing following way PVC gang box suitable for following socket and switches. (Havells/Anchor/HPL make Equivalent make of required specification to be approved by the Engineer In charge)i.3 pin 5 Amp socket with switch |
| 41 | ii.6 pin 15 amp socket with switch |
| 42 | Supply & installation of CAT 6 2 module toll less information outlets complying fully or exceeding with category 6 connecting hardware specifications for all pair combinations upto 250 MHz. Outlets shall use lead frame technology, non PCB pyramid type complete as required.(Make Legrand/Delton/Havells/HPL/Anchor) |
| 43 | Supply Erection and commissioning of 4m swage type MS tubular Pole painted with two coats of Red oxide and two coats of Silver paint finish welded with (300X300X5) mm base plate including digging of pit and back filling the p[it with cement concrete 1:3:6 (1 cement, 3 Fine Aggregate and 6 Corse Aggregate of 30mm nominal size. The pit shall be planted 1/6th of pole height suitable for 15 to 20 watt LED type post Lantren Fitting with Globe including earthing nuts bolts the dia of bottom, middle, and Top swaged should be 3\\" 2\\"6'and 2\\" respectively. |
| 44 | Design, manufacture, testing at works & supply, installation, testing & commissioning cubicle panel floor mounted (on base frame) totally enclosed and extensible type . The general construction shall comprise to IS 8623-93. The design shall include all provisions for safety of operating and maintenance personal. IP 42 for indoor and IP54 for outdoor, shall be compartmentalized type having space and arrangements for I/C. cable/bus ducting/incoming switch gears, bus couplers, insulated and properly supported compartmentalized switch gear, outgoing compartmentalized switch gear, bus bar support and terminations, interconnection between bus bars & switch gear with auxiliary bus bars/ insulated conductors/strips etc. (Make Electric Field/ Bharti Engineers/Gupta & Friends/ Jai maa/KED equivilant make of required specification to be approved by engineer in charge MAIN NORMAL CUM EMRENGECYa. INCOMING Space for 1 No. 400 Amp MCCB 35 kA and Space for 1 no. Change Over of 200Ab. INDICATING PANELThe indicating panel of the incomer shall be provided with the following:i. Ammeter of required range with ASS, CT's.ii.Voltmeter of required range with VSS.c. BUS BARSpace for 1 No. 400 Amp TPN Al. Bus bar of equal cross section for power load.d. OUTGOINGSpace for 5 No. 100Amp 4 pole MCCB Dimensions4’x 4' x 1’6” |
| 45 | Main Outdoor Building Control Panel MAIN NORMALa. INCOMING Space for 1 No. 600A TPN Al. bus bar of equal cross section to feed power to the Main MCCB of building Space for 1 No. 630A FP MCCB for power load/light/A.C load of Building. OUTGOING Space for 1 No. 600A TPN Al. bus bar of equal cross section with drilled hole for taking connection to the existing ground Floor panel anf feed power to Main MCCB of 2nd Floor New building Dimensions4'0\\"x3’0\\"x1’0” |
| 46 | Supply, testing and commissioning of PVC sheathed Aluminum conductor 1100 volts graded PVC AA Armoured/unarmoured XLPE Cable including end termination, crimping, cost of thimbles, nuts bolts, glands, connection, testing and commissioning complete job. (Make: Havells / General/Polycab / Gloster/Klick Equivalent make of required specification to be approved by the Engineer In charge) 3 1/2 core 95 sqm armoured Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 31, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
TodaySep 02, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender