Tender For Repair/Maintenance Of Lt External Electric Supply At Zone A And Comprehensive Maintenance Of Boom Barrier And Tyre Ripper At installation Adyar And Inas 313 Meenambakkam Under Ge (Navy) Chennai
Tender Value
35 Lakhs
Estimated cost
Bid Submission
02 Sep 2026
18 days left
EMD
70000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Chennai → Tamil Nadu
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Maintenance Of Lt External Electric Supply At Zone A And Comprehensive Maintenance Of Boom Barrier And Tyre Ripper At installation Adyar And Inas 313 Meenambakkam Under Ge (Navy) Chennai
BOQ
| Sl. No. | Item Description |
| 1 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed by engineer in charge . Note :- laying of cable route is same as old cable route |
| 2 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 10 sq mm 2 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 3 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 16 sq mm 4 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 4 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 25 sq mm 4 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 5 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 50 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 6 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 120 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 7 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 150 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 8 | Supply and laying LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 240 sq mm 3.5 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed. |
| 9 | Excavation in trenches in hard/dense soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of cables and getting out excavated material complete all as specified and directed. |
| 10 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed. |
| 11 | Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed. |
| 12 | Supply and lay High density poly ethylene pipes(HDPE) of pressurerating PN 10 of size 50mm or suitable size for laying cables laid in trenches complete all as specified and directed. |
| 13 | Supply and lay High density poly ethylene pipes(HDPE) of pressurerating PN 10 of size 75mm or suitable size for laying cables laid in trenches complete all as specified and directed. |
| 14 | Supply, fixing and laying GI tubes light grade ISI mark of 50 mm dia sizes with all fitting and fixed with pole, wall and passing of cable as directed at site ( MS work such as clamps, nuts, bolts, shall be measured and paid separately):- |
| 15 | All as per item No 14 herein before but 40 mm dia |
| 16 | All as per item No 14 herein before but 32 mm dia |
| 17 | M & L for Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 25-35 sqmm 3.5 core all as directed. |
| 18 | M & L for Straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 120-185 sqmm 3.5 core all as directed. |
| 19 | Material & Labour for MCCB 63 Amps 16 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 20 | Material & Labour for MCCB 100 Amps 16 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 21 | Material & Labour for MCCB 125 Amps 16 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 22 | Material & Labour for MCCB 160 Amps 36 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 23 | Material & Labour for MCCB 250 Amps 36 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 24 | Material & Labour for MCCB 400 Amps 50 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 25 | Material & Labour for MCCB 630 Amps 50 KA, 4 Pole including testing and commissioning and dismantling of old MCCB complete all as specified and directed by Engineer-in-Charge. |
| 26 | Supply & fixing MCB TPN 100 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed. |
| 27 | Supply & fixing MCB TPN 63 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed. |
| 28 | Supply & fixing MCB TPN 32 amps of 10 KA in existing panel with incoming and outgoing connection complete all as directed. |
| 29 | M&L for roughning and removing old painting from the LT panels by paint removers, cleaning with scrapes and preparing the surface and applying one coat of painting complete to LT panel with synthetic enamel paint of existing colour and writing details of incoming and outgoing complete all as directed. |
| 30 | Shifting carefully transformer / DG Set of capacity 100 to 500 KVA, 11000 V/415 V from one substation to another substation including disconnecting HV/LV cables, earthing connections etc and reconnecting all connections after installation complete in all respects all as directed. |
| 31 | S&F Mild Steel Chequered Plate of 6 mm thick for Cable Duct Cover and 45 x 45 x 6 mm angle iron, cut into required pieces and lifting groove and placing over angle iron conforming to Fe 410-W (Gde-E- 250) quality-A complete all as specified and as directed. |
| 32 | Supply & fix aluminium lugs for 50 sqmm to 70 sqmm 3.5 core cable complete all as specefied and as directed |
| 33 | Supply & fix aluminium lugs for 95 sqmm to 120 sqmm 3.5 core cable complete all as specefied and as directed |
| 34 | Supply & fix aluminium lugs for 240 sqmm to 300 sqmm 3.5 core cable complete all as specefied and as directed |
| 35 | M & L for earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 32x6 mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I including testing complete. Please Enable Macros to View BoQ information |
| 36 | M & L for earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 32x6 mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I including testing complete. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysSep 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender