Housing Urban and Rular Development Local Bodies Closing in 16 days TDR #57009302

Tender For Work Of External Electrification In Madhuban Bapudham Pocket-A.

Issued by Local Bodies · Ghaziabad, Uttar Pradesh
Tender Value
21.49 Crore
Estimated cost
Bid Submission
09 Sep 2026
16 days left
EMD
42.98 Lakhs
Bank guarantee accepted
Document Fee
18054
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ghaziabad → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Work Of External Electrification In Madhuban Bapudham Pocket-A.

BOQ

Name of Work:- Work of External Electrification in Madhuban Bapudham Pocket-A.
Sl. No. Item Description
1Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.10 sq. mm 4 core
216 sq. mm 4 core
325 sq. mm 3-1/2 core
435 sq. mm 3-1/2 core
550 sq. mm 3-1/2 core
670 sq. mm 3-1/2 core
795 sq. mm 3-1/2 core
8120 sq. mm 3-1/2 core
9150 sq. mm 3-1/2 core
10185 sq. mm 3-1/2 core
11240 sq. mm 3-1/2 core
12300 sq. mm 3-1/2 core
13400 sq. mm 3-1/2 core
14Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm
153.5 X 25 sq. mm
163.5 X 35 sq. mm
173.5 X 50 sq. mm
183.5 X 70 sq. mm
193.5 X 95 sq. mm
203.5 X 120 sq. mm
213.5 X 150 sq. mm
223.5 X 185 sq. mm
233.5 X 240 sq. mm
243.5 X 300 sq. mm
253.5 X 400 sq. mm
26Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
274 X 16 sq. mm (28mm)
283.5 X 25 sq. mm (28mm)
293.5 X 35 sq. mm (32mm)
303.5 X 50 sq. mm (35mm)
313.5 X 70 sq. mm (38mm)
323.5 X 95 sq. mm (45mm)
333.5 X 120 sq. mm (45mm)
343.5 X 150 sq. mm (50mm)
353.5 X 185 sq. mm (57mm)
363.5 X 240 sq. mm (62mm)
373.5 X 300 sq. mm (70mm)
383.5 X 400 sq. mm (82mm)
39Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.100 mm Dia
40150 mm dia
41250 mm dia
42300 mm dia
43Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. 63 mm dia (OD-63 mm & ID-51 mm nominal)
4490 mm dia (OD-90 mm & ID-76 mm nominal)
45120 mm dia (OD-120 mm & ID-103 mm nominal)
46160 mm dia (CD-160 mm & ID-135 mm nominal)
47Deduct in item no. 501 (I) 501 (t) and 506 (a) to (f) when cables is passed through G.I./M.S. or Hume pipe in road crossing or along the wall. The cost of the G.I. pipe, hume pipe is to be extra when and where required.
48Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
49HT CABLING WORK Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. Above 120 sq. mm and up to 400 sq. mm
50Supply and laying of 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across. The armouring of cable shall be properly connected with earth conductor by clamps etc.3.0 C x 300 sqmm Aluminium conductor
51Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. 160 mm dia (CD-160 mm & ID-135 mm nominal)
52Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq.mm
53Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq.mm
54Supplying and making outdoor cable straight jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq.mm
55TRANSFORMER AND PANEL WORK Supply, installation, testing and commissioning of following capacity (continuous loading) 11/0.433 KV Delta/Star,step down, 3 Phase, 50 Hz, Dyn 11 vector group, Cast Resin / VPI (vacuum pressure impregnated) Dry Type, copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better) AN (air natural) cooled transformer suitable for indoor applications with Offload Tap Changer/ On Load Tap Changer (OLTC) ( upto 500 KVA offload and above 500 KVA On Load Tap Changer) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, insulation class F (minimum), suitable for environment conditions class E4, suitable for fire behaviour class F1,climate class-C1, having cable end boxes on HV side suitable for 3x300 sqmm XLPE cable of 11 KV grade with necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers, bus trunking arrangement on LV side complete with all accessories and safety provisions as per relevant IS Code ,The transformer shall be provided with standard fittings/accessories as per relevant IS and mentioned below, protection alarm/trip protection, 3 nos. of Polymeric Zinc Oxide surge Arrestors on HV Side. Winding Temperature scanner (Digital) with alarm/Trip contacts with RTD Sensors per LV winding and space for mounting differential protection CT's in LV chamber with neutral brought out separately including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/HT Panel for safety tripping, complete as confirming to IS-2026 Part-11, i/c supplying and grouting of suitable M.S. Channel with all accessories ,complete in all respects as required at site as per CPWD specifications . Design ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as per location of site, d) Altitude as per location/site. The transformer should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. All testing shall as per relevant IS Code. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551/ NEMA Standard.Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Rating and terminal marking plates; c) Thermometer pocket with cap; d) Lifting lugs for the complete transformer as well as for core and winding assembly; e) Bi-directional flat rollers (for transformers above 200 kVA); f) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); g) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. for transformers up to 200 kVA; h) Bird guard; i) Jacking pads (for transformer above 1 600 kVA); j) Name Rating & Diagram Plate. k) Monogram Plate.i) Additional neutral separately brought out on bushing for earthing.LEVEL 4 400 KVA (losses at 50% loading < 1225watt, losses at 100% loading < 3450watt)
56500 KVA (losses at 50% loading <1510watt, losses at 100% loading < 4300watt)
57630 KVA (losses at 50% loading < 1860watt, losses at 100% loading < 5300watt)
58Cubical Panel Board (ACB & MCCB Type) Supply & Erracetion of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entreis Electrical control panel with TPN ACB(65 KA,4Pole Elect draw out , Micor processer Release IPR2 ) and TPN MCCB's (Four Pole 36 KA with thermal magnatic release) Switches and instrument chamber etc.complete in all respects. The instrument chamber shall be separate and shall comprise of flush type/digital ammeter Voltmeter, Selector switches for ammeter and Voltmeter, istrument fuses, current transormer etc. The Board shall have suitable capacity electrolytic aluminium busbars as per IS8623 insulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/ DMC support with deteachable side covers and shall be suitable for extension on the sides. The switches entry boxes shall be complete with suitable cable end boxes reverse. The Job includes the grounting of the board as per directions of Engineer-in charge. All out goings of 100 Amp and above Will be provided with Amp Metre, current transfonners and selector switches etc and insurtrment fuse. The switch board shall be fabicated with CRCA sheet with a minimum thickness of 1.6 mm/2mm. Cubicle type switch board shall be of cat A & B Only.INCOMING 1000 Amp / 415 Volt ACB-1 No OUT GOING 400 Amp MCCB-2Nos.& 200 Amp MCCB-1 No Cat. B Pannel Cubicle Type
591250 Amp / 415 Volt ACB-1 No OUT GOING 400 Amp MCCB- 3 Nos & 200 Amp MCCB-1 No Cat. B Pannel Cubicle Type
601600 Amp / 415 Volt ACB-1 No OUT GOING 400 Amp MCCB- 1 No,200 Amp MCCB-3 Nos., 100 Amp MCCB-3 Nos & 63 Amp MCCB-4 Nos. Cat. B Pannel Cubicle Type
61Supply and erection of factory fabricated and wired metal clad dust and vermin proof floor mounting panel TPN switch board complete with the following HRC type heavy duty TPN fuse switches with fuses and instrument chamber etc. complete in all respects. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmerer, selector switches for ammeter and voltmeter, instrument fuses, current transormer etc. The board shall have suitable capacity electroytic alumininum busbars as per IS8623 istulate with heat shrink sleeving and mountend on non hygroscopic supports such as CMC/DMC support with deteachable side covers and shall be suitable for extension on the sides. The switches shall be complete with suitable cable end boxes, reverse entery boxes in case of pedestaal type, cable sockets, compression glands and indicating lamp on incoming etc. The Job includes the grounting of the board as per directions of Engineer-in charge. All out goings of 100 Amp and above Will be provided with Amp Metre, current transfonners and selector switches etc and insurtrment fuse. The switch board shall be fabicated with CRCA sheet with a minimum thickness of 1.6 mm/2mm. Cubicle type switch board shall be of cat A & B Only. FEEDER PILLARS INCOMING 400 Amp. TPN-1 No OUT GOING 200 Amp.TPN-1Nos, 100 Amp.TPN-2Nos. & 63 Amp.TPN-1Nos.
62630 Amp. TPN-1 No OUT GOING 200 Amp.TPN-2Nos., 100 Amp.TPN-1No & 63 Amp.TPN-2 Nos.
63APFC PANEL Supply, Installation, testing and commissioning of APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60%capacity and active solution of 40% capacity,3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangment for neutral current balance) to achieve >0.99 lag and TDDI/THDV values within IEEE recommended limits.APFC should be designed as per recommended limits.APFC should be designed as per IS 16636 Or IEC 61921. The active section and passive section shall work in sync to give optimized output. The degree of protection of passive section should be IP 42, and of active section should be minimum IP 21.The switching device for APFC passive section should be through capacitor duty contactor and for the active compensation system shall be IGBT based with 3 level topology having 12 IGBT in inverter circuit. The active compensation system should filter harmonics from 2nd to 50th individual harmonic order and shall be selectable for the entire range. The active compensation system should have feature to improve PF correction and harmonic filtration having response time < 100 Micro second. The hybrid panel shall be indoor type floor mounted free standing totally enclosed, extensible, fabricated in compartmentalised designed made of CRCA sheet steel of 2.0mm thick for framework & covers, 3 mm thick for gland plate i/c cleaning & finishing complete with 9 tank process for powder coated of approved shade ( RAL 7032-Siemens gray or as approved by Engineer-in-Charge), having front section (switch gear and control accessories) and rear section (capacitor and reactor), front and rear access, having suitable current carrying capacity, extensible TPN Aluminium alloy bus bar of high conductivity, DMC/SMC bus bar supports,bottom base channel of MS Section, fabrication shall be done in transportable section, entire panel shall have common copper earth bar of minimum size of 25mm x 5mm with 2 nos. earth studs, the earth terminals provided on the body of capacitor bank shall also be bonded to the main capacitor panel earth bus with 2 nos. 8 SWG or 6 SWG GI earth wires/ equivalent size of copper conductor cable, forced ventilation for maintaining temperature rise not more than 5°C from ambient, interconnections, connections with 14% detuned reactor and heavy duty 525 V ISI marked Impregnated MPP(Metalized Polypropylene) Capacitor (IS 13340 Part -1 & 2) APFC Panel shall be in compliance with IS :16636 & CPWD Specifications etc. as per below details.(A) Incomers Suitable capacity MCCB Microprocessor base with O/C, S/C, E/L release of TPN 50KA breaking capacity (Ics=Icu), ON, OFF, Trip, R, Y, B - LED Indicating Lamp set along with required Instruments and accessories with extended rotary handle and door interlocking arrangement. Current rating of the Incomer in ampere shall be APFC Panel rating in KVAR x 1.4 x 1.5 or Nearest higher standards rating.(B) Instruments & Indicationsa)For Passive Section :i) 3-Phase current sensing APFC microprocessor relay/controller , advance 8/12 stages (8 stages for capacity below 100 KVAR and 12 stages 100 KVAR & above) with Communication Ethernet/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge and having display of Phase wise V, A, PF, Cos-Phi, Kw, KVA, KVAR, THD-V , THD-I, harmonics up to 31 level. 3 nos of dual core CT's accuracy class 1, 15VA at incomer of PCC Panel for APFC relay.ii) Auto Manual Selector switch, auxiliary contactors with timer for delay in manual mode. iii) Digital Multi function meter with LED Display for V, A, PF, KW, KVA, KVAR, THD-V & I, Frequency. iv) Suitable rating control transformer shall be provided for control and indication circuit. v) All components like control transformer, meter,relay and indicating lamp shall be protected by using suitable rating individual MCB's. vi) Wiring of the control circuit shall be done by using 2.5 sq mm, FRLS/HFFR 1100 V grade, PVC insulated multi stranded copper control wire. (C) Bus Bars 1.3 Amp per Sq.mm,TPN, Electrolytic grade Aluminium bus bar of capacity 1.25 times of incomer rating as per CPWD specification \\"(D) Outgoings (APFC Section) Selection of the capacitors combinations shall be for continuous rating and each capacitor bank shall have suitable capacity Heavy Duty ISI Marked Capacitor, capacitor duty contactor,the capacitor shall be mounted on channel with base of perforated M S Powder coated sheet, connections inter connections etc. and otherfeatures as per CPWD Specifications and relevant IS Code having following:\\"(i) Capacitor bank ratings & stages shall be as per the technical specifications sheet of NIT. (ii) Capacitor will be MPP self healing type with discharge resistor, pressure release mechanism.(iii) Since Capacitor Voltage is 525 Volts, thus higher KVAR has to be considered to get rated output at 415 Volts.(iv) 14% Detuned Reactor of class H insulation & 150% linearity in series with Capacitor. (Note: Technical specifications sheet for selection of the capacitors combinations shall be provided by the NIT Approving Authority with due consideration of number of capacitors i.e. 1 KVAR, 2 KVAR, 3 KVAR, 5 KVAR, 10 KVAR.for smooth correction). 150 KVAR
64175 KVAR
65200 KVAR
66EARTHING WORK Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
67Earthing with Cu. earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
68Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
69Providing and fixing 25 mm X 5 mm Cu. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
70Providing and fixing 25 mm X 5 mm Cu. strip on surface or in recess for connections etc. as required.
71Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
72Supply and burring of Safe Earthing Electrode T-19 (Hot-Dip Galvanized), Length up to 3000mm,outer pipe 48.4mm x 3.2mm, inner pipe 26.9mm x 2.6, terminal Dia 12 mm, coating 80-100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonary housing. (From electrode terminal to switch board, cost of 25 x 3 G.I. Strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified.
732 pole structure Supply, erection and commissioning of 2-pole structure for terminating 11 KV O.H. supply from supply company as per specifications and drawing. The 2-pole structure shall comprise of:-a) MS tubular galvanised swaged pole 11 mtrs high (410SP 55) (as per latest relevant BS standard)or as per Indian std., in cement concrete foundation 1:3:6 (1 cement : 3 coarse sand : 6 graded aggregate 40mm nominal size) including excavation and refilling etc. as required. The rate shall be inclusive of painting with 2 coats of aluminium paint (on red oxide). The portion of pole under the ground shall be provided with 2 coats of bituminous paint -2 Nos.b) Steel sections, channels angles, flats, clamps, GI nuts, bolts and required hardware etc of different sizes for cross arms, bracings, supports etc. for pole GODO etc. including anticlimbing barbed wires (conforming to BS Standard) having 4 points barbs spaced 75 ±12mm apart. All steel structure shall be given 2 coats of red oxide primer and 2 finishing coats of aluminium paint as required as per drawings and direction of Engineer-in-charge -Lot c) Supply, installation, testing and commissioning of 11 KV class disc/pin/support insulators complete with clamps and fixing hard disc/pin/support insulators complete with clamps and fixing hard wares etc. complete as required as per drawings and direction of Engineer-in-charge -Lot d) Supply, installation, testing and commissioning of 11 KV station class thyrite type lightning arrestors complete with mounting arrangement (on all phases) -1 Set e) Supply, installation, testing and commissioning of drop out -lock out (DOLO) fuse, gang operating device (Air Break Switch) with pad locking arrangement (operating rod to be supported properly), complete with operating handle and locking arrangement -1 Set f) Supply, installation, testing and commissioning of GI stay set complete with 20mm dia 1.8 M long stay rod with 450 x 450 x 7.5 mm anchor plate with thimbles, stay clamps, 7/4.00 mm dia GI stay wire, turn buckle (20mm x 600mm) strain insulator bow tightner in cement concrete 1:3:6 foundation as excavation and refilling -1 Sets 2-pole structure as described above.
74Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth, 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50m and lift up to 1.5m, disposed earth to be levelled and neatly dressed. All kinds of soil
75Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size).
76Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
77Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars. Fe-500 D
78Centering and shuttering including strutting, propping etc. and removal of form for : Raft and wall/ slab
79Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:4 (1 cement : 4 coarse sand) Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57009302
AUTHORITY Local Bodies
TENDER VALUE 21.49 Crore
LAST DATE 09-09-2026
Authority
Authority Name Ghaziabad Development Authority
Work Description Tender for Work Of External Electrification In Madhuban Bapudham Pocket-A.
Basic Detail
Tender No 685/4/PAT/2026-27 dt 10-08-2026 (S.No-4)
Bidding Type Tender
Location
City Ghaziabad
State Uttar Pradesh
Key Dates
Publish Date 14 Aug 2026
Submission Date 09 Sep 2026
Open Date 11 Sep 2026
Finance
Tender Value 21.49 Crore
Tender Fee 18054
EMD 42.98 Lakhs
Exemption Not Available
Document List
455db6ba-6524-424d-8ffd-bc2c13bb4cb8.html
685_4.pdf
BOQ_2211876.xls
Tendernotice_1 (39).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 14, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 09, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 16 days
Sep 11, 2026

Bid Opening Date

Technical bids will be opened and evaluated.