Tender For Special Repair To Echs Polyclinic Bldg At Cg Complex Under Ge Ludhiana.
BOQ
| Sl. No. | Item Description |
| 1 | Sch 'A' |
| 2 | Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided complete all as specified & directed |
| 3 | Taking down cement plaster on brick or stone walls etc including raking out joints hacking for key scrubbing down with water etc complete all as specified & directed |
| 4 | M&L 15mm thick plastering on fair faces of bricks or concrete surfaces finished even and smooth without using extra cement in CM 1:4 complete all as specified & directed |
| 5 | M&L for complete removal of existing treatment of walls,washing,rubbing down and stopping of distempered and painted surface and applying of plastic emulsion paint over a coat of primer and a coat of wall putty complete all as specified & directed |
| 6 | M&L for preparation of newly plastered surface of wall and applying two coats of cement base paint complete all as specified & directed |
| 7 | M&L for preparing of old plastered surface and applying three coats of white wash on ceiling complete all as specified & directed |
| 8 | Dismantling floor hearth or wall tiling including cement mortar bedding but not backing removing serviceable tiles to store and rubbish off the premises complete all as specified & directed |
| 9 | M&L for Non-skid ceramic coloured tiles 7 to 8mm thick (square or rectangular) area of each tile exceeding 0.11 Sqm but not exc. 0.18Sqm in floors etc. set and jointed in neat cement slurry and pointed in white cement to match the shade of tile over and including 15mm thick rendering of in cement mortar 1:6 complete all as specified & directed |
| 10 | M&L for glazed ceramic coloured tiles (450x350mm) x 7mm thick on vertical surfaces etc. set and jointed in neat cement slurry and pointed in white cement to match the shade of tile over and including 10mm thick rendering of in cement mortar 1:4 complete all as specified & directed |
| 11 | M&L 25mm thick Cement concrete 1:2:4 type B-0 using 20 mm graded crushed stone aggregate as in sub flooring rough finished surface complete all as specified & directed. |
| 12 | M&L Endura chequered cement concrete tiles 30cmx 30cmx 10mm thick set, jointed & pointed in neat cement slurry in floors with grey cement and pigments over & including 20mm thick screed in cement mortar 1:6 complete all as specified & directed |
| 13 | M&L, 75mm thick PCC 1:4:8, type D-2 using 40mm crushed stone aggregate as in sub base floor complete all as specified & directed |
| 14 | M&L for Sand filling under floors or in foundations complete all as specified & directed |
| 15 | M&L 60mm thick interlocking paver block with grey cement and pigment of any size and shape confirming to IS 15658-2006, M-35 Grade as approved laid in flooring and joints filled/broomed with fine sand complete all as specified & directed |
| 16 | M&L cement concrete 1:2:4 type B-1 using 20mm graded crushed stone aggregate provided in coping, rounded or chamfered on edges complete all as specified & directed |
| 17 | M&L for 75mm thick cement concrete type C-2, 1:3:6 (using 40mm graded crushed stone aggregate) as in plinth protection finished even and smooth (without using extra cement) complete all as specified & directed |
| 18 | Taking down carefully exising unserviceable aluminium point wiring (light, fan, socket or power), complete (fitting such as switches,ceiling rose, pendent, regulators etc) removing material to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately and making good disturbed surfaces of wall, floor etc. complete all as specified & directed |
| 19 | Taking down old unserviceable sub main wiring of any type complete all as specified & directed |
| 20 | Taking down the existing unserviceable main switch/cut out/ DBs of any type / capacity / description as existing at site including necessary making good the disturbed surfaces to match with the existing finishes complete all as specified & directed |
| 21 | M&L for Point wiring using approved colour coding as per IS, with multistranded copper conductor 1.5 Sq. mm (nominal area), two single core, PVC insulated and unsheathed FRLSH cable 1100 volts grade ISI-694 marked drawn through in and including heavy duty, PVC concealed conduit including all accessories after chasing in wall/ceiling etc, heavy duty ISI marked, with GI sunken boxes 1.2 mm thick, 60 mm deep with earth dolly duly, covered with modular white cover plate with frame suitable for modular switches, including PVC insulated multistranded copper conductor 1.5 Sqmm (nominal area) single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly including necessary cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified & directed for the following :- |
| 22 | One light point controlled by one, one way switch 5 Amps. |
| 23 | One fan point/ exhaust fan point controlled by one, one way switch 5 Amps and regulator. |
| 24 | One bell point controlled by one, bell switch 5 Amps. |
| 25 | One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board. |
| 26 | One 3 point 5 Amps switch socket outlet point controlled by one switch on the same board. |
| 27 | All as per item No 20 above but with stranded copper conductor 2.5 Sqmm (nominal area), single core, PVC insulated and unsheathed multistranded FRLSH cable 1100 Volt grade ISI-694 marked for 3 pin, 15 Amp socket outlet on independent board including PVC insulated multistranded copper conductor 2.5 Sqmm (nominal area) single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly. |
| 28 | All as per item No 20 above but with stranded copper conductor 4 Sqmm (nominal area), single core, PVC insulated and unsheathed multistranded FRLSH cable 1100 Volt grade ISI-694 marked for 3 pin, 15 Amp socket outlet on independent board including PVC insulated multistranded copper conductor 4 Sqmm (nominal area) single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly. |
| 29 | S&F for Modular switch one way 6 Amps, 1 module complete all as specified & directed |
| 30 | S&F for Modular switch one way 16 Amps, 1 module with neon indicator complete all as specified & directed |
| 31 | S&F for celling rose 2/3 terminals, PVC/polycarbonate, isolated body ISI marked complete all as specified & directed |
| 32 | S&F for modular step type fan regulator 120 watt two module suitable for operation on 230 volt 50 HZ AC supply complete all as specified & directed |
| 33 | S&F for Modular socket, 6 Amps, 2/3 pin combination 2 module complete all as specified & directed |
| 34 | S&F for Modular socket, 6/16Amps, 2/3 pin combination 2 module complete all as specified & directed |
| 35 | S&F for modular Bell push modular 6 Amps single module complete all as specified & directed |
| 36 | S&F for Bell Electric Ding dong type suitable for operation on 230 volt 50 HZ A C supply including removal of old unserviceable one complete all as specified & directed |
| 37 | S&F for for lamp holder, PVC body of brass suitable for batten fitting including removal of old unserviceable one complete all as specified & directed |
| 38 | S&F for Highly efficient LED 9W bulb B22 CDL,Green/Red used as a ready replacement for existing LED direct fit lamp ccomplete all as specified & directed |
| 39 | S&F in replacement of sheet metal enclosure Vertical TPN DB suitable for MCCB Incomer 6 way Vertical type with 125 Amps rated bus bar 415 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified & directed |
| 40 | S&F for sheet metal enclosure MCB DB TPN 4 way with 200 Amps rated bus bar 415 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified & directed |
| 41 | S&F for sheet metal enclosure MCB DB SPN 12 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified & directed |
| 42 | S&F in replacement of sheet metal enclosure MCB DB SPN 8 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall ccomplete all as specified & directed |
| 43 | S&F in replacement of sheet metal enclosure MCB DB SPN 4 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified & directed |
| 44 | S&F MCCB TPN 4 pole 415 volts 16 KA suitable for fixing on DB of capacity of current rating 125 Amps with adjustable thermal and microprocesser release with extended terminals complete all as specified & directed |
| 45 | S&F MCCB TPN 4 pole 415 volts 16 KA suitable for fixing on DB of capacity of current rating 100 Amps with adjustable thermal and microprocesser release with extended terminals complete all as specified & directed |
| 46 | S&F MCCB TPN 4 pole 415 volts 16 KA suitable for fixing on DB of capacity of current rating 63 Amps with adjustable thermal and microprocesser release with extended terminals complete all as specified & directed |
| 47 | S&F for MCB tripple pole and neutral rated capacity 63 A, 415V breaking capacity 10 KA complete all as specified & directed |
| 48 | S&F for MCB Single pole and neutral rated capacity 40 amps, 240 Volts breaking capacity 10 KA complete all as specified & directed |
| 49 | S&F for MCB Single pole and neutral rated capacity 32 amps, 240 Volts breaking capacity 10 KA complete all as specified & directed |
| 50 | S&F for MCB Single pole rated capacity 5 to 32 amps, 240 Volts breaking capacity 10 KA complete all as specified & directed |
| 51 | M&L for circuit/ sub main wiring with approved colour coding as per IS with three single core PVC insulated FRLSH cable with stranded copper conductor of size 16 Sq mm nominal area and drawing into PVC non metallic rigid heavy duty PVC concealed conduit and its accessaries ISI marked heavt duty of suitable size including with two run of PVC insulated 16 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire complete all as specified and as directed. Note:- Three runs of 16 sqmm copper cable and one run of PVC heavy duty conduit will be measured as one unit, with necessary provision for cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 52 | M&L for circuit/ sub main wiring with approved colour coding as per IS with three single core PVC insulated FRLSH cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into PVC non metallic rigid heavy duty PVC concealed conduit and its accessaries ISI marked heavt duty of suitable size including with two run of PVC insulated 6 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire complete all as specified and as directed. Note:- Three runs of 16 sqmm copper cable and one run of PVC heavy duty conduit will be measured as one unit, with necessary provision for cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 53 | M&L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLSH cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into PVC non metallic rigid heavy duty PVC conduit and its accessaries ISI marked heavt duty of suitable size including with one run of PVC insulated 6 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire complete all as specified and as directed. Note:- Two runs of 6 sqmm cable, one run of 6 sqmm earth cable and one run of PVC heavy duty conduit will be measured as one unit, with necessary provision for cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 54 | M&L for Sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLSH cable with stranded copper conductor of size 4 Sq mm nominal area and drawing into PVC non metallic rigid heavy duty PVC conduit and its accessaries ISI marked heavt duty of suitable size including with one run of PVC insulated 4 Sqmm (nominal area) stranded copper conductor FRLSH cable as earth wire complete all as specified and as directed. Note:- Two runs of 4 sqmm cable, one run of 4 sqmm earth cable and one run of PVC heavy duty conduit will be measured as one unit, with necessary provision for cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 55 | S&F in replacement of LED 8/10 watt 2 feet white 85lm/W 6500K batten extruded with decorative end caps complete all as specified and as directed. Make- Goldmedal Cat pat No GL9C2001608CD or eqivalent in Bajaj/ Havells/Philips. |
| 56 | S&F in replacement of Highly efficient LED 9W inverter bulb B22 CDL, 100 lm/W used as a ready replacement for existing LED direct fit lamp complete all as specified & directed |
| 57 | S&F in replacement of LED downlight surface mounted luminare round type 12/18 watts 6500K with inbult driver and polycarbonate opal diffuser white finish operating voltage 230V AC, 50 Hz complete all as specified & directed |
| 58 | S&F in replacement of LED down light recess mounted luminare, square type 15/18 watts with efficiency of 100 lumens per watt, sleek design aluminium housing polycarbonate diffuser white finish operating voltage 150 V-270 V AC, 50 Hz complete all as specified & directed |
| 59 | S&F in replacement of Energy saving new generation 10 watts LED bulk head fitting IP 65 luminaire 100 lm/W with opel diffuser pre wired and necessary mounting arrangements , provision of new 3 core multistranded copper conductor of size 23/0193 from ceiling rose to fitting including LED bulb and removal old existing unsv tube light fitting complete all as specified & directed |
| 60 | S&F in replacement of LED 3 W spot light round, Recess mounted downlighter with pressure die-cast aluminium heat sink & clear PC as a cover in white powder coated finish with independent electronic LED driver LED Spot 3W 3000K complete all as specified & directed |
| 61 | S&F in replacement of Decorative wall light fixture made up of Polycarbonate, suitable for 9 W LED lamp B22 base with unbreakable globe suitable for LED bulb and including provosion of inverter LED bulb 9/10 watts complete all as specified & directed |
| 62 | S&F for Decorative hanging luminaire with decorative glass shade with suitable holder for LED bulb and provosion of LED inverter bulb 10 watts complete all as specified & directed |
| 63 | S&F in replacement LED tube light fittings, 20W, 240V, 50Hz,surface mounting decorative battens with best in class luminaire efficancy. This CRCA housing batterns are quipped with specially designed extruded aluminium heat sink, Milky white P diffuser and elegantly designed white coloured ABS endcaps to enhance the aesthetics of the luminaire <10% THD complete all as specified & directed |
| 64 | S&F for surface mounted 2' x 2' square LED panel 42 watts, high performance luminaires which provides soft-light and glare free symmetrical lumination complete all as specified & directed |
| 65 | S&F in replacement of post top lantern LED type 20/25 watt 230 watt volts AC outdoor type with decorativepost top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified & directed |
| 66 | S&F in replacement of post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorativepost top for 360 degree indirect light IP 66 protection with impact and corrosion resistant complete with driver and lamp complete all as specified & directed |
| 67 | S&F in replacement of Solar LED pathway lights waterproof outdoor modern led walkway path ighting for garden round 80 cm complete all as specified & directed |
| 68 | S&F in replacement of new generation energy saving and environmental friendly long life LED street light capacity 25 watts made up of pressure die cast aluminium housing with high efficiency LED as lighting source and lens embedded PC cover having bottom Opening seperate driver compartment with IP 66 protection 160 lm/W and impact resistance of IK08 and necessary mounting arrangements and provision of 1.5 sqmm three core copper conductor cable multi stranded from ceiling rose to light fitting including necessary dia GI pipe medium grade bracket 1.0 mtr long bend to required shape with clamps, nut, bolts complete all as specified & directed |
| 69 | Supply and fix in replacement of exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250m including necessary connection and replacement of flexible copper cable from ceiling rose and taking down of old unserviceable fan deposited to E/M store complete all as specified and as directed |
| 70 | Supply and fixing in replacement ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep, Pearl white colour. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC),fan design should be approved by Engr-in-Charge and old ceiling fan deposited to E/M store complete all as specified & directed |
| 71 | Supply and fixing in replacement single core cable PVC insulated and unsheathed multistranded copper conductor of size 1.5 Sqmm from point wiring including removal old existing unserviceable one complete all as specified and directed. |
| 72 | Supply and fixing in replacement single core cable PVC insulated and unsheathed multistranded copper conductor of size 6 Sqmm from point wiring including removal old existing unserviceable one complete all as specified and directed. |
| 73 | M&L Earthing including earth work complete with galvanised steel earth plate electrode 60cm X 60 cm X 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level with the top edge of electrode not less than 1.5 mtr below normal ground level connected to galvanised earth lead wire 4mm dia means of bolts, nuts,check nuts and washers of galvanised iron and GI lead protected with protection pipe of GI light grade 15mm dia upto 3mtr above ground level along poles fixed with two clamps of 25mm 3mm flat iron and connected to running earth wire at top of poles and watering pipe 20mm bore of GI medium grade all as shown in electrical plate No 3 of SSR Part-I 2009 connected to earthing test point all as specified and direct and testing on completion including PCC 1:3:6 ) C-I cover and frame excavation and earth work etc complete all as specified in elect plate No 3 of SSR Part -I 2009 Note :- PCC Chamber shall be constructed at least 1.50 mtr away from on the earth pit electrode and pipe for watering shall be provided in slanting manner. |
| 74 | M&L XLPE insulated heavy duty electric cable with aluminium conductor 1100 volt grade cross sectional area 95 sqmm, 3.5 core complete all as specified & directed |
| 75 | M&L XLPE insulated heavy duty electric cable with aluminium conductor 1100 volt grade cross sectional area 70 sqmm, 3.5 core complete all as specified & directed |
| 76 | M&L XLPE insulated heavy duty electric cable with aluminium conductor 1100 volt grade cross sectional area 10 sqmm, 4 core complete all as specified & directed |
| 77 | M&L XLPE insulated heavy duty electric cable with aluminium conductor 1100 volt grade cross sectional area 16 sqmm, 2 core complete all as specified & directed |
| 78 | Excavation in trenches n exc 1.5m wide and n.exc 1.5m in depth for cable,etc n.exc 10sqm on plan and n.exc 1.5m depth and getting out soft.looser soil for cables etc complete all as specified & directed |
| 79 | Returning filling in including spreading,leveling watering and well ramming in layers not exc 25cm complete all as specified & directed |
| 80 | Removing excavated material n exc 50m and depositing where directed at a level in exc 1.5m above the starting point complete all as specified & directed |
| 81 | Supply and spreading of fine river sand and gentally punning for laying of under ground cables complete all as specified & directed Note :- Punned thickness 18cm shall be measured for payment. |
| 82 | Supply and laying sub class 'B' common burnt bricks, old size designated 75, laid dry flat with width equal to length of brick & with gaps between the adjucent bricks n.exc 10mm as cover laid over the cable to give mechanical protection to under ground cable complete all as specified & directed |
| 83 | Supply and fixing of GI tubing galvanised light grade of size 80 mm dia with all fittng and fixed complete to wall, floor and ceilling or laid in trenches (for protection UG cables) complete all as specified & directed |
| 84 | Supply and fixing of GI tubing galvanised light grade of size 80 mm dia with all fittng and fixed complete to wall, floor and ceilling or laid in trenches (for protection UG cables) complete all as specified & directed |
| 85 | Supply installng, testing and commissioning floor mounted LT panel outdoor type of suitable size cubical type factory made, weather and vermin proof made out of CRCA sheet 3.15 mm thick and angle iron frame of 40x40x6mm and 04 Nos legs on angle iron 50x50x6mm each 90 cm long panel duly powder coacted heaving insulated bus bar TPN with openable shutter on both side (Front and rear side) with locking arrangement duly pre-wired with suitable size of copper conductor cable with proper size of copper lugs/thimbles,with cable gland and connecting to MCCBs with suitable size aluminium strip duly bended and fixed with nut & bolts and washers from bus bar to MCCBs and legs grouted in PCC 1:2:4 type B:1 (20 mm graded crushed stone aggregate Powder Coated Spray painted from outside and inside with approved stove enameled grey paint two coats over one coat of red oxide primer complete all as specified and directed.(i) Aluminium bus bar strip of capacity 400 amps fixed on epoxy insulator - 04 Nos(ii) Incomming MCCB of current rating 315 Amps with adjustable thermal release and adjustable magnetic release 4 pole 415 volts 36 KA repturing capacity - 01 Nos.(iii) Out going MCCB of current rating 125 Amps with adjustable thermal release and adjustable magnetic release 4 pole 415 volts 25 KA repturing capacity - 02 Nos(iv) Out going MCCB of current rating 100 Amps with adjustable thermal release and adjustable magnetic release 4 pole 415 volts 25 KA repturing capacity - 04 Nos(v) Out going MCCB of current rating 63 Amps with adjustable thermal release and adjustable magnetic release 4 pole 415 volts 16 KA repturing capacity - 02 Nos(vi) Out going MCB, SPN of current rating 40 Amps 2 pole 230 volts - 02 Nos (vi) Digital voltmeter (0-500 volt) 96x96m squire type with inbuilt selector switch - 01 Nos (vii) Digital ampearmeter (0-600 amps) 96x96m squire type with CTs inbuilt selector switch - 01 Nos(viii) Set of phase indicator lamp R,Y,B with control MCB - 01 Set |
| 86 | S& F in replacement of LED Bollard 8 W Cone NXG LED Bollard series acts as an imposing treet furniture with touch of aesthetic. Innovative design with uniformly lit diffuser at the upper portion acts as beacon of path guidance in a landscape environment with robust IP 65 rating with PCC (1:2:4) foundation complete all as specified & directed |
| 87 | Boring of holes under road, pavement, hard standing by trenchless technique and necessary T&P for passing of LT cables complete all as specified & directed |
| 88 | Material & labour earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed with layers of charcoal dust and common salt, earth electrode GI strip 32 x 6mm connected to GI earth plate electrode by means of bolts, nuts, check nuts and washers of galvanized iron and thimbles and other end of earth strip connected to test point and protected by galvanized iron light grade 50mm bore and GI pipe 20mm bore light grade with funnel and wire mesh for watering including necessary excavation and earth works. PCC chamber in cement concrete (1:3:6) type C-2 using graded stone aggregate and RCC cover in M-25 (Design mix) and all as shown in Electrical Plate No. 3 of MES Schedule (Part-I) of 2009 complete all as specified & directed.Notes :(i) Outer edge of earth pit will be 1.5m away from the outer edge of PCC chamber.(ii) Water pipe shall be provided in slanting position. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysSep 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender