Tender For Provn Of Area Lighting, External Electrification At Mt Garage And Special Repair/Replacement Of Lt Ug Cable Inside Vijay Durg Under Ge(Vd) Kolkata
Tender Value
40 Lakhs
Estimated cost
Bid Submission
03 Sep 2026
18 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kolkata → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Area Lighting, External Electrification At Mt Garage And Special Repair/Replacement Of Lt Ug Cable Inside Vijay Durg Under Ge(Vd) Kolkata
BOQ
| Sl. No. | Item Description |
| 1 | Supply, install, commissioning and testing of Indoor type LT panel board, cubical type,mounting in PCC base dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000mm x 1800mm x 600mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB/change over switch separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers Aluminium bus bar 800 Amps (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 50 x 50 x 6 mm with legs not more than 300mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. Location Engr Branch |
| 2 | (a) Automatic Transfer Switch 630 Amp, 4 Pole (open execution)+AST Controller with wire harness - 01 Sets Make: L&T |
| 3 | (b) MCCB design with Microprocessor Release of capacity 630A, 4P, 50 KA - 02 Nos (Incoming). Make : Legrand/Schnider/Siemens |
| 4 | OUTGOING |
| 5 | (a) MCCB design with Thermal Magnetic releases of capacity 320 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens |
| 6 | (b) MCCB design with Thermal Magnetic releases of capacity 200 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make :Legrand/Schnider/Siemens |
| 7 | (c) MCCB design with Thermal Magnetic releases of capacity 160 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 8 | (d) MCCB design with Thermal-magnetic releases of capacity 100 Amps, 4 Pole, 25 KA - 02 Nos (Outgoing). Make : Legrand/Schnider/Siemens |
| 9 | METERING INSTRUMENT |
| 10 | (a) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 11 | (g) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 12 | (h) MCB SP 6 Amps, 10 KA - 3 Nos. Make : L&T |
| 13 | (f) LED type indication lamp R Y B - 01 set. |
| 14 | (g) Current Transformer Ratio 250/5A - 03 Nos |
| 15 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Changeover to be connected internally with suitable size of copper strip. (iii) Earthing as per SSR 19472 and incl earth work,PCC pit and RCC cover,watering pipe 20 mm dia light grade,funnel,wire mesh,protection pipe 15 mm dia light grade , charcoal dust and salt etc and connected to earthing test point including taking up of old UNSV earthing complete all as specified and directed by Engr-in-Charge. |
| 16 | Excavation in trenches not exc 1.5 mtr width and not exce 1.5 mtr in depth in soft/loose soil and getting complete all as specified and as directed. |
| 17 | M&L for sand cushioning /sand covering for underground cable protection and consolidated and compacted with clean dry sand complete all as specified and as directed. |
| 18 | M&L bricks with sub class 'B' locally available laid in trenches above sand cushioning for cable protection complete all as specified and as directed. |
| 19 | Laying in Trenches Bricks (Serviceable Bricks obtained from Item No. 9.00 here-in-after), for Cable Protection, complete all as specified and as directed. |
| 20 | Returning, filling in including spreading levelling watering and well ramming in layers n.exc 25 thick for soft/loose soil complete all as specified and as directed. |
| 21 | Removal of excavated material to a disance n.exc 50 mtr and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed. |
| 22 | Excavation/Cutting Road/ Hardstanding in Trenches not exc. 1.00 Meter wide and not exc. 1.00 Meter in depth and getting out, complete all as specified and as directed. |
| 23 | Taking down unserviceable LT cable for repair/ replacement etc (from cable duct/underground trench/pole), stacking properly (cable, pipe and bricks) complete all as directed by the Engr-in-Charge of the following cross - sections :- (Note :- Necessary earth work to be measured and paid separately. |
| 24 | 185 Sqmm to 240 Sqmm, 3.5 Core |
| 25 | Supply, Laying and testing for replacement of XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall with saddles/Flat iron clamps as per site requirement /passing through pipe/pole complete of the following sizes and cross sectional area :-Note :- Necessary earth work to be measured and paid separately. |
| 26 | 185 Sqmm, 3.5 Core |
| 27 | 240 Sqmm, 3.5 Core |
| 28 | Taking down unserviceable Galvanised steel tubing Pipe 80 mm bore replacement etc (from underground trench/pole), complete all as directed by the Engr-in-Charge. |
| 29 | M&L for Galvanised Steel Tubing Pipe 80 mm bore (dia), light grade with Bends, laid in Trenches or under Roads/ Flooring/ Culverts etc., complete all as specified and as directed. |
| 30 | Material & Labour for PCC 1:3:6 type C2 using 40mm graded aggregate as in plinth course, string course etc complete including slightly rounded or chamefered for Galvanised steel tubing post for air termination rod including form work etc complete all as specified and directed. |
| 31 | S&F Heat shrinkable straight through Jointing Kit 185 - 240 sqmm, 3.5 core suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion complete all as specified and directed by the Engr-in-Charge. |
| 32 | Materials and Labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized steel earth strip 25 x 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown in Figure 15A of IS 3043 :1987 incl taking out of existing earthing complete all as specified and directed. |
| 33 | Supply and fixing Galvanised iron strip 25 x 4mm for connection of earthing with LT Panel board burried in ground complete all as directed. |
| 34 | Supply, Laying and testing for replacement of XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall with saddles/Flat iron clamps as per site requirement /passing through pipe/pole complete of the following sizes and cross sectional area :-Note :- Necessary earth work to be measured and paid separately. |
| 35 | 16sqmm 3.5 Core |
| 36 | 25 Sqmm, 3.5 Core |
| 37 | 50 Sqmm, 3.5 Core |
| 38 | S & F TP&N Vertical Loadline Dbs are fitted with Bus Bars, Neutral Links, Blanking Plates 4 way double door DB LL 4W DD VERT With 120-160amps MCCB complete all as specified and directed. |
| 39 | S & F MCCBs 415V, 16KA, 4 Pole 100Amps complete all as specified and directed. |
| 40 | Supply only MCB, 'C' series, single pole, 6 to 32 Amps, breaking capacity 10KA complete all as specified and directed. |
| 41 | Supply only MCB, 'C' series, SPN, 32 Amps, breaking capacity 10KA complete all as specified and directed. |
| 42 | S & F PVC Cable trays with cover of size 75mm X 75mm on walls / ceilings as per site requirement for proper fixing of Copper pipe with insulation alongwith fittings and fixtures arrangement complete all as specified and directed. |
| 43 | Cutting Chases pinning in, for concealed conduit wiring and making goods of disturbed surface not exc 15 cm girth complete all as specified and directed. |
| 44 | M & L for sub main wiring with 4 run of FRLSH PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 10.0 sqmm alongwith one run of FRLSH PVC insulated & unsheathed multistranded copper conductor of nominal cross sectional area 10.0 sqmm as earth continuity conductor drawn through and including PVC casing-caping of suitable size, surface type all as directed. |
| 45 | All as per Srl. Item No. 30 above but with 2 run of 6.0 Sqmm cable and 6.0 Sqmm as earth continuity conductor. |
| 46 | All as per Srl. Item No. 30 above but with 2 run of 4.0 Sqmm cable and 4.0 Sqmm as earth continuity conductor. |
| 47 | S & F TP&N Vertical Loadline Dbs are fitted with Bus Bars, Neutral Links, Blanking Plates 4 way double door DB LL 4W DD VERT W/O MCCB complete all as specified and directed. |
| 48 | S & F MCCBs 415V, 16KA, 4 Pole 100Amps complete all as specified and directed. |
| 49 | S & F Double door sheet metal enclosure for DBs(Normal range) for mounting of MCB for 240 Volts 4 Way with 100 Amps rated copper bus bar,single pole and Neutral complete all as specified and directed. |
| 50 | Supply only MCB, 'C' series, single pole, 6 to 32 Amps, breaking capacity 10KA complete all as specified and directed. |
| 51 | Supply only MCB, 'C' series, SPN, 32 Amps, breaking capacity 10KA complete all as specified and directed. |
| 52 | S & F in repair AC short circuit protection motor starter 20 Amps capacity AC 230 Volt complete all as specified and directed. |
| 53 | Supply and Fixing in replacement of following GI pipe light grade (ISI Marked) for cable protection along wall/pole/floor/road crossing etc complete including sealing of pipe ends with approved sealing compound including taking up old UNSV GI pipe of 50mm dia complete all as specified and directed by Engineer-in-Charge. |
| 54 | S&F of Feeder Pillar Box of size 60x60x45 Cm, made out of CRCA Sheet 3.0mm thick, Outdoor, Pedestal type, Weather Proof, Epoxy based Powder Coated Paint, Self-Closing Door having with Locking Arrangement, mounted on brick work Platform of size 100x100x60 Cm with plastering, comprising with 4 No. Aluminium Bus-bar of current rating 400 Amp with and including 1 no. MCCB 200 Amp 25 kA, 4 Pole, complete all as specified and as directed. |
| 55 | Supply and fixing Copper strip 20mm x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as directed by Engineer-in-Charge. |
| 56 | Material and labour for Chemical earthing with Pipe in pipe technology not less than 3 mtr depth of outer dia 76.3 mm and inner pipe dia 42.4 mm filled with crystalline conductive mixture, outer pipe to be covered with Back fill compound not less than 50 Kg, complete earthing in multiples if required (Considering the location and quality of sand) to obtain less than one ohm resistance, including earth work, PCC pit and CI pit cover and removal of debris from site. Model ASEEL-39 (Copper coated) of make Ashlok electrode and Elmech’s method of earthing or equivalent as approved by accepting officer testing complete as directed by Engineerr-in-charge. |
| 57 | Supply and Aesthetically designed Tata Motors branded 7.2KW Charger with with following specifications Integrated Charging gun b. Integrated with all Electrical protection devices for Electrical safety .Reduces charging time of Nexon EV max to 6-7 HRs for full charge LED indication for easy identification of charging status |
| 58 | Supply and fix Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws fixed with MS clamp 40 x 6 mm and 2 set with nut & bolt as specified type 410 SP-31 (9 Meter long) duly painting with two coats of aluminium paint over a coat of red oxide primer on exposed surface and one coat of black bituminious paint on embedded surface incl writing of Pole Numbers etc., and marking of two black & two yellow strips with synthetic enamel paint upto 1.2 Mtr height and making good disturbed surface complete all as specified and directed. |
| 59 | M&L for replacement of Pole Mounted Juntion Box 254 x 180 x 111 mm, having insulated and made out of thermoplastic polycarbonate with glass fibre reinforced, rated for Degree of Ingress Protection IP 66 in accordance with IEC 60529, IK 07, weather proof for outdoor installation (with knockouts for cable entry) having gasket material shall be Polyurethane and gasket shall be internally embedded, tested at 650°C, with Plastic Mounting Bracket, Din Rail, Mild Steel flat Iron Clamp, Nuts, Bolts and washers, with MCB SP 6 Amps, 'B' Curve, 10 KA, complete all as specified and as directed. Make: Cape Electric Model No. TKPS 2518-11M or HENSAL Cat Part No. KF 2525B or equivalent SPELSBERG/RITTAL/SCHNEIDER |
| 60 | S&F PVC insulated unarmoured & PVC sheathed copper cable 3 core of cross sectional area 1.5 Sqmm for providing necessary electrical connection from Sheet metal enclosure to light fittings including with suitable size copper lugs complete all as specified and directed. |
| 61 | Material and labour for PCC (1:4:8) type D2 using 40 mm graded aggregate as in foundations, filling and mass concrete etc using necessary formwork and finishing the exposed surfaces even and smooth without using extra cement, as directed by the Engr-in-Charge. |
| 62 | Material and labour for PCC (1:3:6) type C2 using 40 mm graded aggregate as in foundations, filling and mass concrete etc using necessary formwork and finishing the exposed surfaces even and smooth without using extra cement, as directed by the Engr-in-Charge. |
| 63 | Material and labour for PCC (1:2:4) type B1 using 20 mm graded aggregate as in coping of poles / pipes / strip alignment etc using necessary formwork and finishing the exposed surfaces even and smooth without using extra cement, as directed by the Engr-in-Charge. |
| 64 | M&L of Galvanised Steel Tubing Pipe 50mm bore (02 Nos), light grade having 70 Cm with PVC Bends for Incoming and Outgoing Cables, grouting in Cement Concrete, complete all as specified and as directed.NOTE : Cement Concrete will be measured and paid for separately. |
| 65 | Supply and fixing in replacement brackets made out of 40 mm dia light grade GI Pipe 1.50 mtr long bent to shape and size fixed on location using new 30 x 5 mm GI clamps- 02 Nos made to shape incl nuts, bolts & washersof suitable size including applying two coats of aluminium paint over a coat of red oxide zinc chrome primer incl taking down existing bracket complete all as specified and as directed by the Engr-in-Charge. |
| 66 | Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. complete all as specified and directed. |
| 67 | Supply and fixing GI tubing 50mm bore (light grade) for fixing of Solar Post Top lantern complete all as specified and as directed by Engineer-in-Charge. |
| 68 | S&F for Timelite Distribution Board with Astronomical Time Switch, Contactor 32 Amps, 3 pole, MCB TPN 40 Amps with electrical connection complete all as specified and directed by Engr - in - charge. |
| 69 | Taking out of interlocking paver block, any shape or size and Re-laying the same after removing all vegetation, algae, grass etc, laid to proper slope & gradient over sand cushioning complete all as specified and directed.NOTE : Sand, if required for connection of cushioning level will be measured and paid seperately. |
| 70 | M&L for preperation of new surfaces and applying three coats of white wash on walls complete all as specified and directed. |
| 71 | Supply and fixing LED Flood light fitting 80 Watt 230 V AC outdoor type with high pressure die cast housing, toughened glass, heat resistant complete with individual LEDs with secondary lens optics with IP66 ingress protection, 4 kV in-built and 10 kV external surge protection with minimum efficacy 120 lm/W and CCT 5700 K complete all as specified and directed. |
| 72 | Supply and fixing LED wall lights fitting 1x 15 W, 220V, enviromental friendly, new generation,decorative IP 66 LED UP-down Luminaire with wall surface mounting using COB LED as light source connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specifide and directed. |
| 73 | Supply and fixing LED spike lights fitting 1x 9 W, 220V, enviromental friendly, new generation,decorative IP 66 LED spike light Luminaire with wall surface mounting using COB LED as light source connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specifide and directed. |
| 74 | Supply and fixing LED Monochromatic buried uplighter ideal for uplighting landscape,facades, columns & features with multiple optics and saturated tone of white 2W, enviromental friendly,connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specifide and directed. Make: ADORN MINI / crompton/Philips. |
| 75 | Supply and Fixing of 16W warm white ceiling recess mounted spot light having CCT 300K, system efficacy > 100lm/W, AC 120-300V, 50 Hz, Burning Hr 50,000, CRI 80+,IP 20, with high efficiency anodized aluminium reflector complete all as specified and directed . |
| 76 | Supply and Fixing of 6W warm white ceiling K type LED luminaries conforming IS: 10322 (PART-5/SEC-1)-2012 and having CCT 3000K, system efficacy > 510lm/W, AC 100-300V, 50 Hz,PF>0.9,.028A complete all as specified and directed . |
| 77 | S & F LED Step light IP 65 fitting complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable complete all as specified and directed . |
| 78 | S&F LED flex strip light 5 watt , 45m to 50m length, IP 65, 5watt/metre, any colour including suitable driver and connecting up with three core flexible copper conductor cable of suitable size, as in repairs, complete all as specified and directed. |
| 79 | Supply and fixing LED Bollard light fitting 10 Watt 230 V AC outdoor type with IP65 rating, surge protection 4 KV, CCT 5700K, CRI > 70 complete all as specified and directed. |
| 80 | Supply and fixing LED Post Top light fitting 15 Watt 230 V AC outdoor type with IP65 protection complete all as specified. |
| 81 | Note: Schedule of credit (SCHEDULE OF CREDIT) amount of Rs ________ mentioned on Page No ____ shall be deducted from the total quoted amount of BOQ. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 03, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysSep 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender