Tender For Construction For Upgradation Of Mirik Hospital From 30 To 100 Bedded Sd Hospital, Darjeeling - Supply Installation Testing and Commissioning of Fire Detection System.
Tender Value
22.71 Lakhs
Estimated cost
Bid Submission
01 Sep 2026
17 days left
EMD
45426
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Darjeeling → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction For Upgradation Of Mirik Hospital From 30 To 100 Bedded Sd Hospital, Darjeeling - Supply Installation Testing and Commissioning of Fire Detection System.
BOQ
| Sl. No. | Item Description |
| 1 | Supply,Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector ( VDS / UL / LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector is to be provided without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. Degree of protection as per OEM Standard. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 2 | Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / LPCB / FM approved ) with in built short circuit fault isolator as per NFPA (Note : MCP without built-in fault isolator is also acceptable with one independent short circuit fault isolator is to be provided without extra cost). Degree of protection as per OEM Standard. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 3 | Supply, Installation, Testing & Commissioning of Addressable Loop Powered /panel powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator as per NFPA (Note :Hooter without built-in fault isolator is also acceptable with one independent short circuit fault isolator is to be provided without extra cost). ( VDS / UL / LPCB / FM approved ) approved. Degree of protection as per OEM Standard (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 4 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector ( VDS / UL / LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 58 deg. C to 68 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector in the loop is to be provided without extra cost) the detectors should have built in response indicator with LED indicator.Degree of protection as per OEM Standard.(Approved Make: Cerberus Pro / Honeywell/ Johnson Controls/Edward/Secutron/Securiton/Apollo/ Morley / Eaton / GST/Ravel/Notofire) |
| 5 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. (Approved Make: Cerberus Pro / Honeywell/ Johnson Controls / Edward /Secutron/Securiton/Apollo/ Morley / Eaton / GST/Ravel/Notofire) |
| 6 | Supply, Installation, Testing & Commissioning of Addressable OPC complied Monitor Modules (VDS / UL /ERTL/LPCB/FM approved) for monitoring Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make: Cerberus Pro / Honeywell/ Johnson Controls /Edward/Secutron/ Securiton/ Apollo / Morley / Eaton/GST/Ravel/Notofire) |
| 7 | Supply, Installation, Testing & Commissioning of Addressable Control Modules/ Relay Module ( VDS / UL / LPCB / FM approved ) for controling Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator / External fault isolator with adjustable setting parameter likes(Resistive, Inductive or capacitive) of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required (Approved Make: Cerberus Pro / Honeywell/ Johnson Controls Edward/Secutron/Securiton/ Apollo / Morley / Eaton / GST/Ravel/Notofire) |
| 8 | Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box with metallic cover having two LED and Degree of protection as per OEM Standard etc. complete with all connections etc as required. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire/System Sensor/Agni Suraksha ) |
| 9 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable,600/1000V rated with annealed copper conductor havingXLPE insulation, steel wire armouring & FRLS/HFFR outersheath complete as required. (Approved Make : Finolex/ Gloster/ RR Kable/ Polycab/ KEI ) |
| 10 | Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel (VDS / UL / LPCB / FM approved ) suitable for the devices as stated inthe previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. |
| 11 | Four Loop Panel. (Approved Make : Cerberus Pro / Honeywell/ Johnson Controls / Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton / GST/ Ravel/ Notofire) |
| 12 | NOTE :- 1) The Fire Alarm system shall comply with latest requirements of --(i) National Fire Protection Association (NFPA) Standards, (ii) IS 2189 ,(iii) NFPA 70 National Electric Code, (iv) NFPA 72 National Fire Alarm & Signaling Code , (v) Local Statutory Regulations , (vi) Manufacturer Recommendation. vii) System should be integrated with the components like FACP, Detectors, MCP, Hooter, Monitor Module, Relay Module, etc. and all these components should be of same brand. |
| 13 | TESTS :- 1) The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2) Before energizing the cables and wires, inspection and check for correct connections, and test for short circuits, ground faults, continuity, and insulation and other tests as per applicable Indian/International standards must be done. |
| 14 | TERMS & CONDITIONS :- |
| 15 | The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. |
| 16 | Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules. |
| 17 | GST @18% |
| 18 | CLW Cess @1% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedSep 01, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysSep 03, 2026
Bid Opening Date
Technical bids will be opened and evaluated.