Tender For Electrical Installation And Renovation Works At Sarenga Bphc, Bankura.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
31 Aug 2026
16 days left
EMD
1.40 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bankura → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Electrical Installation And Renovation Works At Sarenga Bphc, Bankura.
BOQ
| Sl. No. | Item Description |
| 1 | Dismentling the existing E.I. work incl existing defective , non functioning Panels , PBDB, LBDB, Main Switch etc by Co's own tools & tackles by maintening normalcy as far as possible as per direction of EIC. |
| 2 | Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection,on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment of the following sizes as to GS. (Normal power - 02 Nos, DG power - 01 Nos ) [ Make:- Legrand/Schneider/Siemens] 8way Enclosure upto 160 Amp |
| 3 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [ Make:- Legrand/Schneider/Siemens] |
| 4 | 6 way Enclosure (for DG Power only) |
| 5 | 8 way Enclosure (for Normal Power only) |
| 6 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [ Make:- Legrand/Schneider/Siemens] |
| 7 | 2+12 way Enclosure |
| 8 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment. [ Make:- Legrand/Schneider/Siemens] |
| 9 | 8 way VTPN |
| 10 | 8 way HTPN |
| 11 | 6 way HTPN |
| 12 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermaland fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure andnecessary connection as to GS. [ Make:- Legrand/Schneider/Siemens] |
| 13 | 100 Amp |
| 14 | 125 Amp |
| 15 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. [ Make:- Legrand/Schneider/Siemens] |
| 16 | 415 V, 63A FP |
| 17 | 240 V, 40A DP |
| 18 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail ofexisting DBs and necessary connection as to GS. [ Make:- Legrand/Schneider/Siemens] |
| 19 | 6A-32A SP MCB |
| 20 | 63A TP MCB |
| 21 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire [Make:- Finolex/Havells/RR Kable / Polycab/Gloster/KEI] partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [only PVC Rigid Conduit on ceiling and remaining portion concealed] Average run 9 mtr. |
| 22 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire [Make:- Finolex/Havells/RR Kable / Polycab/Gloster/KEI] partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. On Board. |
| 23 | Supply & Fixing 240 V, 2 x 6A, plug socket with separate 2 X 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 200x150x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 24 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 25 | Supply & Fixing 240 V, 2 nos. 6A, & 2 nos. 20A plug socket with separate 2 nos. 6 A & 2 nos. 20A Piano key type switch, indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 26 | Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch with indicator & 16A kit-kat flush type fuse (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required ( Computer / Medical Instrument Board ) |
| 27 | Supplying and Drawing 1.1 KV single core stranded 'FRLS'PVC insulated & unsheathed copper wire (Make- Finolex/Havells/KEI/Gloster/Polycab) of following sizes in thick heavy gauge polythene pipe and necy. Connection as required incl. cutting channel of (40mm x 40mm) / (43mm x 43mm) size on masonary wall with S&F heavy gauge 19mm/25mm dia 3mm thick polythene pipe by means of iron hooks and mending good damages to building works. |
| 28 | 2 x 1.5 sqmm + 1x 1.5 sqmm (for Separate Plug) |
| 29 | 2 x 2.5 sqmm + 1x 1.5 sqmm (for Power Plug) |
| 30 | 2 x 4 sqmm + 1 x 2.5 sqmm (for AC) |
| 31 | 2 x 6 sqmm + 1 x 4 sqmm ( from TPN MCB DB to SPN MCB DB s ) |
| 32 | 2 x 6 sqmm + 2 x 4 sqmm (for Auto Clave M/C ) |
| 33 | Supplying of following sizes Al. armoured PVC/XLPE [Make:- Finolex/Havells/RR Kable / Polycab/Gloster/KEI] as per direction of EIC. |
| 34 | 4 core 10 sqmm (For Security light) |
| 35 | 4 Core 35 sqmm ( from VTPN to MCBPBDB) |
| 36 | 4 core 70 sqmm ( from Panel to VTPN & Panel to DG & DG to VTPN) |
| 37 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish. |
| 38 | From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. |
| 39 | Above 35 sqmm to 95 sqmm at an average depth of 100 mm in floor/pavement/wall etc. |
| 40 | Laying of one No. cable of following sizes in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed |
| 41 | Upto 35 sqmm |
| 42 | above 35 sqmm upto 185 sqmm |
| 43 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : |
| 44 | 4 core 10 sqmm |
| 45 | 4 core 35 sqmm |
| 46 | 4 core 70 sqmm |
| 47 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : |
| 48 | 4 core 10 sqmm |
| 49 | 4 core 35 sqmm |
| 50 | 4 core 70 sqmm |
| 51 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. |
| 52 | 50 mm dia |
| 53 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. With 25x25x3mm angle iron support 200x50x1.25mm (18SWG). |
| 54 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire. |
| 55 | upto 50 sqmm [F-3/6(i)] |
| 56 | Supply & delivery of AC 240V 50 Hz 48\\" sweep (1200 mm) ceiling fan complete with down rod, Canopy, fork incl S & F of P - 2 type capacitor as per IS specification & proper Manufacturer certificate of the capacitor and Safety Wire (supplied at the time of delivered the fans ) etc. without regulator, (Make- Usha 1200MM STRIKER PWD ISI 1 STAR (Safety Wire & S3 Capacitor) Br /Orient Electric- New Breeze (5yrs warranty),1200 mm sweep; 44W; 320 rpm; 225 cmm; 3 star ac ceiling fan or equivalent model of Crompton Greaves and as per direction of EIC as per direction of EIC. |
| 57 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. |
| 58 | Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting . |
| 59 | Supply & Fixing Socket type fan regulator (Step type) (Brand approved by EIC) on existing sheet metal switchboard with bakelite/perspex top cover by screw after making housing for regulator knob by cutting bakelite/perspex top cover incl. making necy. connections etc. |
| 60 | Supply and Delivery of 230 V, 50 HZ, 450 mm, , high flo oscillating type, metal blades and metal canopy. ( Make:- Crompton Cat No- 450mm SSTORM 2 Plus ( Metal Blade & Metal Canopy/Orient Electric/USHA ) |
| 61 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length |
| 62 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. As per G.S |
| 63 | 1.5 sqmm |
| 64 | 2.5 sqmm |
| 65 | 4.0 sqmm |
| 66 | 6.0 sqmm |
| 67 | S&F angular holder (Anchor) on 3\\" wooden double round block incl. S&F 9 Watt LED lamp Philips make as per direction on EIC (LED Lamp Make: Signify(Philips)/Wipro/Crompton) |
| 68 | Supply & Delivery of Single LED Tube light fittings (make- Philips, Cat No. TMC-502 P1xT-LED 22W / equivalent model of CG Fittings- IGP161LT8-16 1 x T8 with 01 Nos LED TUBE Philips Cat No- Mas LED Tube 1200mm 18W 865 T8 I – 2100 lm /Crompton- Cat No- LTB-20-865-(2) or equivalent model of Havells/Wipro) |
| 69 | Supply & Delivery of twin LED Tube light fittings (Make- Signify (Philips), Cat No. TMC-502 2XT-LED 22W or equivalent model of CG Fittings- IGP162 LT8-16 2 x T8 with 02 Nos LED TUBE Philips Cat No- Mas LEDTube 1200mm 18W 865 T8 I – 2100lm /Crompton- Cat No- LTB-20-865-(2) or equivalent model of Havells/Wipro) |
| 70 | Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 71 | Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. |
| 72 | Supplying & Fixing 240 V AC/DC superior type Ding-DongCall Bell (Anchor) on HW board incl. S&F HW board |
| 73 | Supplying & Fixing 250 V Bulk Head Outdoor Light fittings Model [Make: Signify (Philips) Cat No. WT202W LED6S NW PSU S2 PC / Crompton/Wipro) By Screw on wall/ceiling etc. |
| 74 | S & D of 220 V 120 W LED Flood light as per direction of EIC. (Make : Crompton Cat No. CFS -504-120-57-60D-SL-GL-NSG/Signify (Philips)/ Wipro) |
| 75 | Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as required |
| 76 | Supply and delivery of 240 V, 50 Hz, 1420 RPM Heavy duty best quality AC Metal body Exhaust fan complete with all accessories incl. making hole in wall and mending good damages and smooth cement finish etc. as practicable as possible also providing necy. length of PVCinsulated wire and making connection as per direction of EIC. (Make : EPC/Crompton Haevy Duty/Usha Heavy Duty)12\\" (30cm) |
| 77 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter including S&F Louver shutter on wall with necy. nuts & bolts (6mm dia x 62mm long) |
| 78 | 12\\" (30cm) |
| 79 | Engraving the deptt. number with 10 mm lettering on the body of fan upto 10 letters incl. hifen, stroke or stop as to GS |
| 80 | Painting upto 10 letters of the engraved number with approved black /red paint as required as to GS |
| 81 | Extra for additional one letter incl. hifen, stroke and stop as to GS |
| 82 | Extra painting for additional one letter of the engraved number with hifen, stroke etc. with black or red paint as required as to GS |
| 83 | Supply & fixing automatic single phase AC starter of 25 Amp capacity equipped with Timecheck, Voltcheck & Ampcheck and 3-digit display to be fixed surface enclosure as to G.S. Including S&F of 4 Module surface or concealed mounting enclosure box. (Make- Electron-model no.-OPL-3+ or equivalent model of LK(L&T)/Legrand) |
| 84 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch, with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. Connections with PVC Cu wire and earth continuity wire etc. |
| 85 | Supply & Fixing 240 V, 25 A, 3 Pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. |
| 86 | Supply & delivery of 2 Star or higher rated 1.5 Tr. capacity split Air-conditioner machine fitted with Rotary/Scroll compressors, LCD remote & all other accessories suitable for Refrigerant-R32/R410A. (Make: - O-General Cat No. ASGA18BMAA-B (R32) /Mitsubishi Electric Cat No. MS-MU AGZ18VF or equivalent make of Voltas) |
| 87 | Installation, testing & commissioning of the above-said split ACs incl. supply & fixing required Angle Iron Structure on wall for placing outdoor unit & mending good the damages as per direction of E.I.C. [NS] |
| 88 | Supply & Installation of Extra Add-on items- HVAC grade 5/8\\"(for suction) & 1/4\\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation including shaddle,screw, insulation tape, fastner etc for above AC machine as per direction of EIC. (Copper Pipe Make: Nippon/Uniflow/Rajco/Venam/Camiflow/Godrej & Nitrile Rubber Insulation Make: A-flex/K-flex/Supreme) |
| 89 | Supply & Laying 4 core 2.5 sqmm PVC insulated & unarmoured Copper Cable for 2/1.5 Tr. Split A.C Machine. [Make:- Finolex/Havells/RR Kable / Polycab/Gloster/KEI] |
| 90 | Supply, laying and fixing of condensate drain water pipe for split AC machine of 19/25 mm dia , including all required fittings and accessories such as bends, elbows, tees, couplers, wall sleeves, hangers, supports, clamps, anchors, providing proper slope for free flow of condensate water, and making good the damages, complete as per direction of Engineer-in-Charge.(Make: Finolex/Supreme/Oriplast/Astral or Any PWD Approved reputed brand /as per choice of Engineer-in-Charge) |
| 91 | S&F Auto clave starter unit of size 16\\" x 12\\" x 6\\" made from heavy gauge CRC sheet metal (16 SWG) with 1no. Front openable hinged type door fixed in wall on flate iron frame. The interconnection should be made by suitable sizes cu wire. The box should be painted by power coated paint & having following accessories:-a) 4 pole power contactor ML3 AC3 -40A, AC1-45A Add on aux. contact block 2 NO + 2 NC (Make- L&TCS90907LOOO)/ Sieems/ABB- 1.00 Nosc) 40A 4 pole MCB Isolator (Legrand)- 1nod) Push Bottom Switch - 2nos. (Make-Gen Next Push Button-Cat Nos-EMN¨FD1 or Other Equivalent make)e) LED Indicator lamp (ESBEE) - 3 Nos.(Make-Gen Next Pro LED Indicator 22.5 mm Cat No-EPL or Other Equivalent Make)f) 200A Capacity 4 way terminal - 1.00 Nos. (All electrical Installation will be make of LK(L&T)/Legrand/Siemens/ABB) |
| 92 | Supply & Delivery of 100 W LED outdoor street light fittings as per direction of E.I.C (Make:- Crompton Cat No. CRP-411-100-57-SL-GL-NSG- Signify (Philips) / Wipro) |
| 93 | Fixing only outdoor / street light type fluorescent light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall and painting. |
| 94 | Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint. |
| 95 | Inter connection between loop box to fittings by 1.1KV 3x1.5sqmm single core stranded FRLS PVC insulated & unsheathed copper wire through 13mm/19mm Polythene pipe or PVC Conduit pipe incl. necy. Fittings as per direction of EIC. |
| 96 | Providing CC (6:3:1) base block (around the pole) dimension 0.60x0.60x0.76 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) incl. drilled hole in pole suitable for alkathene/polythene pipe entry, for street light wiring, without Loop Box. |
| 97 | S&F Timer Control Unit assembled with following accessories: - i) 12-way SPNDB Box (L & T/Legrand/Siemens)-1 no. ii) 16A DP 30mA RCBO (Make: L&T Cat no.-AUF3C202530 or equivalent model of Legrand /Siemens ) - 1 no. iii) S&F Multiple functions - Daily or weekly time switch Programme - 5 years clock working reserve. (Legrand-4126 31 /L&T/1no. iv) 22A 3-pole power contactor (L&T: Type-MNX22 ; Cat no.-CS94980 & CS94981 with 1NO + 1NC Aux. Contacts or equivalent model of Siemens/ABB)---1set. v) Melamine terminal block-2 nos. vi) LED indicating lamp (L&T: SIL R 240V)-1 no. vii) ON/OFF Push = 2 nos (L&T-Gen Next Push ButtonOR OTHER EQUIVALENT MAKE) viii) 6 amp auto mannual toggle switch (Make- L&T or equivalent make as approved by E.I.C) All control circuit wiring would be made by 1x1.5 sqmm FRLS stranded Cu wire(Brand approved by E.I.C) and the I/C & O/G circuit with 1x4sqmm copper wire of suitable length maintaining colour code incl taping, socketing to complete the work. (All electrical Installation will be make of LK(L&T)/Legrand/Siemens/ABB) |
| 98 | Supply & delivery of cubical type L.T. Distribution panel board of |required size wall cum floor mounted compartmentalized with maple arrangement having rigid & self supporting structure fabricated from 2mm thick CRCA sheet steel with M/S angle frame. The panel board consisting of the following switches & the Panel board to be get inspected by EIC -- (All electrical Installation i.e. incoming, outgoing and mesuring instruments will be make of LK(L&T)/Siemens/ABB)A)Incoming Arrangement.a) switch disconnect or fuse (panel mounting cubical type) conform to I813947 in open execution three pole & Neutral AC 23A, 50HZ, 415 Voll400 Amp with 3 nos 400Amp DIN type HBC fuse link, -- 01 Nos |
| 99 | B)Bus_ Section:415 V 600 A. electrolyte grade tinned copper bus bar with vertical section of required size same in size for Phase RYB, & neutral bars of each approx 375 Sq.mm cross section of each Copper Busbar. & 20x 5 mm Al. Bar for earth. A bus bar shall be fixed with FRP chair & the entire bars are insulated with PVC heat Sinkable sleeve of suitable size & color as per direction of E.I.C |
| 100 | C) Outgoing arrangement: Supplying and fixing 415V, TPN SFU open execution in existing SS enclosure/cubical with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make: LK(L&T)/Siemens/ABB) a) 415V,125A TPN SFU----- 02 Nos.b) 415V,100A TPN SFU----- 02 Nos.c) 415V,63A TPN SFU----- 02 Nos. |
| 101 | Metering panel:a) S& Fixing 0-500 V.3PH , Digital Voltmeter of size 96 sq. mm. (square type) with inbuilt selector Switch Accuracy Class 1 .(Make : LK(L&T)/ABB/SIEMENS)--- 01 Nosb) S& Fixing 0-800 Amp. 3Ph, Digital Ammeter of size 96 sq. mm. (square type), Accuracy Class -0.5 With inbuilt selector Switch, (Make : LK(L&T)/ABB/SIEMENS)--- 01 Nos |
| 102 | S&F current transformer of size 600A /5A- (Make: Kappa/AE ) -- 03 NosS&F 20 Amp. Bakelite tuses base & bridge with 7 duy HRC fusc link GE/ Approved Make -- 03 nos S&F Danger board -- 01 Nos.Inter connection :- 1) Connection between 400A TPN SFU with Busbar and SFU outgoing with cable alley terminal block by approx. 250 Sq.mm cross section of each Copper Busbar.2) Connection between 125A TPN SFU with Busbar and SFU outgoing with cable alley terminal block by Single Core multi strand Copper 35 Sq. mm UA Cable.3) Connection between 100A TPN SFU with Busbar and SFU outgoing with cable alley terminal block by Single Core multi strand Copper 25 Sq. mm UA Cable.4) Connection between 63A TPN SFU with Busbar and SFU outgoing with cable alley terminal block by Single Core multi strand Copper 16 Sq. mm UA CableEarthing.Separate earth bolts/Bars -2 Nos will be provided in panel board inboth sides as per drawing. |
| 103 | Cable entry arrangement will be provided in the cubical panel in verticalposition of size with reqd sizes of AC/DC make connector indicating phase & neutral for each outgoing main switches & gland plate must be placed at the bottom of the panel with detachable type as per direction of E.I.C.Painting.The complete panel board shall be painted by 2 coats of powder coatedsynthetic enamel Paint over two coats of R.O. primer of Approved make& brand & color as per Direction of E.I.C. |
| 104 | Constructural Details:All incoming & outgoing panel mounted cubical Switch disconnector fuse shall be housed in Respective compartment with hinged & gasketted Door at front. All doors shall have Panel lock Arrangement. The panelhall be properly Gasketted to prevent ingress of dust & moisture & Remaining. Busbar will be properly arrange & all Switches shall be fixed by M.S. nuts & bolts On angle /flat iron frame base.as per direction of E.I.C.Installation:The panel should be installed as per site condition & requirement with brick and PCC foundation etc to complete the installation as per Direction E.I.C. |
| 105 | Supplying and fixing 415V, 100A, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts With cable end box . (Make: LK(L&T)/ABB/Siemens) |
| 106 | Supplying and fixing 415V, 63A, TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S&F 3 nos. DIN type HRC fuse as per rating. (for OLD Building & Laboratory) |
| 107 | Supply , delivery at site on foundation , testing& commissioning of 30 KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-IV+ Compliant Engine & Acoustic Enclosure having following specifications : (Make: Jakson/Greaves Power/ Eicher) |
| 108 | ENGINEEngine Make: Cummins/Volvo/ Greaves Cotton Limited. |
| 109 | Engine Type : 4 Stroke Diesel Engine, RPM: 1500,Rated Output : 24 KW or Higher, Duty: PRIME, Cooling : Engine water pump, radiator, coolant additive concentrate, by pass thermostat. Cylinder: 4 or higher. Aspiration : Turbo Charged, Charge air Cooled. Type of Governer : Mechanical/Electronic, Fuel Tank Capacity : Minimum capacity 70 Ltrs, Fuel Consumption at 75% rated Load with Radiator or Fan : 6.3 Ltr./ Hr. or Less. Fuel Consumption at 100% rated Load with Radiator or Fan : 7.45 Ltr./ Hr. or Less |
| 110 | Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter. |
| 111 | Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine overspeed indicator, Battery charging and low battery indicator. |
| 112 | Exhaust Silencer: Residential Type |
| 113 | Starting system : 12V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard. |
| 114 | Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning. |
| 115 | Integrated Control System : |
| 116 | Physical Construction- LCD alpha-numeric display with 8 membrane key inter face, Non metallic enclosure, LED Display- fault warning and generator set status, |
| 117 | Governor & Speed / Frequency regulator- Integrated eltronic Governing |
| 118 | Operator Interface - Manual Stop/Start, Remote Start/Stop Cyclic cranking, Alpha numeric screen, Alternator trim adjustment. |
| 119 | 3-ph AC Ammeter, Frequency, PF Meter,KW meter,KVA meter,Indication for alternator supply |
| 120 | Other Accessories - Operating temperature range 0-60 degree C, common fault alarm, common shutdown, Date and time stamp for alarm, Dimension (in mm) are 267x378x157. |
| 121 | Running time indications number of hours of operation and service intervals, service due indications, Low lubricating oil pressure, High water temperature, Start failure, and DG over load |
| 122 | Engine Protection- High coolant temperature (warning & shutdown), Low/High battery Voltage (Warning Low Coolant level shutdown) |
| 123 | Alternator:Make: Stamford/ Leroy Somer/Mecc alte / Crompton Greaves.Rating : 415 V., 3Ph. 50 Hz., 30 KVA, 1500 rpm, Type : Brushless, self excited and self regulated (AVR) , Insulation : Class H, Voltage Regulation (max) : ±1%, Winding connection : Star with Neutral, Total Harmonic distortion in output waveform : No Load<1.5%, Non distorting balanced linear load<5% |
| 124 | AMF Control Panel : Inbuilt AMF Panel including display of all parameter & safety indication with following features: |
| 125 | The AMF Control Panel should be inbuilt and , suitable for a 415V, 3-phase, 50Hz system. shall consist of the following features: 1. Microprocessor based AMF Controller having safety features with display of following Engine & Alternator parameters:- 2. Engine Display features:- Low lube oil pressure, High water temperature, Overspeed, Low Fuel Level, RPM, No. of Hours Run, Battery Voltage. 3. Safeties:- LLOP, HWT, LFL, Over Speed. 4. Alternator Display features:- Ampere, Voltage, Frequency, Power Factor, Kw, Kwh, KVAR 5. Safeties: Over Current, Over/Under Voltage, Over/Under Frequency, Short Circuit .6. Current Transformers of suitable ratio. |
| 126 | 7. 2 Nos. 63Amps, 4Pole, AC-1 Duty Power Contactor for DG & Mains. 8. 2 Nos. 63Amps, 4 Pole, 36KA MCCB with necessary thermal magnetic protections for DG & Mains. 9. 1 No. 63Amps, 4 Pole Manual On load Changeover Switch for Bypass arrangement. 10. Indicating Lamps for Mains ON (RYB), Mains Load ON, DG ON (RYB)/DG Load ON, DC , ON. 11. MCB for Control Protection 12. Selector Switch for Control ON/Off 13. Selector Switch for Auto/Manual 14. Selector Switch for Contactor ON/Off Manually. 15. Push Button for Engine Start/Stop Manually 16. Battery charger with auto trickle & boost charging facility. 17. Electronic Voltage Regulator (EVR) for Mains Contactor Coil 18.Multifunction Digital Display Meter for display of Voltage, Ampere, Frequency, Power , Factor, Kw, KWH. |
| 127 | ACOUSTIC ENCLOSURE Acoustic enclosure shall be made of specially procured 16SWG CRCA Sheet and structural sheet metal Base frame and comply with CPCB norms with following features: 1. The most compact, six sided, close, modular construction and detachable 2. Meet CPCB / MOEF norms. 3. Sound level < 75 DbA at one meter distance under free field conditions as per norms. 4. Easy accessibility around the DG Set, which ensures optimum serviceability. 5. Special power coated enclosure, weather proof, corrosion resistant, environment friendly. 6. Specially designed lifting hooks. 7. Use of high quality hardware ensures longer life of enclosure. 8. Provision for emergency stop facility. |
| 128 | Base Frame : Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook. |
| 129 | TERMS & CONDITIONS |
| 130 | (i) Rate should be quoted inclusive of all applicable taxes and Duty etc. |
| 131 | (ii) All materials, equipments & accessories must conform to relavent IS /IEC specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer. |
| 132 | (iii) Nacessary manufacturer's test certificate for Desiel Engin, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment. |
| 133 | (iv) Copy of \\"Type Approval Certificate\\" and Certificate of \\"COP\\" must be produced at the time of delivery issued from competant Authority (As per CPCB-II). |
| 134 | (vi) The entire set must be warranted atleast 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier. |
| 135 | Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 x 19/8 stranded GI (Hot Dip) wire (4 Mts. long), 25 mm dia x 150 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts |
| 136 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 137 | Connecting the equipments to earth busbar including S & F No.7/14 SWG GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. |
| 138 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. |
| 139 | Extra for treatment of soil by using salt & charcoal or coke for plate electrode. |
| 140 | Dismantling all types of plain cement concrete works, stacking serviceable materials at site and removing rubbish as directed within a lead of 75m.(a) upto 150 mm thick |
| 141 | S& laying 2.5 sq. mm. 10 core Armoured multi core multistrand PVC insulated flexible Cu cable in Suitable uPVC / GI pipe from DG to separate AMF panel. [Make: Gloster/ Polycab/Havells/RR Kabel/KEI] |
| 142 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, includingfilling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. |
| 143 | Extending the exhaust pipe with 75 mm. dia MS black pipe (Thickness 4 mm) including connection with the existing silencer attached with the flexible coupler and S&F flange, nuts, bolts & washers etc. & necessary fixing materials etc. as required from DG set upto 2.5 Mts high of the near higher installation with Asbestos rope / glass wool insulation and chicken net and Aluminium fol covering, with end cap with suitable high temperature painting. and making insulation by 2\\" glass wool including netting arrangement and covered with aluminium clading as per direction of the EIC. |
| 144 | Making insulation by 2\\" glass wool including netting arrangement and covered with aluminium clading as per direction of the EIC. ---- Residential Type Silencer of DG Set. |
| 145 | Supply and fixing of Special type MS angle iron bracket support to vertically extended exhaust pipe made up of 40x40x6 mm. MS angle with flat iron clamp with nuts, bolts & washers etc. for 90 mm. dia (Vertical Run) and structure should be proper grouted on ground by PCC Structure and as per the direction of EIC |
| 146 | S&F rain protection canopy. |
| 147 | Supplying & erection of foundation of 30 KVA D.G.Set on outdoor, having dimension given below:- a) 300 mm deep (below ground) PCC of size 3150 mm (L) x 1700 mm(W) having thickness 100 mm after single brick flat soling on the ground after excavation of the earth.b) 15-inch thick brick wall from the 300 mm deep (below ground) PCC to 600mm (above G.L.), i.e. around the PCC (total Brick Wall Height 900mm), and keeping the central part as follows. c) Filling the hollow portion with a mixture of sand & shifted soil.d) Construct a 06 inch thick PCC slab at the top of the brick foundation of size 3150 mm (L) x 1700 mm (W) incl punning, finishing upto the completion the foundation structure and providing foundation bolts, nuts, etc. [Foundation Size: 3150 mm x 1700mm & 600 mm above GL and 300 mm below GL] [N.B: On-site DG set foundation size may be changed as per site condition and manufacturer standered, bidders are requested to visit the site and final execution may be done as per manufacturer recommendation and duly approved drawing by EIC] |
| 148 | Shed Work: Supply & fixing of Zn-Al alloy(55% Al & 45% Zn) coatings of 150 grams per sq. mtr (followed by colour coated on both sides) steel sheet work with incl. the supporting angle iron frame or MS structure with hollo section (Make-TATA/ JINDAL/Equivalent) work fitted & fixed with suitable inclined at both side as per direction of EIC. sheet ridging fitted with self taping screws EPDM washers etc. to complete 300 mm laping on each way with .75 mm sheet. Priming one coat on steel or metal surface with synthetic oil brand primer of approved quality incl. smoothing surfaces by sand papering.Painting with best quality synthetic enamel paint of approved make and brand lincl. smoothing surface by sand papering etc. incl using approved putty within on surface if necessary ( on steel surface 2 coat).[N.B: On-site DG Shed size as per site condition and manufacturer standered, bidders are requested to visit the site and final execution may be done as per manufacturer recommendation and duly approved drawing by EIC ] |
| 149 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: |
| 150 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. |
| 151 | Connecting the equipments to earth busbar including S & F 10SWG GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. |
| 152 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe . |
| 153 | i) Supply and fixing of angle iron frame fabricated from 40 mm x 40 mm square four nos hollow bar with cross and radial supportincluding one no 40x40 mm angle iron support in the middle for the Sign board of following size vith suitable three nos. crosss angle support welded with 4 nos angle hook in equal space for fixing on the structure with all necessary welding and fabrication. The structure shall rest in both sides with proper welding as per instruction of EIC. |
| 154 | ii) S&F LED Sign Board made 3 mm thick ACP Sheet (Alstrong/ Aludecor) finished with approved metallic colour as back ground (blue) after router cutting. The riser structure also shall be covered with ACP Sheet.& appx 6-7 inch depth (Both size ACP sheet) |
| 155 | iii) S&F Special type of imported acrylic English letter appx 50 mm thickness flushed on the ACP board made on imported acrylic ACAST sheet. The following letter font shall be in horizontal line as mentioned. |
| 156 | iv) S&F SMD LED inside the board and to run for each letter including wiring soldering etc and fixing the SMPS properly with the specification of the SMD --1. LED colour : White/ Red/ Blue (make-samsung /Nichia /Cree/Hisine)2.Stright : 2 or 3 nos LED per module3. Luminous Flux ; 140 LUMEN4. Life : 70000 burning hoursS, Visibility: 100 meter atleast normal eye6. Power Supply: 1.2 watt to1.6 watt per module7.Input: 230A.C, Output: 12V DC8.Shape of LED : ecrangle or square9. Grade :IP -65 |
| 157 | v) S & F LED Power supply 300/ 400W IP65 50/60Hz frequency, 108 to 305 VAC driver power supply other electrical accessories the panel prepared along with its necessary arrangement (make Hisine/Migion/Cehosa/PWD approved ) |
| 158 | vi) Cost of painting of MS structure with 2 coats of RO primer and one coat of synthetic enamel paint after scrapping with emery paper properly make ICI/Asian paints |
| 159 | vii) Cost of carrying the LED sign board from work shop to sitle Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 31, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysSep 02, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender