Housing Urban and Rular Development Government Departments Closing in 3 days TDR #57002447

Tender For B.O.Q For Balance Electrical Works Of Mushroom Specialist Laboratory At Lalmandi Srinagar 2026-27

Issued by Government Departments · Budgam, Jammu and Kashmir
Tender Value
8.23 Lakhs
Estimated cost
Bid Submission
27 Aug 2026
3 days left
EMD
16461
Bank guarantee accepted
Document Fee
600
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Budgam → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for B.O.Q For Balance Electrical Works Of Mushroom Specialist Laboratory At Lalmandi Srinagar 2026-27

BOQ

Name of Work:- B.O.Q for Balance Electrical Works of Mushroom Specialist Laboratory at Lalmandi Srinagar 2026-27
Sl. No. Item Description
1( 1st floor panel) Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)( Building Distribution Panel ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.with latest ammendment IS61439.Refer SLD .
2Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
3Normal INCOMING:
4a)160A 4P MCCB 25 KAincluding spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make.
5b) 4 No. of Aluminium Bus Bar of 250 Amp.
6Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc.
7a)100 A 4P MCCB 25 KA Legrand/ Shinider/ Eq. standard make.
8b) 4 No. of Aluminium Bus Bar of 200 Amp.
9Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc.
10OUTGOING:
11F.P 40A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
12F.P 63A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
13D.P 63 A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
14c) space for 12 way MCB's
15( 2nd floor panel) Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)( Building Distribution Panel ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.with latest ammendment IS61439.Refer SLD .
16Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
17Normal INCOMING:
18a)160A 4P MCCB 25 KAincluding spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make.
19b) 4 No. of Aluminium Bus Bar of 250 Amp.
20Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc.
21a)100 A 4P MCCB 25 KA Legrand/ Shinider/ Eq. standard make.
22b) 4 No. of Aluminium Bus Bar of 200 Amp.
23Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc.
24OUTGOING:
25F.P 40A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
26F.P 63A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
27D.P 63 A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
28c) space for 12 way MCB's
29( Main Distribution panel) Supplying,Installation,Testing and Commissioning of Cubical Type Indoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42)( Building Distribution Panel ) .The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved.with latest ammendment IS61439.Refer SLD .
30Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
31Normal INCOMING:
32b)250 amp TPN MCCB 35 KA including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make.
33b) 4 No. of Aluminium Bus Bar of 400 Amp.
34Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc.
35d) onload Change over switch 200 Amp for generator.Front operated.
36e) 4 No. of Aluminium Bus Bar of 300 Amp.
37Digital Metering devices, comprising of Voltmeter, Ammeter, Selector Switch, Indicating Lamp, CT Set etc.
38INVERTER INCOMING:
39a)100 amp DP MCCB 10 K Legrand/ Shinider/ Eq. standard make.
40b) 2 No. of Aluminium Bus Bar of 160 Amp.
41OUTGOING:
42a)100A 4P MCCB 25 KA including spreader links, ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/L&T/ABB make.
43a)160A 4P MCCB 25 KAincluding spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ABB make.
44F.P 40A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
45F.P 63A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
46D.P 63 A 10 Ka \\"C\\" Curve MCB Legrand/ Shinider/Semiens/ABB make.
47c) space for 12 way MCB's
48Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor (Polycab Green/Havell Life guard/ Fenolex/ Salzer/RR/Apar make as desired by engineer incharge ), single core cable in surface/ recessed medium class PVC conduit as required.
492 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
502 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
514 X 6 sq. mm + 2 X 6 sq. mm earth wire
524 X 10 sq. mm + 2 X 6 sq. mm earth wire
534 X 16 sq. mm + 2 X 6 sq. mm earth wire
54Supplying and fixing of following sizes of medium class PVC conduit( Anchor/ Ravindra/ Eq. make)along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required, with cement plaster, wall putty , paint, complete
5525 mm
5632 mm
57S/L , testing and commissioning of PVC alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size.
58a)95 sq.mm 3.5 core
59a)25 sq.mm 4 core
60a)35 sq.mm 4 core
61Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) including bends, Tees, cross members and allied accessories with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
62200 mm width X 50 mm depth X 1.6 mm thickness Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 57002447
AUTHORITY Government Departments
TENDER VALUE 8.23 Lakhs
LAST DATE 27-08-2026
Authority
Authority Name Public Works Department
Work Description Tender for B.O.Q For Balance Electrical Works Of Mushroom Specialist Laboratory At Lalmandi Srinagar 2026-27
Basic Detail
Tender No NIT No.124//2026-27 Dt/13/08/2026
Bidding Type Tender
Location
City Budgam
State Jammu and Kashmir
Key Dates
Publish Date 13 Aug 2026
Submission Date 27 Aug 2026
Open Date 29 Aug 2026
Finance
Tender Value 8.23 Lakhs
Tender Fee 600
EMD 16461
Exemption Not Available
Document List
8bea3f4e-d627-420a-b8e4-ce8ec8cc74ac.html
BOQ_1068165.xls
Tendernotice_1 (11).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 13, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 27, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Aug 29, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 5 days

Tender Documents

Download All (ZIP) ↓
html

8bea3f4e-d627-420a-b8e4-ce8ec8cc74ac.html

xls

BOQ_1068165.xls

pdf

Tendernotice_1 (11).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender