Tender For Repair, Replacement And Improvement Of Lt Distribution System By Replacement Of Unserviceable Lt Cables & Switch Gears At Military Hospital Khadki & 41 Arty Div Under Ge (Mh & Rh) Khadki.
Tender Overview
Project Description
Tender for Repair, Replacement And Improvement Of Lt Distribution System By Replacement Of Unserviceable Lt Cables & Switch Gears At Military Hospital Khadki & 41 Arty Div Under Ge (Mh & Rh) Khadki.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Aug-2026 | AMENDMENT | BOQ | 02-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Disconnecting incoming and outgoing cable/busbar connections, taking out from the cradle and overhauling of manually/electrically operated, draw out type air circuit breaker of any make, 03 or 04 pole, 415 volts, AC, current rating 800 A, Make C &S complete all as specified and directed. (a) Cleaning of dust, spider web, foreign particles etc. (b) Removal of old grease from various parts. (c) Cleaning of various parts with CRC-2-26. (d) Check the tightness of all hardware. (e) Replacement of damaged parts. (f) Re-greasing and lubricating of all rotating, moving parts. (g) Checking, setting and fault attending of spring charging mechanism operation. (h) Checking, setting and fault attending of closing and tripping mechanism operation. (j) Checking, setting and fault attending of breaker auxiliary switch contact healthiness. (k) Checking of breaker operation in isolating / test and service position. (l) Confirming of Insulation resistance value of each live part w.r.t earth. Make:- C & S ACB Spares will be measured in relevant following items:- |
| 2 | Supply in repair / replacement of Motor Auxiliary isolating contact assembly CS-AIH-2-116(4P), complete all as specified and directed. |
| 3 | Supply in repair / replacement of Motor Compact UVT Coil6D- 16D/06N-2OS, CS-AUH-V-A-NA, complete all as specified and directed. |
| 4 | Supply in repair / replacement of Motor Shunt Trip 6D-16D/06N-2OS,CS-AVH-S-116-MA, complete all as specified and directed. |
| 5 | Supply in repair / replacement of Motor Closing Coil 6D-16D/06N-2OS,CS-AVH-S-116-MA, complete all as specified and directed. |
| 6 | Supply in repair / replacement of Motor Arcing Contact, CS-ARCCONT-O8D, complete all as specified and directed. |
| 7 | Supply in repair / replacement of Motor Main isolating Contact(Jaw Contacts) CS-MIC-O8D(50k), complete all as specified and directed. |
| 8 | Supply in repair / replacement of Motor Cradle terminal for drawout AH ACB, complete all as specified and directed. |
| 9 | Supply in repair / replacement of Motor Arc Chutes, complete all as specified and directed. |
| 10 | Supply in repair / replacement of Spring Charging Motors (220 Volts AC / DC), complete all as specified and directed. |
| 11 | Supply in repair / replacement of Motor Control relay for charging Motor (220 V AC), complete all as specified and directed. |
| 12 | Supply in repair / replacement of Motor Micro switch for motor cut off 6 D, complete all as specified and directed. |
| 13 | Supply in repair / replacement of Motor Drawout Handle, complete all as specified and directed. |
| 14 | Supply in repair / replacement of Motor Complete lower mechanism assly of 800 A, complete all as specified and directed. |
| 15 | Supply in repair /replacement of U V coil 440 Volts AC, complete all as specified and directed. |
| 16 | Supply in repair / replacement of Contractor coil 240 Volts AC Make- TC (630/800 Amps Contractor), complete all as specified and directed. |
| 17 | Disconnecting incoming and outgoing cable/busbar connections, taking out from the cradle and overhauling of manually/electrically operated, draw out type air circuit breaker of any make, 03 or 04 pole, 415 volts, AC, current rating 630-2500 A, complete all as specified and directed. Make : L & T all as specified under - (a) Cleaning of dust, spider web, foreign particles etc. (b) Removal of old grease from various parts. (c) Cleaning of various parts with CRC-2-26. (d) Check the tightness of all hardware. (e) Replacement of damaged parts. (f) Re-greasing and lubricating of all rotating, moving parts. (g) Checking, setting and fault attending of spring charging mechanism operation. (h) Checking, setting and fault attending of closing and tripping mechanism operation. (j) Checking, setting and fault attending of breaker auxiliary switch contact healthiness. (k) Checking of breaker operation in isolating / test and service position. (l) Confirming of Insulation resistance value of each live part w.r.t earth. |
| 18 | 800A S1 EDO 3P SR18G |
| 19 | CN-CS 1000C EDO 3P |
| 20 | 1600A S1 MDO 3P SR18 |
| 21 | 1600A S1 EDO 3P SR18G |
| 22 | 1600A S1 EDO 4P SR18G |
| 23 | 2000A S1 EDO 4P SR18G |
| 24 | 2500A S1 EDO 3P SR18G |
| 25 | NOTE FOR ITEM NO 1.00 and 2.00:- 1. The contractor has to submit detail service report for each breaker over-hauled. 2. All the necessary tools and tackles shall be arranged by contractor for the subject work. 3. The contractor has to replace minor spares like spring washers, washers locking pin, circlip, spring, small nut-bolts etc. free of cost. 4. Contractor has to arrange for necessary cleaning agent (petrol, diesel, CRC 2-26 etc.) and lubricating material like grease, oil and lubricating sprays if any, as required for subject work. 5. The servicing / overhauling of breaker is to be carried out at site. However, if any breaker requires to be taken to contractor’s work-shop, then contractor has to arrange transportation of such breakers from site to Work-shop and back to site without extra cost. 6. Major spares required to be replace during servicing will be measured and paid under relevant item as specified in the schedule hereforth.7. Load break test should done in front of Engineer-in-Charge.8. All required load bank should be carried by Contactor without extra cost.9. Servicing work done with prior permission of Engineer-in-Charge as breaker installed inside the hospital.10. All working executive must performed technical qualification and necessary exprience of work. |
| 26 | L&T ACB Spares |
| 27 | Supply in repair / replacement of Pole Assy. 400 -2500 S1 D/O, complete all as specified and directed. |
| 28 | Supply in repair / replacement of CTs for SR18 800S1-SR18 2500S1, complete all as specified and directed. |
| 29 | Supply in repair / replacement of Jaw contact Assy 400-2500A S1, complete all as specified and directed. |
| 30 | Supply in repair / replacement of Vertical Terminal Adapter 400-2500 S1, complete all as specified and directed. |
| 31 | Supply in repair / replacement of Arc Chute 630-2500 C/H/S1, complete all as specified and directed. |
| 32 | Supply in repair / replacement of Fixed Arcing Contact 630-2500S1, complete all as specified and directed. |
| 33 | Supply in repair / replacement of Moving Arcing Contact 630-2500 Amps, complete all as specified and directed. |
| 34 | Supply in repair / replacement of Shutter Assy. Supply in repair / replacement of 400-3200 S1, complete all as specified and directed. |
| 35 | Supply in repair / replacement of Cradle Terminal support and Assy. 400-2500S1, complete all as specified and directed. |
| 36 | Supply in repair / replacement of Shunt Release EA 220V DC, complete all as specified and directed. |
| 37 | Supply in repair / replacement of Under-voltage Release 240V AC, complete all as specified and directed. |
| 38 | Supply in repair / replacement of Closing Coil 240V AC/ 220V DC, complete all as specified and directed. |
| 39 | Supply in repair / replacement of FRCD 400-3200S1 (3P & 4P), complete all as specified and directed. |
| 40 | Supply in repair / replacement of Left-plate Assy 400-3200 S1, complete all as specified and directed. |
| 41 | Supply in repair / replacement of Motor 240V AC, complete all as specified and directed. |
| 42 | Supply in repair / replacement of Spring charge motor gear assembly, complete all as specified and directed. |
| 43 | Supply in repair / replacement of Spring charge limit switch, complete all as specified and directed. |
| 44 | Supply in repair / replacement of Spring charge motor assembly plunger, complete all as specified and directed. |
| 45 | Supply in repair / replacement of Power Contact 800 amps, complete all as specified and directed. |
| 46 | Supply and fix in repair of Bezal of L&T Braker Sr.No SL916020000, complete all as specified and directed. |
| 47 | Supply and fix in repair following type MCCBs in various panels, complete all as specified and directed. |
| 48 | MCCB 400 Amp four pole, Fixed thermal magnetic type 415 volts, 50 kA, suitable for existing of panel complete all as specified and directed. |
| 49 | MCCB 300-350 Amp four pole, 415 volts, 36 kA suitable for existing of panel , complete all as specified and directed. |
| 50 | MCCB 250 Amp four pole,Fixed thermal magnetic type 415 volts, 36 kA suitable for existing of panel , complete all as specified and directed. |
| 51 | MCCB 200 Amp four pole,Fixed thermal magnetic type 415 volts, 36 kA suitable for existing of panel , complete all as specified and directed. |
| 52 | MCCB 160 Amp four pole,Fixed thermal magnetic type 415 volts, 25 kA suitable for existing of panel , complete all as specified and directed. |
| 53 | MCCB 125 Amp four pole,Fixed thermal magnetic type 415 volts, 25 kA suitable for existing of panel , complete all as specified and directed. |
| 54 | MCCB 100 Amp four pole,Fixed thermal magnetic type 415 volts, 25 kA suitable for existing of panel , complete all as specified and directed. |
| 55 | MCCB 63 Amp four pole,Fixed thermal magnetic type 415 volts, 25 kA suitable for existing of panel, complete all as specified and directed. |
| 56 | Supply and fix in repair 3 Pole 630/800 Amps contractor with 2 NO + 2 NC operation coil voltage 230 Volt AC and having interlocking arrangement as per existing contractor installed at change over panel at MRS MH Kirkee, complete all as specified and directed. |
| 57 | Supply and fix in repair 3 Pole 315/400 Amps contractor with 2 NO + 2 NC operation coil voltage 230 Volt AC and having interlocking arrangement as per existing contractor installed at change over panel at MRS MH Kirkee, complete all as specified and directed. |
| 58 | Material & Labour in repair Control wiring of ACB Panel with using suitable size PVC tray of required size including all necessary material/hardware as per existing parameter and manufacturers specification complete all as specified and directed |
| 59 | Supply and Fix in repair Rectifier Unit as per exsting panel complete all as specified and directed |
| 60 | Supply and Fix in repair SMPS Units with incoiming 240 V AC and outgoing 24 V AC as per exsting panel complete all as specified and directed |
| 61 | Supply and Fix in repair PLA relay with 5/8/11 pin and base as per exsting panel complete all as specified and directed |
| 62 | Supply & Fix in repair on delay timer for ACB in distribution panel along with necessary timer setting as per site requirement complete all as specified and directed |
| 63 | Supply & Fix in repair control break switch as per site requirement complete all as specified and directed. |
| 64 | Material & Labour in Repair to APFC panel by replacing old U/S damaged electrical components parts and providing new parts as under, complete all as specified and directed. |
| 65 | 50 KVAR APP type capacitor Heavy Duty, complete all as specified and directed. |
| 66 | 25 KVAR APP type capacitor Heavy Duty, complete all as specified and directed. |
| 67 | 20 KVAR APP type capacitor Heavy Duty, complete all as specified and directed. |
| 68 | 12.5 KVAR APP type capacitor Heavy Duty, complete all as specified and directed. |
| 69 | 10 KVAR APP type capacitor Heavy Duty, complete all as specified and directed. |
| 70 | Supply & Fix in repair heavy duty power contactor for capacitor of 10KVAr to 50 KVAr, complete all as specified and directed. |
| 71 | Supply & Fix in repair 400A FN Type switch with bollet HTC Fuse, complete all as specified and directed. Make:- L & T |
| 72 | Supply & Fix in repair APFC Relay meter for 08 stage suitable for existing panel of 144 x 144 mm size, complete all as specified and directed. |
| 73 | Supply & Fix in repair APFC Relay meter for 12 stage suitable for existing panel of 144 x 144 mm size, complete all as specified and directed. |
| 74 | Supply and fix in repair 32A to 80 A control fuse links top and base, complete all as specified and directed. |
| 75 | Supply and fix in repair Illuminated push buttons red/green, complete all as specified and directed. |
| 76 | Supply and fix in repair LED type RYB indicating lamps(set of three), complete all as specified and directed. |
| 77 | Supply and fix in repair Voltage meter as per site requirement sutable incoming braker, complete all as specified and directed. |
| 78 | Supply and fix in repair Amps meter as per site requirement sutable incoming braker, complete all as specified and directed. |
| 79 | Supply & Fix in repair selector switch of 3 stage on - off - on suitable for existing panel complete all as specified and directed. |
| 80 | Supply & Fix in repair selector switch of 3 stage on - on - on suitable for existing panel for volt / amps meter complete all as specified and directed |
| 81 | Supply and fix in repair any size/shape of CT for Ammeter of ratio upto 800/5, complete all as specified and directed. |
| 82 | Supply and fix including taking down of burnt aluminum bus bar of any size and capacity and fix with all necessary provision cutting, bending, drilling, fixing with nut bolt washers complete all as specified and directed Please Enable Macros to View BoQ information |
| 83 | Supply and fix including taking down of burnt aluminum bus bar of any size and capacity and fix with all necessary provision cutting, bending, drilling, fixing with nut bolt washers complete all as specified and directed Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 9 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysTender Documents