Tender For Supply, INSTALLATION And Electrification Of Air Conditioners In The Dj And Adj Court Rooms, Chambers And Office In District Court Pilibhit.
Tender Overview
Project Description
Tender for Supply, INSTALLATION And Electrification Of Air Conditioners In The Dj And Adj Court Rooms, Chambers And Office In District Court Pilibhit.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 22-Aug-2026 | Date corrigendum | Date | 01-Sep-2026 |
| 2 | 01-Sep-2026 | Date Extent | Date | 11-Sep-2026 |
| 3 | 11-Sep-2026 | Date corrigendum 2 | Date | 21-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | HI-WALL SPLIT SYSTEMSSITC of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 °C. Min 5 year OriginalEquipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730. hermetic compressor IS 10617. heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS: 1391 Part II 2023. The system shall be able to operate up to 52°C (out door ambient temperature).Inverter Type Cooling only2.0 TR with 5 Star BEE RatingMake : Carrier/Panasonic/Blue Star/LG |
| 2 | HI-WALL SPLIT SYSTEMSSITC of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 °C. Min 5 year OriginalEquipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730. hermetic compressor IS 10617. heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS: 1391 Part II 2023. The system shall be able to operate up to 52°C (out door ambient temperature).Inverter Type Cooling only1.5 TR with 5 Star BEE RatingMake : Carrier/Panasonic/Blue Star/LG |
| 3 | SITC of 4 KVA Automatic Voltage Stablizer (130- 280V) Copper Winding. |
| 4 | SITC of 5 KVA Automatic Voltage Stablizer (130- 280V) Copper Winding. |
| 5 | Supply and laying of 2.5sqmm 4 Core round copper cable for indoor unit to outdoor unit |
| 6 | Supply and laying of 2.5sqmm 3 Core round copper cable for Stabilizer to indoor unit |
| 7 | SITC of Suction/Discharge both copper pipe line in split A.C. Unit 1.5 ton capacity including brazing, nitrile, rubber insulation 6mm thick class 'O' etc complete 1/4\\" (6.40 mm) and 1/2\\" (12.70mm) |
| 8 | SITC of Suction/Discharge both copper pipe line in split A.C. Unit 1.8/2.0 ton capacity including brazing, nitrile, rubber insulation 9mm thick class 'O' etc complete 3/8\\" (9.50 mm) and 5/8\\" (15.90mm) |
| 9 | Supply and laying of Heavy Duty PVC Plastic braided 20mm OD flexible pipe for condensed water drain with clipping accessories complete |
| 10 | Supply and Fixing of Outdoor Unit stand for split type A.C. |
| 11 | Supply , Fabrication and Installation of M.S. cage for protection of Outdoor unit from animal/theft L X W X H 1300 mm X 600 mm X 1200 mmcomplete in all respect |
| 12 | Supplying & fixing suitable size Gl box with modular plate and cover in fronton surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 13 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 14 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. 6 sq. mm 4 core |
| 15 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. 16 sq. mm 4 core |
| 16 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. 50 sq. mm 3 1/2 core |
| 17 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top as directed by enginer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor with clamps etc. 120 sq. mm 3 1/2 core |
| 18 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 4 X 16 sq. mm (35mm) |
| 19 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as requiredv 4 X 50 sq. mm (38mm) |
| 20 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 3 1/2 X 120 sq. mm (45mm) |
| 21 | Providing, laying and fixing following dia G.l. pipe (medium class) in ground complete with G.l. fittings including trenching (75 cm deep)and re-filling etc as required. 100 mm dia |
| 22 | Providing, laying and fixing following dia G.l. pipe (medium class) in ground complete with G.l. fittings including trenching (75 cm deep)and re-filling etc as required. 150 mm dia |
| 23 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) 4 way (4 + 12), Double door |
| 24 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door |
| 25 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 26 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 100 A.30KA.FPMCCB |
| 27 | Supplying and fixing 63 A 4 pole rating, 415 V, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A four pole |
| 28 | Supplying and fixing 32 A 4 pole rating, 415 V, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 32A four pole |
| 29 | Supply, Installation, Testing amd Commissioning of LT Panel vermin proof floor mounting , M.S. channel base with bottom and Fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating.The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit of 50kA for panels having ACB as Incomer & 36kA for panels having MCCB Incomers. Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be completed in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering.All Incomer Feeders shall be provided with Multifunction Metering along with Phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. and all Outgoing Feeders 100A & above shall be provided with 3 phase Ammeter along with phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. The Feeders above shall be provided ac accommodated all Measuring Instruments shall be Digital type & all Indicating Lights shall be LED type.Wiring shall be done from 1100V Grade PVC Insulated copper flexible wire. All ACB shall be Electrically operated Draw-out type with Microprocessor Based O/L, S/C & E/F Release of Breaking/ Withstand Capacity (ICU/ICs/Icw) 50kA or more All MCCB shall be Thermal Magneetic/Microprocessor with O/L & S/C Protection along with Required Spreaders & Extended Rotary Handle with pad Locking facility of Breaking capacity (ICU/ICS) 36kA or more All MCB shall be Thermal 10kA 'C' Curve. Cubicle type switch board shall be Cat-A and B only.Incoming 200 Amp. MCCB-1 No & Outgoing 100 Amp. MCCB-2 Nos. |
| 30 | Supply, Installation, Testing amd Commissioning of LT Panel vermin proof floor mounting , M.S. channel base with bottom and Fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating.The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit of 50kA for panels having ACB as Incomer & 36kA for panels having MCCB Incomers. Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be completed in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering.All Incomer Feeders shall be provided with Multifunction Metering along with Phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. and all Outgoing Feeders 100A & above shall be provided with 3 phase Ammeter along with phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. The Feeders above shall be provided ac accommodated all Measuring Instruments shall be Digital type & all Indicating Lights shall be LED type.Wiring shall be done from 1100V Grade PVC Insulated copper flexible wire. All ACB shall be Electrically operated Draw-out type with Microprocessor Based O/L, S/C & E/F Release of Breaking/ Withstand Capacity (ICU/ICs/Icw) 50kA or more All MCCB shall be Thermal Magneetic/Microprocessor with O/L & S/C Protection along with Required Spreaders & Extended Rotary Handle with pad Locking facility of Breaking capacity (ICU/ICS) 36kA or more All MCB shall be Thermal 10kA 'C' Curve. Cubicle type switch board shall be Cat-A and B only.Incoming 100 Amp. MCCB-1 No & Outgoing 63 Amp. MCCB-1 Nos. and 32 Amp. MCCB-2 Nos |
| 31 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 32 | Supplying and laying 25 mm X 5 mm G.l. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm) |
| 33 | S/F of shock Treatmemt Chart (prescribed under IE rules) |
| 34 | S/f of Danger Board fabricated from 10 Gauge M.S. Sheet as per IE Ruls. |
| 35 | S/F of Rubber matting1800x900x12 mm tested and chequred Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender