Tender For Urgent Electrical Installation Work Including Repairing And Replacement Of Defective Switchgears, Busbars, Interconnection Of Panel At Dc Office Kanjhawala
Tender Value
7.52 Lakhs
Estimated cost
Bid Submission
18 Aug 2026
4 days left
EMD
15043
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Urgent Electrical Installation Work Including Repairing And Replacement Of Defective Switchgears, Busbars, Interconnection Of Panel At Dc Office Kanjhawala
BOQ
| Sl. No. | Item Description |
| 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.a) Group C |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit/channel as required. a) 3 x 4 sq. mm |
| 3 | b) 6 x 4 sq. mm |
| 4 | Providing and fixing of PVC Trunking of following sizes complete with flexible cover, joint, endcap, cover , partition clip wherever reqd. on surface of wall/existing mounting etc. as required. a) 32 mm x 20 mm |
| 5 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.a) 15/16 A switch |
| 6 | b) 6 pin 15/16 A socket outlet |
| 7 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 8 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.a) 3 Module |
| 9 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.a) 150 A, 16 KA,TPMCCB |
| 10 | b) 250 A, 25 KA,TPMCCB |
| 11 | c) 400 A, 35 KA,TPMCCB |
| 12 | d) 400 A,50KA,FPMCCB |
| 13 | abrication, supplying, installation, testing & Commissioning of cubical type panel having IP 65 Rating, With following accessories MCCB, MCB, Digital Voltmeter, Ammeter with separate selector switch upto 300 mm depth made out of 2mm thick (14 SWG) CRCA MS Sheet having detachable gland Plates, floor mounted, compartmentalized , front operation, dust & vermin proof duly powder coated with proper locking arrangement complete with 400 Amp. TPN high conductivity aluminium alloy bus bar with DMC/SMC supports, continuous earth bar, interconnections, connections and providing & fixing of angle iron stand made out of 50mm X 50mm X 6mm thick M.S. Angle iron to suit the size of feeder pillar with 4 nos. 50 cms. legs grouted in cement concrete duly painted with one coat of red oxide & two coats of superior quality enamel paint etc. as reqd at site. (To be fabricated from CPRI approved fabricator.) a) 250 A,36KA,FPMCCB :- 1 No.b) 125 A, 16 KA,TPMCCB :- 2 Nos.c) 100 A, 16 KA,TPMCCB :- 2 Nos.d) 63 A, 10 KA. DP MCB :- 8 Nos. |
| 14 | Repairing of existing burnout Sub panel Dismantling / Disconnection of All Cable Connection from bus bar MCCB, removing all melted/ Damaged aluminium bus bar solid connection link with suitable capacity busbar cleaning of all terminals of MCCB/ MCB Bus bar with thinner CTC removing carbon dust dirt by sand paper with Fabrication, Drilling, Replacing defective nut, Bolt, washer i/c interconnection with 10 Sq.mm FRLS copper wire for MCB and reconnections all the cable to bus bar/ MCCB after repairing the Sub panel/ Main Panel, Providing missing front cover i/c making good the same for suitable for 415 Volt 50Hz AC supply complete with testing etc as reqd. |
| 15 | SITC of water gyser having capacity 25 Litres, 8 Bar Pressure, Suitable for High Rise Building, Thermostat Knob for Temperature Setting, Multiple safety system with BEE rating, Shock resistant & rust proof, Thermoplastic body Indicator for Power on, Heating function Child Safety Mode. |
| 16 | Supplying, Laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor armoured power cable of 1.1 kV grade of following size on wall surface as required. (a) 3.5 X 70 sq. mm Alu. Cable. |
| 17 | Supplying, Laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor armoured power cable of 1.1 kV grade of following size DWC/HDPE/ RCC/ HUME/METAL as required.(a) 3.5 X 70 sq. mm Alu. Cable. |
| 18 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.a) 3½ X 70 sq. mm (38mm) |
| 19 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 20 | Cutting of R.C.C. / Bitumen Road etc upto depth of 30 cm work, cutting by machine including making good as same as earlier and disposal of unserviceable material as per direction of Engineer - in- charge etc as required complete at site and no payment for other items by department. |
| 21 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 22 | Providing and fixing sheet steel enclosure suitable for 400/630 Amp FP/TPN MCCB, fabricated out of CRCA MS sheet, dust and vermin proof, wall mounted type, having hinged door with locking arrangement, powder coated finish after proper surface treatment, , earthing terminals and complete with all hardware, nuts, bolts, connections, testing and commissioning etc. as required and as directed by Engineer-in-Charge. |
| 23 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) (4 Nos 2*2 fitting of 3000 k CCT and rest 5700-6500 k CCT) a) 36 watt |
| 24 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) a) 18- 22 watt |
| 25 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥105 <120 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). a) 150 watt |
| 26 | Credit for following old/dismantle material removal from site. a) Alum. Cable of size 3.5 x 70 Sq. mm |
| 27 | b) Copper wire of size 1.5 Sq.mm, 4 sq.mm Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 11, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysAug 18, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender