Project Description

Tender for Ancillary Electrical Works For Setting Up Of 50 Bedded Critical Care Hospital Block At Malda Medical College & Hospital, Malda. (Electrical Work) - Supply Installation Testing and Commissioning of Ac Machine

BOQ

Name of Work:- Ancillary electrical works for Setting up of 50 Bedded Critical Care Hospital Block at Malda Medical College & Hospital, Malda. (Electrical Work) - SITC of AC Machine
Sl. No. Item Description
1SUB-HEAD 1--Water Cooled Screw Chiller
2Supplying, Installation, Testing and Commissioning of following capacity floor-mounted VFD (Variable FrequancyDrive) Operated water cooled screw-type chiller machine complete with single/multi semi-hermatic mono/multi screwtype compressor, with independent circuits, water-cooled Shell & Tube type condenser, Shell & Tube horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with 19 mm nitrile rubber insulation i/c suitable foundation/mounting structure made of RCC/MS Structure i/c anticorosive paint, anti vibration pad, power control cable and connection inter connection etc. as per design approved by engineer-in-charge, common base frame, interconnected copper refrigerant piping and wiring, vibration Isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser and ozone friendly Chlorofluorocarbons (CFC)-free refrigerant gas R- 134A. The refrigerant flow control shall use an electronic expansion valve. The chiller shall be designed for a Water Side working pressure of 150 psig and hydraulically tested at 1.5 times of design pressure . A number of properly spaced baffles shall be provided for maintaining optimum water velocity and heat transfer and the tubes shall be adequately supported. The chiller shall be Building Management System (BMS) compatible The system shall be in confirmation to IS : 16590 and CPWD Specification as amended upto date. BEE Star labeling and CPWD Specification as amended upto date and tested as per IS 16590.
3Chilled water Leaving Temp. (6.67°C)Chilled water Entering Temp. (12.2°C)Evaporator fouling factor = 0.018 m2. °C/kWCondenser water Entering Temp. (32.2°C) Condenser water Leaving Temp. (36.4°C)Suitable for Seismic Zone and Altitude as per location/site.Microprocessor based controller.
4100 TR BEE 4 Star Rated [Make: Blue Star/Carrier/Voltas/Hitachi/Mitsubishi/Trane/York/Dunham Bush] [2W + 1S]
5SUB-HEAD 2--FRP INDUCED DRAFT COOLING TOWER
6Supplying, Installation, testing and commissioning of Induced Draft counterflow cooling Towers(CTI approved). The Cooling Tower shall be of Fiber Reinforced Plastic (FRP) Construction. The casing, basin/sump, fan deck and fan cylinder shall be of FRP, with direct driven fans, Galvanised hardware complete with sump and drain connection with suitable valve, PVC Honey comb fill, louvers, drift eliminator complete with spray nozzle having self rotating sprinklers, steel ladder, Isolating switch and other accessories to make it fully operational and maintaince NationalAccreditation Board for Testing and Calibration Laboratories (NABL) & positioning of cooling tower at Terrace of Building. Propeller Type Fan, weather proof IP 55 and Direct driven.The fan motor shall be premium efficiency IE3 class , as per IS 12615 The Cooling tower shall be capable to communicate effectively with Building Management System (BMS). Range of CT: 6 0C. Designed Duty Conditions :- EWT,LWT , D/WBT Complete as per CPWD specification/drawings and as directed by Engineer-incharge. ( Note - Cooling tower size depends on the ambient temperature conditions , contractor must check the required design temperature)
7450 USGPM [Make: Advance/Paharpur/Bell or As per approved by EIC]
8SUB-HEAD 3--PRIMARY CHILLED WATER PUMP
9SITC of End Suction Back Pull out type primary chilled water pump with CI casing, CI/Bronze Impeller, Sleeve mechanical seal along with TEFC pump motor, Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class \\"B\\" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard(minimum) and Efficiency 75% minimum and as per ISI & NBCC guideline (overall pumping system) for minimum 270 USGPM flow rate under suitable head 15M (Min), mounted and aligned on a common MS base and, drain assy., vibration isolators complete in all respects duly insulated with 32mm thik Nitrite Rubber, mounted on common MS base plate, complete as per specifications etc. as required. The pump motor shall have IP55, all weather proof, isolator with lockable arrangement. [Head to be calculated as per site condition] (2 Nos. Working + 1 No. StandBy) [Make: Kirloskar/KSB/GRUNDFOSS/BEACON]
10SUB-HEAD 4--SECONDARY CHILLED WATER PUMP
11SITC of End Suction Back Pull out Type Secondary variable flow chilled water pump with CI casing, CI/Bronze Impeller, Sleeve mechanical seal along with TEFC pump motor, duly insulated with 32mm thik Nitrite Rubber , Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class \\"B\\" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 30-50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard (minimum) and 75% minimum Efficiency (Overall pumping system) for minimum 270 USGPM flow rate under suitable head 40M (Min) mounted and aligned on a common MS base and, drain assy., vibration isolators complete in all respects with insulation. [ Head to be calculated as per site condition] The pump motor shall have IP55, all weather proof, isolator with lockable arrangement. Each pump shall have Variable Frequency Drive, with IP_-54 panel enclosure and having a bypass mode. (All are working) [Make: Kirloskar/KSB/GRUNDFOSS/BEACON]
12SUB-HEAD 5-- SITC of VFD CONTROL PANEL FOR SECONDARY CHILLED WATER PUMP
13The VFD shall comply with IEEE-519 and having built-in input chokes, for harmonic supression on current (THID) less than 30 % to 35% only and voltage harmonic (THVD) less than 5%. This indicated harmonics shall be at drive input side. Standard logic applicable for the secified pump. The drive shall be having open protocole connectivity (Modbus/Bacnet/N2/FLN) and having a bypass mode with Star-Delta starter including S&F of VFD of suitable rating ( MAKE: ABB/DANFOSS/SIEMENS) , MCCB as incomer of suitable rating, C/O Switch overload protection, SPP, phase srequency protection and connection with suitable copper wire with ON,OFF & Trip indication, connectors etc. in SS enclosure with 2 nos ventilation fans (1W+1S) through 24x7 time switch to be fixed on wall as per direction of EIC. [Make: ABB/Blue Star/Danfoss or as per approved by EIC]
14Variable Frequency Drive (VFD) of suitable capacity as per the rating of secondary CW pump-motor with consideration of starting current (Input: 3-phase, 440 V, 50 Hz +/- 2.5% AC input & output: 3-phase, 0-415V, 0-50 Hz AC). The VFD shall comply with IEEE-519 and having built-in input chokes, for harmonic supression on current (THD) less than 30 % to 35% only and voltage harmonic (THVD) less than 5, i.e, harmonics shall be at drive input side. (All are working) (drawings & documents with data sheets to be approved by he EIC before delivery) [Make: ABB/Blue Star/Danfoss]
15Logic Controller for the pumps in a suitable sheet steel enclosure (IP-54) with lockable hinged door with both side dry powder coated painted. (drawings & documents with data sheets to be approved by he EIC before delivery) [Make- Kirloskar/KSB/M&P/Grundfos]
16SITC of DP sensor for Variable Pumping application & optimization with automation of the system. (drawings & documents with data sheets to be approved by he EIC before delivery) Make- [Make- Honeywell/Johnson/Siemens]
17Supplying and delivery of following size Un-Armoured cables XLPE insulated are designed for 1.1 kV Stranded copper conductor and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To DateAmendments.) [Make: Finilex/Havells/Polycab/ or as per approved by EIC]
184 core 1.5 sqmm
19SUB-HEAD 6--CONDENSER WATER PUMPS
20SITC of End Suction Back Pull out Type Condenser Water Pumps with CI casing, CI/Bronze Impeller, Sleeve mechanical seal along with TEFC pump motor, Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class \\"B\\" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 30-50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard (minimum) and 75% minimum Efficiency (Overall pumping system) for minimum 430 USGPM flow rate under suitable head 30M (Min) mounted and aligned on a common MS base and, drain assy., vibration isolators complete in all respects.[ Head to be calculated as per site condition] The pump motor shall have IP55, all weather proof, isolator with lockable arrangement. [Head to be calculated as per site condition & to be approved by EIC ] (All are working) [Make: Kirloskar/KSB/GRUNDFOSS/BEACON]
21S&F of Expansion tank, HDPE, 2000 Ltr, with 1 no float valves & 3 nos 50 mm dia butterfly valves with 50 mm thick thermocol insulation having 16 kg/cum density and sand cement plaster. [ For Makeup chilled water line] [Make: As per approved of EIC]
22S&F of Condensate chilled water storage tank, HDPE, 3000 Ltr, with 1 no float valves & 3 nos 50 mm dia butterfly valves with 50 mm thick thermocol insulation having 16 kg/cum density and sand cement plaster. [For Condensate chilled water storage ] [Make: As per approved of EIC]
23SUB-HEAD 7--FLOOR MOUNTED AIR HANDLING UNITS
24FLOOR MOUNTED TYPE AIR HANDLING UNITSSupplying, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units in confirmation to IS 18794 : 2024 made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine,complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filtersection with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (Total static pressure considered is max. 50 mm wg). [Make: Caryaire/Ethos/Edgetect/Zeco/Trane]
25Cooling capacity - 8500 CMH
26Cooling capacity - 11900 CMH
27SUB-HEAD 8-- CEILING SUSPENDED AIR HANDLING UNITS
28CEILING SUSPENDED AIR HANDLING UNITSSupplying, Installation, testing and commissioning of Factory built ceiling suspended chilled water double skin type horizontal/vertical air handling units offollowing capacity, made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with Polyurethane Foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 4 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with Totally Enclosed Fan Cooled (TEFC) drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for Variable Frequency Drive (VFD) applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.) and industrial type thermometres (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration Isolation arrangement, noise level shall not exceed 70 dB. AHU shall be AHRI/Eurovent certified, fan shall be AMCA certified etc. Complete as per CPWD specification/drawings and as directed byEngineer-in-Charge. (Total static pressure considered is 50 mm WG) [Make: Caryaire/Ethos/Edgetect/Zeco/Trane]
29Cooling capacity - 8000 CFM
30Cooling capacity - 6000 CFM
31SUB-HEAD 9-- FLOOR MOUNTED AIR HANDLING UNITS FOR OT
32FLOOR MOUNTED AIR HANDLING UNITS ( FOR OTs ):Supplying, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units in confirmation to IS 18794 : 2024 made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine,complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filtersection with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (Total static pressure considered is max. 50 mm wg). [Make: Kruger/Nicotra/Systenair/Caryaire]
33Cooling capacity - 5100 CMH
34SUB-HEAD 10-- Heater Bank, FCU, Ducting, Piping, Valves etc.
35SITC of duct mounted suitably selected Strip Heater bank made of SS Tubes with GI fins minimum 4.5 KW in 3 Banks (3x1.5KW) with Humidistat, Thermostat and other protection devices including control panel.[Make: As per approved by EIC]
36SITC of Aluminium laminar bench with perforated sheet cover to accommodate inside HEPA filter bank along with necessary support as per standard of minimum 6 ft X 8ft dimension for OT Area as per approved drawing necessary flange joints of air duct shall have to be fixed with sealant adhesive to prevent leakage. [Make: Sepctrum/AFI/Priyanka/Mechmaark]
37SITC of Cabinet inline Fan shall be of DIDW, forward/ backward curved centrifugal impeller fitted with maintenance free external rotor motor, belt / direct drive type. Impeller material shall be Galvanized Steel. Motor shall be suitable for external power supply 200~220V/50Hz/Single Phase. [Make: As per approved by EIC]
38500 CFM, 20MM Static for OT Exhaust
39CASSETTE FAN COIL UNIT Supplying, installation, testing and commissioning of Chilled Water Ceiling Suspended Hydronic Cassette type fan coil unit, four(4) way directional flow, lownoise, each complete with two(2) rows of deep chilled water cooling coil, multi-blade centrifugal fan, test reports from National Accreditation Board for Testing and Calibration Laboratories (NABL)/AHRI accerdited lab, electronic air cleaning system, required set of ball valves with & without strainers & 2 way Motorized valve, insulated condensate drain pans with drain pump assembly & drain pump failure alarm, pipe connections through copper pipes, Infra-red remote control, Liquid Crystal Display (LCD), four (4) speed motor , fan four(4) direction air flow, auto swing louver, decorative panel etc., condensation drain connections, All units shall be suitable for 220 +/- 10% Volts, 50 Hz, single phase power supply etc. complete as perspecification. The wireless Remote temperature control / thermostat shall have memory back up for set point re-store in case of power failure and re-start. Four(4) hanger rods with required anchoring fasteners, hooks, washers etc.complete as per CPWD specification and as directed by Engineer-in-charge. [Make: CARYAIRE/ETHOS/EDGETECH/Zeco]
403.5 TR nominal capacity with 1400 CFM air quantity
413.0 TR nominal capacity with 1200 CFM air quantity
422.0 TR nominal capacity with 800 CFMm air quantity
431.5 TR nominal capacity with 600 CFM air quantity
44INSULATED CHILLED WATER PIPING (resin bonded fiber glass INSULATION)
45Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with 80 kg/cum density resin bonded fiber glass or 144 Kg/ cum density mineral wool (non Combustible) pipe section insulation covered with a layer of 120 gm/sqm polythene sheet (vapour barrier) and finally applying 0.63mm aluminium sheet cladding complete with type3 , grade 1 roofing feltstrip(as per IS:1322 as amended up todate ) at joints and repairing of damage to building etc. as per specifications and as required. [Make: As per approved by EIC] Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
46150mm NB (Insulation 50 mm thick)
47125mm NB (Insulation 50 mm thick)
48100mm NB (Insulation 50 mm thick)
4980 mm NB (Insulation 50 mm thick)
5065 mm NB (Insulation 50 mm thick)
5150mm NB (Insulation 50 mm thick)
5240mm NB (Insulation 50 mm thick)
5332mm NB (Insulation 50 mm thick)
5425mm NB (Insulation 50 mm thick)
55Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted / buried in ground excavation and refilling etc. as per specification and as required complete in all respect.Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. [Make: As per approved by EIC]
56200mm NB
57150mm NB
5850mm NB
59INSULATED VALVESSupplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.
60BUTTERFLY VALVEBUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified [Make: As per approved by EIC]
6150 mm dia
6265 mm dia
63125 mm dia
64150 mm dia
65200 mm dia
66NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified. [Make: As per approved by EIC]
67125 mm dia
68150 mm dia
69Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. [Make: As per approved by EIC]
70125 mm dia
71150 mm dia
72POT STRAINER MS SITC of the following Water line POT-Strainer as per following categories, sizes and qunatities complete with providing flanges, nut-bolts, gasket and welding arrangements. Pot-strainer shall be fabricated out of Mild Steel, flanges as per BS 10 shall be provided at inlet and outlet of the connection. The body shall be pressure tested at 16 Kg/cm² and shall be hot dip galvanized. Permanent magnet shall be provided in the body of the strainer to arrest MS particles. Filter element shall be of non-magnetic 20 gauge SS sheet with 3 mm perforation. (All fixing bolts, double Nuts, different type washers must be of SS304 material to avoid frequent failurefor wear & tear due to rust & corrosion.) [Make: anergy/DS Engineering/Rapid Cool/Emerald/Sant]
73200 mm dia
74BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. [Make: Advance/Flowcon/Honeywell]
7550 mm dia
7665 mm dia
77125 mm dia
78150 mm dia
792 WAY MOTORISED MIXING VALVE FOR AHUsS & F of the following Water line 2-WAY MIXING VALVE WITH ACTUATOR, LINKAGE & THERMOSTAT as per following categories, sizes and qunatities complete with providing flanges, nut-bolts, gasket and welding arrangements: The two way modulating valves shall be provided in chilled water line to the cooling coil of Air- handlers which is actuated by a proportionate thermostat. The two-way valve shall be selected for valve authority value in the range of 30 % to 60 %. These valves shall consist of bronze metal valve body with stainless steel trim with linear flow characteristics. Modulating motor shall be suitable for operation with a signal of 0-10 volt DC.The pressure drop across valve for air-handler unit shall not exceed 5.0 PSI. The valve linkages shall be of the same make as of valves & modulating motor.(All fixing bolts, double Nuts, different type washers must be of SS304 material to avoid frequent failurefor wear & tear due to rust & corrosion.) [Make: As per approved by EIC]
8050 mm dia
8165 mm dia
82S&F of Rubber Bellow Expansion Joints for following dia pipe [Make: As per approved by EIC]
83125 mm dia pipe
84150 mm dia pipe
85S & F of Auto Air Vent with Ball Valve Make: Anergy/Sant [Make: As per approved by EIC]
86S & F of Water Flow Switch [Make: As per approved by EIC]
87INDUSTRIAL TYPE PRESSURE GAUGEProviding and fixing in position industrial type pressure gauges with gun metal / brass valves complete etc. as required. [Make: As per approved by EIC]
88INDUSTRIAL TYPE THERMOMETERProviding & fixing in position industrial type mercury thermometers complete etc. as required. [Make: As per approved by EIC]
89Supply and Laying of Rigid PVC Drain Pipe (Medium Class)with respective fittings , proper supports at 5 feet interval and duly insulated with 6 mm thick closed cell nitrile rubber insulation. [Make: As per approved by EIC]
9025 mm NB
9132 mm NB
9240 mm NB
93Supply and fixing of Flexible double Canvas connection in between each FCU & Duct [Custom Make or As per direction of EIC]
94Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications complete etc. as required. [Make: As per approved by EIC]
95Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required. [Make: As per approved by EIC]
96Supply & fixing of GI Collar Damper [Make: As per approved by EIC]
97Supplying, Fixing, installation, testing and commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required. [Make: As per approved by EIC]
98Supplying, Fixing, installation, testing and commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core in confirmation to SMACNA/IS and as per specifications complete etc. as required. [Make: As per approved by EIC]
99Supplying, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc in confirmation to SMACNA/IS and as per specifications complete etc. as required.[Make: As per approved by EIC]
100Supplying, Fixing, testing and commissioning of fire dampers of minimum 90 minutes fire rated in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal and, in confirmation to IS and as per specifications complete etc. as required. [Make: As per attached list]
101Fire Damper
102Actuator
103Supplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps,collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required. [Make: As per approved by EIC]
104Thickness 0.63 mm sheet
105Thickness 0.80 mm sheet
106Thickness 1.00 mm sheet
107SITC of AL Duct of for supply/ return air duct along with necessary supports, flanges etc. as required and as per IS standards of following gauges. For OT Only. [Make: As per approved by EIC]
10822 SWG thick
109DUCT ACCOUSTIC INSULATIONSupplying and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminium sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound in confirmation to SMACNA/IS and as per specifications complete etc as required. [Make: As per approved by EIC]
110DUCT THREMAL INSULATIONSupplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. [Make: As per approved by EIC]
111Supplying and fixing Installation, Testing and commissioning of 50mm thick aluminium foil faced resin bonded fibre glass insulation (on duct) of density 24 kg/cu.m or mineral wool insulation(non combustible) of density 44 kg/cu m after applying two coats of cold setting adhesive (CPRX compound) sealing all joints with self adhesive aluminium tape & covering with 0.63mmx19mm GI wire mesh netting & butting all joints and laced with GI wire complete and finally covered with one layer of tar felt stuck with hot bitumen as per specifications and as required. (for outdoor applications) [Make: Finolex/RR Kable/Polycab/Havells/ KEI/ Gloster]
112Supply & Fixing of underdeck insulation with 50mm thick, 16Kg/Cu Mtr. TF quality Extruded Polystyrene (XPS) or Closed-Cell XPS (CCXPS) slab. [Make: Finolex/RR Kable/Polycab/Havells/ KEI/ Gloster]
113SUB-HEAD 11--Starter Panel for AHU
114VFD Bypass AHU Starter Panel SITC of wall mounted cubical type LT distribution control panel & DOL type VFD Bypass Starter Electrical Panel Board fabricated from CRC Sheet with following accessories incl. internal wiring earthing & painting. The panel should be constructed as per rating of AHU Morots and provision for 01 nos Controle circuit (1W+1S) with Selector Switch. a) MCB suitable rating as Incomer & outgoing per the ratings of AHUmotor. b) DOL starter as per HP ratings. c) VFD and Bypass Starter as per HP ratings. d) Terminal block for power distribution. e) Power Contactor for Main I/P & O/P of VFD, contractor, over load relay, with inbuilt single phasing protection, control transformer . f) Phase indicating lights and indicating light for ON , OFF & TRIP status. g) Ammeter with selector switches , h) Wiring for microswitch for stopping the fan of AHU when fire damper closes. i) Panel mounted digital Ammeter with SS j) Auto Manual selector switch, K) VFD & Manual selector switch with suitable capacity. l) 24V, DC relay with 2NO & 2NC auxilary contractor --- 1 set (m) 230VAC/24V DC
115VFD Bypass AHU Starter Panel for OT Area SITC of wall mounted cubical type LT distribution control panel & DOL type VFD Bypass Starter Electrical Panel Board fabricated from CRC Sheet with following accessories incl. internal wiring earthing & painting. The panel should be constructed as per rating of AHU Morots and provision for 01 nos Controle circuit (1W+1S) with Selector Switch. a) MCB suitable rating as Incomer & outgoing per the ratings of AHUmotor. b) DOL starter as per HP ratings. c) VFD and Bypass Starter as per HP ratings. d) Terminal block for power distribution. e) Power Contactor for Main I/P & O/P of VFD, contractor, over load relay, with inbuilt single phasing protection, control transformer . f) Phase indicating lights and indicating light for ON , OFF & TRIP status. g) Ammeter with selector switches , h) Wiring for microswitch for stopping the fan of AHU when fire damper closes. i) Panel mounted digital Ammeter with SS j) Auto Manual selector switch, K) VFD & Manual selector switch with suitable capacity. l) 24V, DC relay with 2NO & 2NC auxilary contractor --- 1 set (m) 230VAC/24V DC m) Suitable rated MCB for OT Heater with interlocking safety sensors. n) TP-MCB provision for OT exhaust Fan.
116SUB-HEAD 12--Supplying & Laying of Cable
117Supplying and delivery of following size Armoured cables XLPE/PVC insulated are designed for 1.1 kV Stranded Aluminium conductor, high tensile galvanized steel wire/strip armour for mechanical protection, and PVC/FR PVC outer sheathing power cable of following size.(IS 7098 Part - 1/2011 with Up To Date Amendments.) [Make: Finolex/RR Kable/Polycab/Havells/ KEI/ Gloster]
1184 Core 150 Sqmm
1193 Core 16 Sqmm
1203 Core 10 Sqmm
121Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.
122100x50x1.25mm (18SWG) without angle iron support
123200x50x1.25mm (18SWG) with angle iron support
124600x50x1.25mm (18SWG) with angle iron support
125Supplying and delivery of following size Un-Armoured cables XLPE insulated are designed for 1.1 kV Stranded copper conductor and PVC/FR PVC outer sheathing power cable of following size. (IS 7098 Part - 1/2011 with Up To Date Amendments.) [Make: Finolex/RR Kable/Polycab/Havells/ KEI/ Gloster]
1267 Core 1.5 Sq. Sq.mm XLPE round copper Cable
1273 Core 1.5 Sq. Sq.mm XLPE copper Cable
128SUB-HEAD 13 -- EARTHING
129Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
130Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. Make: As per approved by EIC
131No. 8 SWG
132SUB-HEAD 14 -- WATER TREATMENT PLANT FOR AC SYSTEM
133Supply, installation, testing and commissioning of suitable capacity Water Treatment plant to operate in conjunction with 200 TR (100 TR, 2 Working + 1 Standby) running capacity AC plant constructed with welded Mild Steel of adequate thickness not less than 5 mm complete with Feed pump with suitable capacity along with motor, Iron eliminator, Water Softener, Brine Tank made out of FRP / HDPE 5 mm thick, Water Meter, Butterfly Valves, Pressure Gauges etc. electrical cabling work, chemicals and reagents for initial charge complete with all respect for satisfactory performance:Make Up water to deliver: 60 USGPMHardness of output water : Less than 25 PPM (CaCO3)PH Value of output water: Less than 7.5Iron content of Output water: Less than 0.3 PPM
134Cutting chase upto 125 x 150 mm. and subsequent mending of damages. [For entry of different sizes duct & pipe lines]
135(a) in brick wall [Cement-3.6 Kg/Mtr]
136(b) in concrete wall [Cement-3.6 Kg/Mtr]
137Cutting holes and subsequent mending good damages. [For entry of different sizes duct & pipe lines]
138Diameter upto 150 mm (In brick work [Cement-4.0 Kg/Mtr])
139Diameter upto 150 mm (In concrete work (plain or R.C.) [Cement- 3.0 Kg/Mtr])
140Diameter exceeding 150 mm. but not exceeding 300 mm (In brick work [Cement-6.0 Kg/Mtr])
141Diameter exceeding 150 mm. but not exceeding 300 mm In concrete work (plain or R.C.) [Cement-4.6 Kg/Mtr]
142Diameter exceeding 300 mm. but not exceeding 450 mm. (In brick work [Cement-10.0 Kg/Mtr])
143Diameter exceeding 300 mm. but not exceeding 450 mm. (In concrete work (plain or R.C.) [Cement-7.5 Kg/Mtr])
144Removal of rubbish,earth etc. from the working site and disposal of the same beyond the compound, in conformity with the Municipal / Corporation Rules for such disposal, loading into truck and cleaning the site in all respect as per direction of Engineer in charge
145Labour for breaking 1/2 Bricks or Full Bricks (Old / New) into metal / Khoa / chips as per specific size and stacking the same at site or stackyard with due allowance of sinkage / shrinkage as per direction of the Engineer in charge.
146Metal Size 50 mm to 65 mm
147Khoa Size 32 mm to 25 mm
148Chips Size 20 mm to 10 mm
149Supplying, fabrication & fixing of M.S. Angle/M.S 'C' channel of necessary size for placing the indoor AHU units & necessary support structure of Duct arrangement with mending goods damaged to the original finish as per direction of the EIC. Make: As per approved by EIC
150Add 18% GST (on Item No. 01.00 to 59).
151Add 1% CESS (on Item No. 01.00 to 60).
152N.B.: 1) Sl. No. 60.00 is variable depending on the total cost of the actual work on which 18% GST to be calculated during measurment of the work (Item No. 01.00 to 59.00).2) Sl. No. 61.00 is variable depending on the total cost of the actual work on which 1% CESS to be calculated during measurment of the work (Item No. 01.00 to 60).
153N.B.: i) The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.ii) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. iii) If any refurbished material is supplied and installed, penal action will be taken as per existing rules.iv) Defect Liability period 1 (One) Year. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56963131
AUTHORITY Government Departments
TENDER VALUE 2.84 Crore
LAST DATE 08-09-2026
Authority
Authority Name Public Works Department
Work Description Tender for Ancillary Electrical Works For Setting Up Of 50 Bedded Critical Care Hospital Block At Malda Medical College & Hospital, Malda. (Electrical Work) - Supply Installation Testing and Commissioning of Ac Machine
Basic Detail
Tender No WBPWD/SE/NEC/NIT-07/2026-27
Bidding Type Tender
Location
City Maldah
State West Bengal
Key Dates
Publish Date 11 Aug 2026
Submission Date 08 Sep 2026
Open Date 10 Sep 2026
Finance
Tender Value 2.84 Crore
Tender Fee Ref. Documents
EMD 5.69 Lakhs
Exemption Not Available
Document List
b772087e-4f61-4138-9448-617757833769.html
BOQ_5089356.xls
Tendernotice_1 (18).pdf
Tendernotice_2 (3).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 11, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 08, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 24 days
Sep 10, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 26 days

Tender Documents

Download All (ZIP) ↓
html

b772087e-4f61-4138-9448-617757833769.html

xls

BOQ_5089356.xls

pdf

Tendernotice_1 (18).pdf

pdf

Tendernotice_2 (3).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders