Defence Statutory Bodies & Commissions/Committees Closing in 9 days TDR #56962251

Tender For Repair / Maintenance Of Internal Wiring Including Cooling/Heating Appliances And Other Connected Works At Necklace Area, Col Point, Ramnagar & Scientist Hostel Under Ge (I) R&D Pashan

Issued by Statutory Bodies & Commissions/Committees · Pune, Maharashtra
Tender Value
Ref. Documents
Estimated cost
Bid Submission
01 Sep 2026
9 days left
EMD
88000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Maintenance Of Internal Wiring Including Cooling/Heating Appliances And Other Connected Works At Necklace Area, Col Point, Ramnagar & Scientist Hostel Under Ge (I) R&D Pashan

BOQ

Name of Work:- REPAIR / MAINTENANCE OF INTERNAL WIRING INCLUDING COOLING/HEATING APPLIANCES AND OTHER CONNECTED WORKS AT NECKLACE AREA, COL POINT, RAMNAGAR & SCIENTIST HOSTEL UNDER GE (I) R&D PASHAN
Sl. No. Item Description
1Taking down carefully copper/Aluminium point wiring (Light,Fan/Point Socket or power) including (swtiches, sockets, regulators, bell, bell push any size) and keep the same for shcedule of credit & making good to disturbed surface of walls/floors etc complete all as specified and directed.
2Taking down carefully by unscrewing from boards/outlet boxes, fittings and fixtures such as ceiling fitting, bulk head fittings, tube light fitting,garden and gate light fittings etc and making good the distrubed surfaces complete all as directed by Engr-in-Charge.
3Taking down existing unserviceable MCCBs/ MCB DBs with MCCBs , MCBs complete including making surface good as per direction of Engr-in-Charge.
4Taking down Electric water Heater complete all as specified and directed.
5Taking down carefully 10 Sqmm to 35 Sqmm XLPE insulated, armoured cable complete all as specified and directed.
6Material and labour for point wiring using approved colour coding as per IS with stranded copper conductor single core 1.5Sqmm (Nominal area), PVC insulated FRLS cable in and including concealed PVC conduit ISI marked medium grade with all connecting accessories as required at site complete, incl PVC insulated copper conductor 1.5 Sqmm (Nominal area) single core PVC FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified. Note :Modular face sheet,Modular piate/ Modular Switch/sockets and other related items to be measured and paid for separately. (a) All as per item No:6 above but One light point controlled by one ; one way switch complete all as specified and as directed.
7(b) All as per item No:6 above but One Fan/Exhaust point controlled by one ; one way switch complete all as specified and as directed.
8(c) All as per item No:6 above but One 3 pin 5 Amp socket out let controlled by one switch independent board complete all as specified and as directed.
9(d) All as per item No:6 above but on same board. complete all as specified and as directed.
10(e) All as per item No:6 above but One bell/buzzer point controlled by one push button. complete all as specified and as directed.
11All as per item 6 above but with 2.5 sq mm size pvc insulated and unsheathed 1100 volts grade FRLS single core stranded ( multistoried ) copper conductor cable for 3 pin socket outlet 15 amp on independent board including one continues run of PVC insulated green in colour 2.5 sq mm multistranded copper conductor earth wire connecting to earth dolly complete all as specified and as directed.
12Material and labour for point wiring complete with single core multi stranded Copper conductor cable of size 1.5 sqmm PVC insulated unsheathed 1100 volt grade in and including PVC casing capping Tee junction bends etc fixing to wall/roof and PVC switch board / hylam sheet of 3 mm thick in existing M.S. sunken boards of suitable size for housing switch sockets etc including 1.5 sqmm. green PVC insulated wire for earth continuity complete all as specified and as directed for the followings:- (a) One light point controlled by one ; one way switch complete all as specified and as directed.
13(b) All as per item No:12 above but One Fan/Exhaust point controlled by one ; one way switch complete all as specified and as directed.
14(c) All as per item No:12 above but One 3 pin 5 Amp socket out let controlled by one switch independent board complete all as specified and as directed.
15(d) All as per item No:12 above but 5 Amp on same board.complete all as specified and as directed.
16(e) All as per item No:12 above but One bell/buzzer point controlled by one push button.complete all as specified and as directed.
17(f) All as per item No:12 above but One light point controled by two way switch complete all as specified and as directed.
18All as per item 12 above but with 2.5 sq mm size pvc insulated and unsheathed 1100 volts grade FRLS single core stranded ( multistoried ) copper conductor cable for 3 pin socket outlet 15 amp on independent board including one continues run of PVC insulated green in colour 2.5 sq mm multistranded copper conductor earth wire connecting to earth dolly complete all as specified and as directed.
19Material and labour for point wiring complete with single core multi stranded Copper conductor cable of size 1.5 sqmm PVC insulated unsheathed 1100 volt grade FRLS in existing conduit pipe wall/roof and PVC switch board / hylam sheet of 3 mm thick in existing M.S. sunken boards of suitable size for housing switch sockets etc including 1.5 sqmm. green PVC insulated wire FRLS for earth continuity will be replaced complete all as specified and as directed. (Note : Switch/sockets to be measured and paid for separately) :-(a) one light point controlled by one; one way switch. complete all as specified and as directed.
20(b) All as per item No: 19 above but one fan/Exhaust point controlled by one; one way switch.complete all as specified and as directed.
21(c) All as per item No: 19 above but one 3 pin socket out let 5 amp independent point complete all as specified and as directed.
22(d) All as per item No: 19 above but one 3 pin socket out let 5 amp point on the same board with other switches. complete all as specified and as directed.
23(e) All as per item No: 19 above but One bell/buzzer point controlled by one,one way switch on independent board.complete all as specified and as directed.
24(f) All as per item No: 19 above but one light point controlled by two; two way switch for stair case. complete all as specified and as directed.
25All as per item 19 above but with 2.5 sq mm size pvc insulated and unsheathed 1100 volts grade FRLS single core stranded ( multistoried ) copper conductor cable for 3 pin socket outlet 15 amp on independent board including one continues run of PVC insulated green in colour 2.5 sq mm multistranded copper conductor earth wire connecting to earth dolly complete all as specified and as directed.
26Supply and Fix switch piano, flush type, 5 Amp, single pole, two way complete all as specified and as directed.
27Supply and Fix switch piano, flush type, 6 Amp, single pole, one way complete all as specified and as directed.
28Supply and Fix socket 6 Amp surface type complete all as specified and as directed.
29Supply and Fix Switch socket combination 6 Amp surface type complete all as specified and as directed.
30Supply and Fix switch piano flush type, single pole 1 way 16 Amp complete all as specified and as directed.
31Supply and Fix socket out let 2 in one 6 pin 6 & 16 Amp complete all as specified and as directed.
32Supply and Fix bell push, 6 Amps, SP, flush type. complete all as specified and as directed.
33Supply and Fix Lamp holder insulated body with back plate.complete all as specified and as directed.
34Supply and Fix Electric Bell , AC 230 volts, single pole complete all as specified and as directed.
35Supply and Fix stepped type electronic fan regulaor flush type on the existing/new phenolic sheet etc as required at site complete all as specified and directed
36Supply and Fix Ceiling rose surface Bakelite, 65x50mm three terminals 230 Volts, AC Single phase all as specified.
37Supply fixing & testing of sheet metal enclosure distribution board SPN 4 way double door type including making good to the disturbed surface all as specified and as directedNote : All incoming/out going MCBs shall be measured and paid under appropriate item here in after.
38Supply fixing & testing of sheet metal enclosure distribution board SPN 8 way double door type including making good to the disturbed surface all as specified and as directedNote : All incoming/out going MCBs shall be measured and paid under appropriate item here in after.
39Supply fixing & testing of sheet metal enclosure distribution board SPN 12 way double door type including making good to the disturbed surface all as specified and as directedNote : All incoming/out going MCBs shall be measured and paid under appropriate item here in after.
40Supply and fixing of Vertical TPN distribution board factory made double door flush type as per IS 8623 made from sheet metal duly powder coated for single phase outgoing and three phase incomer, with 200 Amps rated bus bar, 415 V, 4 way flush with wall complete with all accessories all as directed by Engineer-in-Charge. Note : All incoming/out going MCBs shall be measured and paid under appropriate item here in after.
41Material and labour in repair for MCCB 4 pole, 415 volts, 63 amps with breaking capacity 25KA including electrical connection as per site requirement complete all as specified and as directed.
42Supply and fixing in repair of MCB single pole 6-32 Amps capacity 10 KA, 240 Volts AC 50 Hz, B Curve.complete all as specified and as directed.
43Supply and Fix in repairs MCB single pole and neutral 20 to 40 Amps capacity 10 KA, 240 Volts AC 50 Hz, C Curve.complete all as specified and as directed.
44Supply and Fix in repairs MCB Triple pole and neutral 63 Amp Amps capacity 10 KA, 240 Volts AC 50 Hz, C Curve.complete all as specified and as directed.
45Taking down sub main wiring of any size carefully complete and making good disturb surface of walls / ceilings etc. and catered for schedule of credit.complete all as specified and as directed.
46Material and labour for sub main wiring using two single core 6 sqmm copper conductor,FRLS cable in including PVC casing caping of suitable size,including one run of PVC insulated copper earth continuity wire of 6.0 sqmm and connected to earth dolly including cutting chases for concealed conduit wiring complete all as specified and as directed. Note: 2 run of 6 sqmm ( 01 for phase and 01 for neutral) with 1 separate run of 6 earth wire and one run of PVC conduit will be measured as one unit.
47All as per item No 46 above but 2 run of 2.5 sqmm ( 01 for phase and 01 for neutral) with 1 separate run of 2.5 sqmm earth wire and one run of PVC conduit will be measured as one unit.complete all as specified and as directed.
48All as per item No 46 above but 2 run of 4 sqmm ( 01 for phase and 01 for neutral) with 1 separate run of 4 sqmm earth wire and one run of PVC conduit will be measured as one unit.complete all as specified and as directed.
49All as per item No 46 above but 4x10.0 sq. mm + 1x10.0 sq. mm earth wire complete all as specified and as directed.
50Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sq. mm 4 core complete all as specified and as directed.
51Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sq. mm 4 core complete all as specified and as directed.
52Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep for taking out/laying of HT/ LT under ground cable and getting out in the following type of earth stata complete all as specified and as directed:-(a) Soft soil
53(b) Hard soil
54(c) Disintegrated rock
55Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm in soils complete all as specified and directed.
56Removing surplus excavated soil to a distance not exceeding 50m depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
57Material and labour for riddled earth filling in trenches to required width at bottom and top of cable cusioning including spreading leveling and consolidation complete all as specified and as directed. Note : Punned thickness shall measured and paid.
58Supply and lay in trench reinforced precast concrete Class LV, Type I, flat, size 250mm x 150mm x 40mm LT cable protection complete all as specified and directed by the Engr-in-charge.
59Supply and Fix of surface and wall mounting General Purpose Aluminum Battens with best in class Luminaire Efficacy. These Extruded Aluminum housing battens are equipped with high specifications CISPR 15 compliant Electronics driver, 20 Watt 230V complete with all accessories internally prewired and provision of flexiable three core copper conductor 23/0.0076 upto 1.5mtr from celing rose to fitting all as directed by Engr-in-Charge.
60Supply and Fix Surface mounting General Purpose LED Battens in Extruded Aluminium housing with wide range of wattages to suite variety of application areas and integrated electronic driver, 10 Watt 230V complete with all accessories internally prewired and provision of flexiable three core copper conductor 23/0.0076 upto 1.5mtr from celing rose to fitting all as directed by Engr-in-Charge.
61Supply and Fix Decorative wall mounting with different finishes with borosil glass frosted & soda glass suitable for 7.5 W A60 LED Lamp with E27 base complete with pre-wired and including 9W LED lamp energy efficient ready to use pack,complete all as specified and as directed.
62Supply and Fix energy saving new generation 10W LED IP-65 bulkhead luminaire with opal diffuser, with lamp holder etc complete with all accessories and including connecting up with twin core twisted flexible copper conductor cable with suitable size of 230V, 50Hz, complete all as specified and as directed.
63Supply and Fix in repairs new LED building security luminaries 25 watts pressure die cast aluminum housing with IP 66 and replaceable integrated electronic driver LED as light sources housing including fixing on existing bracket complete with all accessories internally prewired all as specified and as directed
64Supply and fix in repairs of street light bracket made out of 25/32mm dia medium grade GI pipe of 1.5 mtr long bend to shape including MS flat iron clamp made out of 20x3mm 2 Nos and all fixing arrangement to fix with pole any type/height/wall complete all as directed by Engineer-in-Charge.
65Material and labour in repairs for earthing with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 M deep below ground level with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip 32 x 6 mm by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 03 of SSR Part I connected to earthing test point including excavation/ earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber including necessary formwork / mould for fair and even surfaces, precast RCC 1:2:4 type B0 chamber cover slab, GI funnel, with GI watering pipe 20 mm bore med gde, wire mesh, protection pipe 40 mm bore, charcoal and salt, GI pipe light gde for earth lead upto 7.50 m long including testing complete all as specified and directed by Engineer-in-Charge.Note : (i) GI strip beyond 7.5 mtr will be measured and paid sepeartely.(ii) Test report shall be prepared and submitted by the contractor in triplicate duly obtaining signatures of MES JE / AGE & PMG / user. Test results are to be written in letters of 20mm height in white colour on black paint back ground. (iii) The earth resistance should be less than 3 Ohm.(iv) if the test result of earth resistance not obtained below 2 ohms the contractor shall improve the earth resistance with own arrangement no extra payment will be paid by the department.
66Material and labour in repairs for Earthing complete with hot dip galvanized steel pipe in pipe electrode, outer pipe 76 mm dia medium grade and inner pipe 32 mm dia including testing 3 mtr long and having 50x6 mm terminal on inner pipe to connect earthing strip with 14 mm dia holes for nut bolts. buried directly and vertically in ground with top edge at 30 cm below ground level after making bore hole of 100 mm dia and 3.3 mtr deep using suitable mechanical drilling machine (for drilling near the specified bldg) connected with galvanized steel earthing lead of 32 x 6 mm strip with minimum two Nos of GI nut, bolts and connected to test point from earthing pit. The electrode pipes should be filled with 2x 25 Kg bags of carbon based earthing compound. The compound shall be highly conductive, hygroscopic, non magnetic, non corrosive in nature and have best moisture retaining qualities! with ph value between 7-9, connected to the earthing test point, fiber reinforced plastic pit not less than 300x300 mm with pit cover, including necessary returning, filling and removal of extra soil.complete all as specified and as directed.
67Taking down carefully electric water heathers (Gysers) 25/35/50 ltrs cap of any make and type including disconnecting electric and water connections and dismantiling re-assembling refixing and testing complete after doing the following as directed Engr-in-Charge:- (a) Descalling ther inner water tank complete and testing at a pressure of 43 PSI. (b) Descalling of heating element (c) Checking all electrical connections (d) Spares to be paid and measured saparately under supply only items:-complete all as specified and as directed.
68Supply only heating elements of capacity 1.5/ 2 KW for any type of Geysers ISI marked suitable for existing complete all as specified and directed.
69Supply only thermostate for geysers, ISI marked complete all as specified & directed
70Supply only indicator lamp 230 volt square or round shape for geysers complete all as specified and directed
71Supply only copper flexible cable PVC insulated 3 core 40/0.0076 and connecting complete all as specified and directed
72Supply only plate assembly with inlet and outlet and provn for thermostat housing rubber nuts, bolts and washers of required size complete for 25/35 ltrs capacity geysers complete all as specified and directed
73Supply only PVC connections 15mm size with SS Braided of length 450mm ISI marked fixed as in repairs complete all as specified
74Supply only stainless steel made hot water pipe 15mm size with SS Braided of length 450mm ISI marked fixed as in repairs complete all as specified.
75Supply and Fix in repair single pole enclosure with a two pin and earth plug and socket complete with one single pole MCB of 16/ 20 Amp metal enclosed industrial type complete all as directed.
76Supply and fixing of Bollard fitting 10 watt new generation energy saving environmental friendly, 4Feet long life aesthetically designed aluminium landscape IP 65 luminaire for diffused lighting with high power LED as light source complete all as specified and directed.
77Supply and Fix in repair LED 15Watt post top lantern (gate light) energy saving, environment friendly designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source complete all as specified and directed.
78Taking down the defective exhaust fan of any sweep 250mm sweep to 300mm sweep any type and make after disconnecting electrically & mechanically and transporting to the work shop dismantling, examine & carry out the repairs as required and brought back to site, re-fixing, testing in all respect for smooth running and comprising of the following:-(a) Servicing/overhauling the ceiling fan by thoroughly cleaning the bearing, shaft, stator, rotor & applying the lubricant / grease to the bearing including applying one coat of varnish over the winding to improve the insulation value complete. complete all as specified and as directed.
79Re-winding of Exhaust fan any sweep taking down vide item No 78 with same guage supper enameled copper wire to maintain speed at load.complete all as specified and as directed.
80Fixing only exhaust fan of any sweep and connecting up including provision of cable from ceiling rose/connector to fan complete all as specified and as directed.Note : Exhaust fan will be issued under Schedule 'B'.
81Taking down the existing un-serviceable exhaust fan of any sweep deposited to MES store and Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers including PCC work and hume pipe as required at site complete all as specified and as directed.
82Taking down the existing un-serviceable exhaust fan of any sweep deposited to MES store and Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250mm complete all as specified and as directed.
83Taking down carefully existing ceiling fan/ Exhaust fan any size from site and keeping in safe custody for reuse at site as per direction of Engr-in-Charge.complete all as specified and as directed
84Material and labour for Cleaning dust, removing of cavaties and painting of Ceiling fan any size taking down under item No with synthetic enamel paint by spraying as per direction of Engr-in-Charge.complete all as specified and as directed
85Hanging only ceiling fan and connecting up including provision of cable from ceiling rose or connector to fan complete all as specified and as directed.Note : Ceiling fan will be issued under Schedule 'B'.
86Suply and fix fan capacitor 2.5/4 mfd as specified and directed
87Taking down the existing un-serviceable ceiling fan of any sweep deposited to MES store and Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE complete all as specified and as directed
88Re-winding of ceiling fan any sweep taking down vide item No 85 with same guage supper enameled copper wire to maintain speed at load complete all as specified and as directed
89Supply and Fix recess mounting LED 2X2 luminaire of 35/36w ,230v , skylight type, white powder coated aluminium extruded housing with LED including drivers etc complete in all respect and accessories, internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable with 1.5 sqmm size complete all as directed .
90Supply and Fix in replacement of Modular switch piano 6A Amps flush type single pole one way as per exixtingcomplete all as specified and as directed
91Supply and Fix in replacement of modular socket 2in1,3 pin, 5/6 Amp, flush type as per exixting complete all as specified and directed
92Supply and Fix in replacement of Modular switch switch 1 way 16 Amps , 230 V as per exixting complete all as specified and as directed
93Supply and Fix in replacement of modular socket out let 2in1,3 pin, 6 and 16 Amp, flush type as per exixting complete all as specified and directed
94Supply and Fix in replacement of Modular bell push 6 amps, as per exixting complete all as specified and as directed
95Supply and Fix in replacement of Modular fan regulator Electronics step type 120 watts and connecting as per existing complete all as specified and directed by Engineer-in-Charge.
96Supply and fix electric water heater, vertical storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc complete all as specified and as directed
97Supply and Fix in replacement of Modular cover plateand frame as per following:-(a) White cover plate with frame, 1 module complete all as specified and as directed
98(b) -ditto- but 2 module complete all as specified and as directed
99(c) -ditto- but 3 module complete all as specified and as directed
100(d) -ditto- but 4 module complete all as specified and as directed
101(e) -ditto- but 6 module complete all as specified and as directed
102Supply and Fix in replacement of Modular GI metal flush box with suitable size as per following:-(a) Metal flush box 1/2 modul complete all as specified and as directed
103(b) -ditto- but 3 module complete all as specified and as directed
104(c) -ditto- but 4 module complete all as specified and as directed
105(d) -ditto- but 6 module complete all as specified and as directed Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56962251
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 01-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Maintenance Of Internal Wiring Including Cooling/Heating Appliances And Other Connected Works At Necklace Area, Col Point, Ramnagar & Scientist Hostel Under Ge (I) R&D Pashan
Basic Detail
Tender No GERD/PSN/TOKEN/50 OF 2026-27
Bidding Type Tender
Location
City Pune
State Maharashtra
Key Dates
Publish Date 11 Aug 2026
Submission Date 01 Sep 2026
Open Date 08 Sep 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 88000
Exemption Available
Document List
8749.pdf
ac58e00c-feea-43be-9545-59d04e4a26d4.html
BOQ_878390.xls
Tendernotice_1 (7).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 11, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 01, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 9 days
Sep 08, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 16 days

Tender Documents

Download All (ZIP) ↓
pdf

8749.pdf

html

ac58e00c-feea-43be-9545-59d04e4a26d4.html

xls

BOQ_878390.xls

pdf

Tendernotice_1 (7).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders