Housing Urban and Rular Development Government Departments Closing in 4 days TDR #56948725

Tender For repair maintenance Various E&M Services In Various Delhi Govt. Offices Under Ae (E) Emsd-Iii, South East, Sunlight Colony, New Delhi.(Sh:- Electrical Repair And Renovation Work, Installation Of Ups, Water Cooler, Ros At South East Circle O

Issued by Government Departments · Delhi, Delhi
Tender Value
19.67 Lakhs
Estimated cost
Bid Submission
18 Aug 2026
4 days left
EMD
39350
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for repair maintenance Various E&M Services In Various Delhi Govt. Offices Under Ae (E) Emsd-Iii, South East, Sunlight Colony, New Delhi.(Sh:- Electrical Repair And Renovation Work, Installation Of Ups, Water Cooler, Ros At South East Circle Office And Education Maintenance Division South And South East, Sukhdev Vihar And Replacement Of Submersible Pump At Sunlight Colony, New Delhi.)

BOQ

Name of Work:- RMO various E&M services in various Delhi Govt. Offices under AE (E) EMSD-III, South East, Sunlight Colony, New Delhi.(Sh:- Electrical repair and renovation work, installation of UPS, water cooler, ROs at South East Circle office and Education Maintenance Division South and South East, Sukhdev Vihar and replacement of submersible pump at Sunlight Colony, New Delhi.)
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mmFRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.
2a) Group C
3Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required.
4a) Group C
5Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
6a) 20 mm
7b) 25 mm
8Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface / recessed steel / PVC conduit as required.
9a) 3 x 1.5 sq.mm
10b) 6 x 1.5 sq.mm
11c) 3 x 4 sq.mm
12d) 6 x 4 sq.mm
13e) 3 x 6 sq.mm
14Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required.
153 Module (100mmX75mm)
166 Module (200mmX75mm)
178 Module (125mmX125mm)
1812 Module (200mmX150mm)
19Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
20a) 5/6 amp switch
21b) 3 pin 5/6 amp socket outlet
22c) 15/16 amp switch
23d) 6 pin 15/16 amp socket outlet
24e) Bell Push
25f) 25A modular SP MCB \\"C\\" curve
26Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
273 Module
286 Module
298 Module
3012 Module
31Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve includingconnections, painting etc. as required.
32Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
33Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
34Supplying and fixing of two module stepped type electronic fan regulator on the existing modular plate switch box i/c connections but excluding modular plate etc as reqd.
35Supplying and fixing following way, single pole and neutral, sheet, steel, MCB distributions board, 240 volts, on surface/recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
3616way Double door
37Supplying and fixing of following ways surface/recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting CBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
38a) 8 way (4 + 24), Double door
39Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc. as required.
40a) For 14 way, Double door SPN MCBDB
41Supplying and fixing Cable End Box (Loose Wire Box) suitable for triple pole and neutral, sheet steel, Vertical MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc. as required.
42Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
43a) Single pole
44Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
45a) 40 amp
46b) 63 amp
47Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release an terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
48a) 125 A, 16 KA,TPMCCB
49Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
50Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
51Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
52Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
5318- 22 watt
5436 watt
55Supplying, installation, Testing & Commissioning of LEDRecessed / surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Powder coated die cast /Extruded aluminium Body including trim
5618 watt
57Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.) Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm)
5836 watt
59Supplying. Installation, testing and commissioning of 300 mm sweep metallic heavy duty 900 rpm exhaust fan suitable for operation on 230V, 50 Hz single phase AC supply complete with louvers / shutters in the existing opening including making the hole to suit the size of the above fan making good the damage and connections etc. as reqd.
60Supplying & fixing 400mm sweep wall mounted cabin fan with speed regulator oscilatting type i/c testing & commsisioning suitable for 230volt 50Hz AC supply etc as reqd.
61Supplying & Intallation of fresh air fan 250 mm sweep with shutter and louver in the existing opeining , including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required.
62Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
63a) 1200mm, service value ≥ 6.0 CM/Min/Watt, airdelivery 210 CM/Min (Minimum)
64Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. a) Upto 35 sq. mm (clamped with 1mm thick saddle)
65Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. a) Upto 35 sq. mm
66Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. a) 63 mm dia (OD-63 mm & ID-51 mm nominal)
67Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year OriginalEquipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).
68a) 1.5 TR inverter AC with 5 Star BEE Rating
69Supplying , Installation, Testing and Commissioning of Window type Air conditioners complete with copper power cable upto 3 Mtr, wireless Remote, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing, cooling, dehumidification, air circulation, R-32/R-410A /R-407B Green Refrigerant with Scroll / rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), antifreeze thermostat on the coil as a safety feature, complete with fixing including T&P & labour etc as required complete in all respect as specified of following capacity. Sound level of up to 50dB inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-I 2023 and CPWD Specification. The system shall be able to deliver 100% of the rated capacity upto 42 0C. The system shall be able to operate up to 50 0C (out door ambient temperature).
70a) 1.5 TR with Inverter 5 Star BEE rating
71Supplying ,installation , testing and commissioning of 4 KVA voltage stablizer wall mounted type for domestic use copper wound complete upto 1.5TR Capacity Air Conditioners unit, , Operating Voltage range (Input): 150-280 volts,Output 230+ 10 Volts, 50Hz AC supply etc. as required.
72Supply and fixing of 15/16Amp 3pin top plug including connection complete as reqd.
73Supplying & Fixing 25 mm diameter PVC heavy duty pipe for drainage in the existing split type AC unit with supporting clamps etc . complete as reqd.
74Supplying and fixing of Extra copper refrigerant piping of 5/8”, 3/8”, 1/4” i/c nitrile rubber insulation wrapping etc. complete as reqd.
75Providing and fixing of 3 core 2.5 sqmm PVC insulated and PVC sheathed bright annealed copper conductor cable for communication between indoor unit/outdoor unit/controllers inside building in existing steel/PVC Conduit/ surface/ existing channel, i/c making connection etc as reqd.
76Supplying and fixing stand for the outdoor unit of the STAC made of MS duly powder coated complete etc as required.
77Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS) system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection againstneutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for the rectifier & inverter with PWM (Pulse Width Modulation) Technology. The quality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion(ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute.
78Operating temperature 0 to 40 0C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging, output over current, short circuit, battery deep discharge , 10 KV surge. Display for watt/VA,Amp and Voltage power parameters etc. UPS shall comply with low voltage electromagnetic compatibility (EMC) achieved as per EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and Frequency Independent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/ RS485/ SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accessories are inclusive in the cost. The UPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc.
796 KVA
80Supplying and fixing of 650 Line Interactive UPS 650VA/360W, Micro Processor Based UPS System, an Ideal Power Backup & Protection for Desktop PC, Input Voltage Range: 140 V ~ 300 VAC, Frequency: 50 Hz ± 10%, 12V/7AH x 1 Battery, Auto Switch Off in Battery Low is In-Built. Off mode Charging & Overload Protection are In-Built complete etc as reqd.
81Supplying Installation Testing and commissioning of water cooler with 150/150ltr storage capacity suitable for operation on 230Volts 10%, 50Hz, single phase AC supply with high efficiency compressor faster cooling, ergonomically desgined for greater safety and operational convenience low power consumption, superior quality grooved copper tubes in heat exchager, ISI marked blue fins on condensor coil, stainless steel body for longer product lift, stainless steel tank food grade water piping float valve and other components which come in contact with drinking water, water inlet, hosepipe, overflow pipe to be provided with water cooler packing adjustable pedestal made of high non corrosive strong material minimum two number faucets etc complete as reqd.
82Supplying Installation Testing and Commissioning of 50LPH RO System design to deliver upto 50ltrs of purified water per hour through a 6 stage purification process. its membrane should have a pore size of 0.0001 micron size which prevents the passage the micro organisms and total dissolved salts making the water lighter test natural and save to drink. the RO system should have 04nos of 75 GPD membrane, system operating voltage 48volt DC suitable for operating temperature 5 degree to 45 degree, suitable for 230volt 50Hz AC supply i/c making plubming connection and interconnection with pipe, pipe accessories complete etc as reqd.
83Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
84Lifting the defective submersible / mono block submersible pump set along with GI pipe upto 5 HP from existing bore well / sump well with the help of chain and pulley block etc as reqd.
85Supplying, lowering and fixing of 7.5 HP open well submersible pump set with totally enclosed water proof squirrel cage induction motor in the existing sumps having 80 x 65 mm suction & delivery, discharge range LPS 10-18 @ head of 18-28 mtrs. suitable for 3 phase, 50Hz, AC supply complete with connection, testing etc. as reqd.
86Supplying and fixing of 3 HP mono block centrifugal pump set with totally enclosed water proof squirrel cage induction motor in the existing sumps having 65 x 50 mm suction & delivery, discharge range LPS 4-9 @ head of 10-26 mtrs. suitable for single phase, 50Hz, AC supply complete with connection, testing etc. as reqd.
87Supplying and fixing of 3HP submersible pump motor starter panel suitable for three phase 415 volt 50Hz AC supply with enclosure relay range 4-6.5 amp having single phase preventer with complete testing and commissioning etc as reqd.
88Supplying and fixing of 5HP submersible pump motor starter panel suitable for three phase 415 volt 50Hz AC supply with enclosure relay range 6-10 amp having single phase preventer with complete testing and commissioning etc as reqd.
89Supplying and fixing of 7.5HP submersible pump motor starter panel suitable for three phase 415 volt 50Hz AC supply with enclosure relay range 23-32 amp having single phase preventer with complete testing and commissioning etc as reqd.
90Providing, laying, testing & commissioning of 'B' class medium duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
91a) 65 mm
92Supplying, Installation, Testing and Commissioning of fixing of following dia. Gun metal gate valve (Screwed type) on the existing pipeline, including testing & Commissioning etc. complete as required.
93a) 65mm dia
94Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
95a) 65mm dia
96Supplying & fixing PVC insulated PVC sheathed copper conductor submersible flat cable ISI Marked in existing metal/ HDPE / PVC/ pipe/ in bore well/ in sump including fixing the cable to GI/HDPE pipe with suitable cable tags of following sizes etc. as required.
97a) 3 Core 6 Sq mm Flat Cable
98Credit for dismantle materials
99Assorted : Ceiling fan
100Assorted : Ex fan
101Assorted : Fresh Air Fan/wall fan
102Assorted : Switch/socket/regulator (Piano/Modular)
103Assorted : SP /DP MCB upto 63 A
104Assorted : SP/TPDB MCB DB
105Assorted : copper Wire with insulation
106Assorted : GI Box with modular plate/phenolic sheet
107Assorted : LED batten/Downlighter/fl. Fitting
108Assorted : 2x2 fitting
109Assorted : cable
110Assorted : Pump
111Assorted : Motor starter
112Assorted : Gate valve/NRV
113Assorted : Submerible cable
114Assorted : Water cooler
115Assorted : RO Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56948725
AUTHORITY Government Departments
TENDER VALUE 19.67 Lakhs
LAST DATE 18-08-2026
Authority
Authority Name Public Works Department
Work Description Tender for repair maintenance Various E&M Services In Various Delhi Govt. Offices Under Ae (E) Emsd-Iii, South East, Sunlight Colony, New Delhi.(Sh:- Electrical Repair And Renovation Work, Installation Of Ups, Water Cooler, Ros At South East Circle Office And Education Maintenance Division South And South East, Sukhdev Vihar And Replacement Of Submersible Pump At Sunlight Colony, New Delhi.)
Basic Detail
Tender No 89/EE(E)/EMD South East/PWD/2026-27
Bidding Type Tender
Location
City Delhi
State Delhi
Key Dates
Publish Date 11 Aug 2026
Submission Date 18 Aug 2026
Open Date 18 Aug 2026
Finance
Tender Value 19.67 Lakhs
Tender Fee Ref. Documents
EMD 39350
Exemption Not Available
Document List
59114ddd-1261-459e-bdfd-0ba39b7e216c.html
BOQ_395251.xls
tender.pdf
Tendernotice_1 (11).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 11, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 18, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 4 days
Aug 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 4 days

Tender Documents

Download All (ZIP) ↓
html

59114ddd-1261-459e-bdfd-0ba39b7e216c.html

xls

BOQ_395251.xls

pdf

tender.pdf

pdf

Tendernotice_1 (11).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail