Defence Statutory Bodies & Commissions/Committees Closing in 8 days TDR #56946205

Tender For Repair/Maintenance And Replacement Of Lt Panel,Busbar And Other Connected Work At Sector ‘A & ‘B Under Ge (A) Baroda.

Issued by Statutory Bodies & Commissions/Committees · Vadodara, Gujarat
Tender Value
15 Lakhs
Estimated cost
Bid Submission
24 Aug 2026
8 days left
EMD
30000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Vadodara → Gujarat
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maintenance And Replacement Of Lt Panel,Busbar And Other Connected Work At Sector ‘A & ‘B Under Ge (A) Baroda.

BOQ

Name of Work:- REPAIR/MAINTENANCE AND REPLACEMENT OF LT PANEL,BUSBAR AND OTHER CONNECTED WORK AT SECTOR ‘A & ‘B UNDER GE (A) BARODA.
Sl. No. Item Description
1M&L for preparation of existing old painted surface of any description such as Panels any height and painted completed with one coats of primer (superior quality) and in smokey greay color all around the panels. (Make of Paint : Asian, Berger or equivalent.)
2M & L in repair for fabrication of bus bar chamber of size 80cmx60cmx40cm for 415 volts 3 phase 4 wire system with MCCB 250A ,25 KA ,4 pole, out going MCCB 100Amps ,16KA , 4 Pole - 01 Nos and 63 Amps16KA , 4 Pole -01 Nos ,outdoor type, with digital volt amp meter ,double door, withpedestal mounted, weather and vermin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 1.2 mtr above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge .
3Expertise and labour only for load balancing of feeder complete after removing all service cables connected to all the three phases, checking these for ohmic value, leakage if any and connecting to all the three phases in such a sequence so that load is nearly balanced in all the three phase complete all as specified and directed.
4Inspection/checking & testing after repair of APFC panel 3 Phase,440 voltage 50Hz AC supply system to improve power factor 0.80 to 0.99 automatic step wise switched capacitor panel to make it serviceable in auto and maunal mode, with the help of connecting relays, capacitors,contactors,MCB\\"s.,CTs, re-wiring burnt/worn out control wires etc and rectifying the defects, replacement of unserviceable parts as required at site and cleaning of AMFAPFC panel as detecting during inspection or pointed out by department and carry out maintenance complete all as specified as directed by Engineer-in-Chrage. (Notes :-This items includes the cost of cleaning & rewiringof panel. Spare parts required shall be measured and paid for separately under respective items as supply only)
5Supply only in replacement of APFC microprocessor based relay up 8 stage PFC controller ,230 volts complete all as specified and directed by Engineer-in-Charge. Make-L&T/EPCOS/Siemens
6Supply only in replacement of Heavy duty capacitor 3 Phase,415 Volt, AC, 50 Hz of capacity 10 KVAR complete all as specified and as directed by Engineer-in-Charge.
7Supply only in replacement of Heavy duty capacitor 3 Phase,415 Volt, AC, 50 Hz of capacity 15 KVAR complete all as specified and as directed by Engineer-in-Charge.
8Supply only in replacement of capacitor duty contactor 3 phase suitable upto 20 KVAR capacity 240 volts complete all as specified and as directed by Engineer-in-Charge. Make-EPCOS,L&T
9Supply only of capacitor duty contactor 3 phase suitable upto 5 KVAR capacity 240 volts complete all as specified and as directed by Engineer-in-Charge. Make-EPCOS,L&T
10Supply only in replacement of current transformer of ratio 200/5, 10 VA with accuracy of 1.0 including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
11Supply only in replacement of current transformer of ratio 100/5, 10 VA with accuracy of 1.0 including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
12Supply & fixing in repair of MCB SP 6 to 32 Amps, curve 'c' ,10 KA complete all as specified and directed by Enginner-in-Charge.
13Supply & fixing in repair of MCB SPN 32 Amps, ,curve 'c' 10 KA complete all as specified and directed by Enginner-in-Charge.
14Supply & fixing in repair of MCB SPN 40 to 63 Amps, ,curve 'c' 10 KA complete all as specified and directed by Enginner-in-Charge.
15Supply & fixing in repair of MCB 40 to 100 Amps, TPN curve 'c' 10 KA complete all as specified and directed by Enginner-in-Charge.
16Supply & fixing Start/stop push button complete including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
17Supply & fixing in replacement of selector switch rotary type, flush button, 3 way position in one for voltmeter or Ammeter of any range as per existing complete all as specified and as directed by Engineer-in-Charge.
18S&F following MCCBs thermal and magnetic adjustable of capacities , mentioned against each as suitable to be housed in existing space including link separator of existing including taking down old UNSV make:-Havells /Legrand/L&T/ Schneider /ABB
19(a) MCCB but 40 Amp,4 Pole 415 Volt ,16 KA, Thermally and Magnetic Adjustable
20(b) MCCB but 63 Amp, 4 Pole 415 Volt ,16 KA Thermally and Magnetic Adjustable
21(c) MCCB but 100 Amp,16 KA -Ditto-
22(d) MCCB but 125 Amp,6KA -Ditto-
23(e) MCCB but 160 Amp, 25 KA -Ditto-
24(f) MCCB but 200 Amp, 25 KA -Ditto-
25(g) MCCB but 250 Amp ,36 KA -Ditto-
26(h) MCCB but 400 Amp,36 KA -Ditto-
27Supply and fix new digital Basic Multifunction Meter showing V,A,F,PF,KW,KVA etc suitable for mounting on LT panel including taking down UNSV all as specified and as directed.
28S & F in repair of on load changer switch in sheet steel enclosure four pole, 415volt, front handle operated of capacity 250 Amp complete, change over switch fixed in panels or on walls as per site requirement all as specified and directed by EICMake: Legrand/ABB/Havells Please Enable Macros to View BoQ information
29S & F in repair of on load changer switch in sheet steel enclosure four pole, 415volt, front handle operated of capacity 250 Amp complete, change over switch fixed in panels or on walls as per site requirement all as specified and directed by EICMake: Legrand/ABB/Havells Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56946205
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 15 Lakhs
LAST DATE 24-08-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maintenance And Replacement Of Lt Panel,Busbar And Other Connected Work At Sector ‘A & ‘B Under Ge (A) Baroda.
Basic Detail
Tender No 8977
Bidding Type Tender
Location
City Vadodara
State Gujarat
Key Dates
Publish Date 11 Aug 2026
Submission Date 24 Aug 2026
Open Date 25 Aug 2026
Finance
Tender Value 15 Lakhs
Tender Fee 500
EMD 30000
Exemption Available
Document List
BOQ_878218.xls
fc0b6d19-7983-4746-8992-a04f24718588.html
Tendernotice_1 (7).pdf
Tenderpages8977.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 11, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Aug 25, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 9 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_878218.xls

html

fc0b6d19-7983-4746-8992-a04f24718588.html

pdf

Tendernotice_1 (7).pdf

pdf

Tenderpages8977.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders