| Sl. No. | Item Description |
| 1 | Supply, installation, testing, and commissioning of an Intelligent Microprocessor-based Addressable Fire Alarm Control Panel, LPCB approved and EN 54 certified. The panel shall be 1 built-in SLC loop expandable up to 32 loops, supporting up to 256 addressable devices per loop for Class A, and 512 addressable devices per loop for Class B networkable with up to peer-to peer 128 panels via RS485 or Fiber Optic cable. The panel shall have a minimum 36-zone LED display to indicate Fire, Fault, and Disable conditions. The panel shall have an inbuilt 24VDC, 3A auxiliary power supply for external device powering. It shall have minimum 7 inches touch-sensitive LCD screen with feather -touch buttons for fire/fault indication and multiple LED indicators for clear visual status of fire, fault, disable, and system operation. with address and analog values, support Class A and B wiring, and feature 2 programmable sounder outputs, 6 programmable equipment outputs, 24V DC/3A auxiliary output, and battery backup of 30 mins at fault consition and 24 hours for normal condition. The panel shall be modular and support optional features including FPE monitoring, alarm counter, output delays, and address disablement. Make: Glyptic/Siemens/Autronica |
| 2 | Supply, installation, testing and commissioning of Addressable Multi Detector, LPCB approved to EN54-7, with embedded MCU, drift compensation, Every detector shall be microprocessor based with 360° LED indication and electronically settable addresses and should not have DIP/rotary addressing and only store the address on memory and dirty detector notification, four programmable sensitivity levels, and two-wire non-polarized loop connection with operating voltage between 16–28 V DC (Modulated-pulse) and provides minimum obscuration ratio - 0.113 to 0.203 dB/m , Heat sensitivity 54° C ~ 65° C and standby Current: ≤ 0.5 m with alarm current: ≤ 1.0 mA having minimum relative humidity: ≤ 95% RH (non-condensing at 40°C ±2°C) . The detector shall have red LED for alarm indication and provide red flashing for LED polling indication The detector should be having digital filter for dust discrimination with nuisance alarm indication.Make: Glyptic/Siemens/Autronica |
| 3 | Supply, installation, testing and commissioning of Addressable Manual Call Point, suitable for indoor use,dual -action hammerless resettable type (operated by special key), and ransparent protective cover for accidental activation protection with LED status indication Red alarm LED (steady ON during alarm) Red polling LED (flashing during normal communication) , manual addressing capability, two-wire non-polarized loop connection, operating voltage 16–28V DC, IP43 protection rating, complete with mounting box and accessoriesm and fully compatible with Fire detection alarm panel. LPCB approved to EN 54 standardMake: Glyptic/Siemens/Autronica |
| 4 | Supply, installation, testing and commissioning of Addressable Sounder cum Strobe (Sounder Beacon), compliant with EN54-3, suitable for indoor use, with 16 selectable tones, adjustable sound output upto 4 levels, high-intensity LED for visual alarm, loop-powered operation (no external 24V required for standard use), manual addressing capability, two-wire non-polarized connection, operating voltage 16–28V DC, IP43 protection rating, complete with base and accessories. LPCB approved to EN 54 standard Make: Glyptic/Siemens/Autronica |
| 5 | Supply Installation Testing Commissioning of Conventional reflective beam detectorwith EN-54 COMPLIED AND CE APPROVED and minimum distance range of 100 metres. with Integrated transmitter and receiver. Reflective prism for ranges beyond short span Automatic signal compensation for building movement, dust accumulation, and aging Fault monitoring for beam block, alignment loss, contamination, and internal failures. The detector should have minimum 3 sensitivity levels and minimum 3 dedicated LED status indicators for Fire, Fault and Alignment. The detector should have Relay Output: Fire/Fault output, 2.0A @ 30 VDC, Normally Open (NO). Make: Glyptic/Siemens/Autronica |
| 6 | Supply, Installation, Testing and Commissioning of dual IR powered flame detection system designed for critical infrastructure and harsh outdoor environments. The device shall have minimum dual sensors including a 5MP progressive scan super low lux CMOS sensor and an IR flame sensor using 4.3 µm main detection with a 5.0 µm comparative band, and the device shall have a fixed F1.6 4 mm 5MP lens with horizontal field of view of 90° and vertical field of view of 48°. The device shall be capable of distinguishing radiation spectrum differences produced by sunlight, light and combustion, using two pyroelectric infrared detectors in different bands to ensure high sensitivity detection and very low false alarm rates. The device shall have a minimum built‑in mechanism to confirm and filter flame detection results directly at the device side, and the details shall have full‑color night view capability with WDR support and selectable 3D DNR levels (disable/low/middle/high). The device shall have dual video streams with main stream resolutions up to 2880×1620 @ 25 fps, 2560×1440 @ 25 fps, 1920×1080 @ 25 fps or 1280×720 @ 25 fps and sub stream resolutions selectable down to 640×360 @ 15 fps, with H.265 and H.264 compression, configurable CBR or VBR bitrates, and G.711A or AAC audio compression at 64 kbps. The device shall have support for TCP/IP (IPv4 and IPv6), HTTP, DHCP, RTSP, NTP, P2P and SIP protocols, and shall have ONVIF and WebRTC interface support with SDK for integration, supporting simultaneous preview of not less than 10 channels.The detector should have minimum built in 2G DTR watchdog for continuous monitoring of the healthiness of the system.The device shall have built‑in 64 GB MicroSD/SDHC/SDXC card local storage, expandable to 128 GB or 256 GB, alarm picture and video push and linkage.The detection range should be minimum at 1.5m distance for 30x30 pixel to of at least 30 meters for a 30 cm × 30 cm flame, with a full‑screen detection area and self‑defined arming schedule, and shall be capable of installation indoors at heights above 2.5 m or outdoors at heights above 3.5 m. The device shall have white LEDs with maximum white light range of 30 m, and shall support operating temperature from –20 °C to +60 °C with ≤90 % relative humidity non‑condensing. The device shall have an IP67 ingress protection rating for outdoor weatherproof installation, shall support OSD with title, time, date and up to seven user‑defined OSD lines, and shall support firmware upgrades via tool upgrade.Make: Glyptic/Siemens/Autronica |
| 7 | Supply, installation, testing and commissioning of Addressable Monitor Module, for monitoring external fire protection devices with EOL supervision, LED indication, two-wire loop connection, 16–28V DC operation, complete with base and accessories.The module shall have 2 LEDs, Operating indication LED flashing and action LED emitting on signal input with minimum IP32 rating. LPCB approved to EN 54 standard Make: Glyptic/Siemens/Autronica |
| 8 | Supply, installation, testing and commissioning of Addressable Isolator Module, EN54-17 compliant, loop powered, dual isolation with LED indication, 18–28V DC operation, complete with base. Each isolator module shall be equipped with two independent directional LED indicators (Left LED and Right LED) that display the exact zone or loop segment where the short-circuit has occurred. In the event of a short circuit before the isolator, the Left LED shall illuminate. In the event of a short circuit after the isolator, the Right LED shall illuminate. LPCB approved to EN 54 standard Make: Glyptic/Siemens/Autronica |
| 9 | Supply, Installtion, Testing and Commissioning of 2C x 1.5 sq.mm armoured, FRLS cable complete as required and as per specifications.Make: Glyptic/Siemens/Autronica |
| 10 | Supply, Installtion, Testing and Commissioning of 2C x 2.5 sq.mm armoured, FRLS cable complete as required and as per specifications.Make: Glyptic/Siemens/Autronica |
| 11 | Supply, Installtion, Testing and Commissioning of 5 amp SMPS Make: Glyptic/Siemens/Autronica |
| 12 | Add GST @18% and CESS @1% Connecting the equipments body to earth busbar incl. S & F 50 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender