Tender for Providing Electrical Works For Bsnl Integrated Network Command Centre (Bincc) At Telephone Bhawan, Bhubaneswar (S.H: Providing Fire Alarm And Fire Extinguishers)
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of UL listed, CE certified 2 wire conventional Photo electric / Ionization type Smoke detector with base (Blinking LED type) made of ABS plastic with all accessories, suitable for operation on 24V DC, internal protection class: IP23, dual pulsing LED with 3600 visibility, relative humidity: ≤95%; non-condensing and EN54 compliance of approved make etc. as required. (Make- Apollo / GST/ Honeywell / System sensor) |
| 2 | Supply, installation, testing and commissioning of electronic hooter cum speaker made of 16/18SWG CRCA sheet duly powder coated with PO red colour, output not less than 80db @25mtr, LMT with adjustable sound output of 2.5 watt,5 watt, suitable knock out for cable entry from top suitable for operation on 100/70 volt RMS AC supply etc. as required. (Make- Agni Instruments Engineers (P) Ltd/Apollo / Honeywell / GST/ system sensor/ Ravel ) |
| 3 | SITC of manual push button station (pill box) Manual Call Point in MS Housing for Conventional Fire Alarm System with glass for breaking up in case of fire and hammer with chain etc. (Make- Agni Instruments Engineers (P) Ltd/Apollo / Honeywell / GST/ system sensor/ Ravel ) |
| 4 | Supply and laying of 2core 1.5sqmm copper conductor FRLS PVC insulated and PVC sheathed Un Armoured Cable on surface/recess for looping the fire alarm devices & providing power supply to sounder cum strobes etc. as required. (ISI) |
| 5 | Supplying and making indoor end termination with brass compression gland and aluminium lugs for 2 core, 1.5 Sq. mm (19mm) size of PVC insulated and sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 6 | S/F ABS round box / MS Box on ceiling for fixing the detectors etc as reqd. |
| 7 | Supplying installation, connection and testing of Response indicator having twin LEDs for mounting on false ceiling / wall at the entries of the cabin for indicating the operation of detectors in the above false ceiling / below false flooring detectors etc., as required. |
| 8 | Supplying & Fixing of wall mounted Auto glow Signage Fire Exit Sign Board 3mm PVC Sheet with high Glow intensity in total Darkness. (Red and Green colour with exit symbols as per requirements) |
| 9 | Refilling of 4.5 KG CO2 type Portable Fire Extinguisher with fresh /sufficient quantity / quality of CO2 with proper weight and measure, labeling with date of refilling and expiry date of refilling as per the ISI standards and as per the norms of Fire Authorities including transportation to workshop/factory and back, loading, unloading etc, re-fixing the same in proper position and location as per the requirement and direction of BSNL authority. |
| 10 | Hydraulic Pressure Testing of 4.5 capacity CO2 type Fire Extinguishers as per IS: 5844 -1970 (Reaffirmed 2006) and submission of Test certificates etc. as required. |
| 11 | Painting the Fire Extinguisher cylinders with appropriate signal red colour as per the standards after removing the rust etc. and supply and fixing of operating instructions stickers on the extinguishers having instructions and use of fire extinguishers as per standards etc. as required. |
| 12 | Supply and Fixing of Carbon Dioxide based (as per IS 15222), Stored pressure type, 4.5 Kg capacity fire extinguisher confirming to IS: 15683:2018 (with latest amendments), cylinder body made of steel (as per latest IS:7285), operating temperature from -200C to +600C with carrying handle, hose assemblies, mounting brackets etc. suitable for Class A,B & C fire, minimum effective discharge time 11sec or higher, fire ratings of 55B or better, BIS marking etc. as required. (Test report from Central Govt. Laboratory/NABL accredited Laboratory/ILAC accredited Laboratory or higher shall be furnished) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 11, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysAug 18, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender