Tender For Provision Of Stand By Air Circuit Breaker And Addn/Altn To Crash Bell Of Atc At Af Stn Ad Ur
Tender Value
9.03 Lakhs
Estimated cost
Bid Submission
02 Sep 2026
22 days left
EMD
18060
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jalandhar → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Stand By Air Circuit Breaker And Addn/Altn To Crash Bell Of Atc At Af Stn Ad Ur
BOQ
| Sl. No. | Item Description |
| 1 | Taking out old unserviceable LT UG Cable of any sizes/capacity, complete all as specified and directed |
| 2 | Excavation in trenches n. exc 1.5 metre wide for taking out/ laying pipe line, cable, foundation etc. not exc exceeding 1.5 metre deep and getting out as in soft/ loose soil complete all as specified and directed. |
| 3 | Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 4 | Removal of excavated surplus spoil to a distance n. exc. 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified and directed. |
| 5 | M&L for Clean dry sand ( locally available) as cushioning for under ground cable 230 mm thick (one layer of 80 mm thickness before laying the cable and other layer of 150 mm thickness after laying the cable) complete all as specified and directed.NOTE:- Punned down thickness (over all 180 mm) shall be considered for measurement and payment. |
| 6 | M&L for supplying and laying locally availabel, sub class 'B' Bricks (old size), laid flat and perpendicular to the direction of cable adjacent to each other in trenches over the cable for protection complete all as specified and as directed. |
| 7 | M&L for boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all specified and directed. |
| 8 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 16 Sqmm, 4 core multistranded including cable connecting lugs, glands,jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and as directed. |
| 9 | Supply and fixing in replacement gong bell single phase 220V AC cast iron body and weather proof dia 12\\" complete all specified and directed. Make - Edison or equivalent. |
| 10 | Supply and fixing in replacement push type NO/NC Switch 240V, 10A including enlosure box complete all specified and directed. |
| 11 | S&F sheet metal enclouser (DB) double door single pole and netural 4 way, 240 volt with 200 Amps rated bus bar complete all specified and directed. |
| 12 | Supply and fixing MCB Triple pole and Neutral, 415 volts, 63 Amps, 'C' Curve, 10 KA, including disconnecting, taking down old/unserviceable, MCB Triple pole and Neutral complete all as specified and as directed. |
| 13 | M&L for Submain wiring alongwith PVC insulated unsheadhed multi stranderd copper conductor cable of size 2x2.5 sqmm+1x2.5 sqmm earth wire FRLS in and including non metalic concealed PVC conduit medium grade suitable dia as per SSR specification. |
| 14 | Supply, installation, testing and commissioning of Air Circuit Breaker 1250 Amps, 4 Pole, 415V, Ics = 100% Icu, Icw= 50 KA for 1 second, Cat-B, short circuit making current peak 105 KA, rated lightening impulse withstand voltage 12 KV, opening time < 40 mili second, closing time < 70 mili second, provision of ETU (Electronic trip unit) for measurement of current, overload protection, short ciruit protection, earth fault protection, various fault indication, manual draw out type, as per IS-13947-2/IEC-60947 Part 2 : 2016 complete all as directed by Eng-in-Charge. Make Havells, Model-TitaniaNote : The breaker should be compatible |
| 15 | Supply, installation, testing and commissioning of Air Circuit Breaker 630 Amps, 4 Pole, 415V, Ics = 100% Icu, Icw= 50 KA for 1 second, Cat-B, short circuit making current peak 105 KA, rated lightening impulse withstand voltage 12 KV, opening time < 40 mili second, closing time < 70 mili second, provision of ETU (Electronic trip unit) for measurement of current, overload protection, short ciruit protection, earth fault protection, various fault indication, manual draw out type, as per IS-13947-2/IEC-60947 Part 2 : 2016 complete all as directed by Eng-in-Charge. Make Havells, Model-TitaniaNote : The breaker should be compatible |
| 16 | Note : Amount of credit for retrieved materials is mentioned in Sch 'A' Section-II of tender documents in pdf form which will be deducted while acceptance of tender offline. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 11, 2026
11:30 IST
Tender Published
Tender notice published.
TodaySep 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 22 daysSep 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 24 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender