Tender For Provn Of Three Phase 03 X 30 Kva Online Ups With 1 Hrs Backup For P-114 (Ot), T-16 (Icu) & Acute Ward Alongwith All Allied Works And Provn Of Lighting Conductor At New Opd Complex Alongwith Earthing At Mh Ramgarh Cantt
Tender Overview
Project Description
Tender for Provn Of Three Phase 03 X 30 Kva Online Ups With 1 Hrs Backup For P-114 (Ot), T-16 (Icu) & Acute Ward Alongwith All Allied Works And Provn Of Lighting Conductor At New Opd Complex Alongwith Earthing At Mh Ramgarh Cantt
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-Aug-2026 | BOQ CORRIGENDUM | BOQ | 31-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | S & F of online UPS 30 KVA/360V 3- phase, input- voltage range 305-478 VAC @100% load and otput400/415 VAC zero transfer time, LCD panel noise level less than 65db @1 Meter with connected accessories including testing on completion complete all as specified and as directed by Eng-in -Charge. |
| 2 | S & F of Exide Power Safe Battery 12 V 65 AH-16 Nos as suitable for 30 KVA online UPS complete all as specified and as directed |
| 3 | M & L for Sub main wiring FOUR single core 10.0 Sqmm PVC insulated FRLSH multistanderd copper conductor cable and one run of 10 Sqmm PVC insulated unsheathed FRLSH multistanderd copper conductor cable for earth wire drawn in & including srface rigid non metallic PVC conduit medium grade with fittings (ISI marked) not less than 25 mm dia in ncluding taking down of existing conduit or batten complete and making good disturbed surface wall complete all as specified and as directed. Note : - FOUR runs of 10 Sqmm cable and one run of 10 Sq mm earth wire and one run of PVC conduit shall be measured as one unit length. |
| 4 | Supply, laying and testing LT cable, XLPE Insulated ,armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 Sq.mm. 3.5 core including complete all as specified & directed. Note:- 1. Excavation & earthwork shall be measured & paid under respective item (2) All Necessary T & P required shall be arranged by the Contractor. |
| 5 | Supply, laying and testing LT cable, XLPE Insulated ,armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sq.mm., 4.0 core including complete all as specified & directed. Note:- 1. Excavation & earthwork shall be measured & paid under respective item (2) All Necessary T & P required shall be arranged by the Contractor. |
| 6 | S&F sheet metal enclosures for DBs tripple pole & neutral 4 way double door with suitable Amp rated bus bar, 415 Volts suitable to accommodate MCB and necessary electric cable connection through suitable lugs by crimping and making good disturbed area of wall complete all as specified & as directed. |
| 7 | S&F 415V, 10KA 'B' curve miniature circuit breaker (MCB) of triple poles and neutral (TPN) and current carrying capacity 100 Amp in the DB with connection testing and commissioning complete all as specified and as directed. |
| 8 | S&F sheet metal enclosures for DBs single pole & neutral 4 way double door with suitable Amp rated bus bar suitable to accommodate MCB and necessary electric cable connection through suitable lugs by crimping and making good disturbed area of wall complete all as specified & as directed. |
| 9 | Supply and fixing amp rating 240V, 10KA 'B' curve miniature circuit breaker (MCB) of single poles and neutral and current carrying capacity 63 Amp in the MCB DB complete with connection testing and commissioning complete all as specified and as directed. |
| 10 | Supply and fixing 240V, 10KA 'B' curve miniature circuit breaker (MCB) of single poles (SP) and current carrying capacity 6 to 32 Amp in the MCB DB with connection testing and commissioning complete all as specified and as directed. |
| 11 | M & L for Excavating in trenches, in any type of soil not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc or not exceeding 10 Sqm on plan and not exceeding 1.5m in depth for shafts, cesspits, manholes, pier holes, etc and getting out in any type of soil complete all as specified and as directed. |
| 12 | M & L for Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as specified and as directed. |
| 13 | M & L for Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed |
| 14 | M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable all as specified and directed by Engr - in - Charge. (Note:- Punning thickness shall be measured) |
| 15 | Material and labour for Supplying and laying un-reinforced pre cast concrete cable cover class LV, Type - 1 , flate, size 250 mm x 150 mm x 40 mm complete all as specified and as directed by the Engineer-in-Charge. |
| 16 | S&F in repair Rigid non-metallic PVC conduit 25 mm dia exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and as directed. |
| 17 | M&L in repairs for Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth wire of 4 mm dia (up to 7.5 m in length from earth plate ) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no.3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia at 150mm c/c in both ways as reinforcement, watering funnel, 20 mm dia light grade for protection of earth electrode, 20 mm dia GI pipe light grade for watering complete all as specified and as directed by Engineer in charge and tested on completion. Note : The rate is ilnclusive of necessary earth work, returning, filling in and removal etc |
| 18 | S&F in replacement of off load changeover switch 415 volt in sheet metal encloser 4 pole of capacity 200 Amp complete all as specified and directed. |
| 19 | Supply and Installation of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm². Test Parameter: a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.034 µΩm, c.Tensile strength - 178 MPa or N/mm² d. Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2. CAPE Type: SRC 8–AL (Article No. 400 008) |
| 20 | Supply and fix of Stainless steel Conductor Holder clip for fixing the 8mm dia round conductor on the side wall . Test Parameter: Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-4 Cape Type: CHC 8 (Article No. 400 552) |
| 21 | Supply and fix of Stainless Steel Metal roof holder or Folding Clamp as per sheet profile for 8-10 mm dia Aluminium alloy Solid Round Conductor for horizontal Air terminal above metal sheet to meet the requirements for IS/IEC 62305. Test Parameter: Salt Spray Test ( IEC 62561-4) - No sign of Corrosion CAPE TYPE: MRMCH 8-10 (Article No. 402 230) OR CAPE Type: FSCH 14-8 (Article No: 440 011) |
| 22 | Supply of Adhesion Glue for fixing metal roof conducter holder over the metal surface to meet the requirment of IS/IEC - 62305. CAPE Type: AG10 (Article No. 400 411) |
| 23 | Supply and fix of UV resistance Nylon/PU roof conductor holder for flat roof with concrete block for fixing 8 mm dia Aluminium alloy Solid Round Conductor in the terrace flat surface at every 1 mtr. CAPE Type: MBPCH 8 (Article No. 403 201) |
| 24 | Supply and Installation of Stainless steel 304 Grade Cross Connector for 8 mm dia Aluminium alloy round conductor & 10 mm Copper bonded conductor at cross/Tee junction. Test Parameter a) Mechanical Load b) Electrical Test c) ENvironmental Test Tested for IEC 62561-1 CAPE Type: CCSS 8-10 (Article No. 400 206) |
| 25 | Supply and Installation of Expansion Joint with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations. Expansion Joint should be consider at every 20 mtr length of straight horizontal air termination and connected at both the end with use of straight connector conductor. CAPE Type: EPC 8 (Article No. 401 209) |
| 26 | Supply and Installation of Aluminium Straight conductor connector for interconnecting 8mm Aluminium conductor to meets the requirement of IS/IEC 62305. Test Parametres: a) Mechanical Load b) Electrical Resistivity c) Environmental Test Tested as per IEC 62561-1 CAPE Type: CJ 8 (Article No. 401 211) |
| 27 | Supply of air termination rod of 1mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends (Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories. Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2 CAPE Type: VATW1 (Article No. 402 411) |
| 28 | Supply of air termination rod of 2mtr length of material AlMgSi of diametre ø 16/10 mm crimped on both the ends (Tappered Type). The rod shall be mounted with stainless steel clamp and fixing accessories . Test Parameter: Mechanical Load Test for individual aluminium alloy rods - 120 to 280 N/mm² Salt Spray Test-No sign of corrosion Tested as per IEC 62561-1&2 CAPE Type: VATW2 (Article No. 404 420) |
| 29 | Supply and Installation of Folding Clamp as per for 8 mm dia Aluminium alloy Solid Round Conductor for horizontal Air terminal above metal to meet the requirements for IS/IEC 62305. CAPE Type: FSCH 14-8 (Article No: 440 011) |
| 30 | Supply and Installation of 8mm dia Aluminium alloy Solid Round Conductor of material AlMgSi used in air termination and down conductor system . Cross sectional area of conductor should be 50 mm². Test Parameter: a.Lightning impulse current of 100kA for 10/350 µs b.Electrical resistivity - 0.034 µΩm, c.Tensile strength - 178 MPa or N/mm² d. Salt spray - No Sign of Corrosion. Tested as per IEC 62561-2. CAPE Type: SRC 8–AL (Article No. 400 008) |
| 31 | Supply of Stainless steel Conductor Holder clip for fixing the 8mm dia round conductor on the side wall . Test Parameter: Salt Spray Test - No Sign of Corrosion Tested as per IEC 62561-4 Cape Type: CHC 8 (Article No. 400 552) |
| 32 | Supply and Installation of Stainless Steel 304 grade Test Joint with enclosure to interconnect between 8 mm Al. round conductor to 10 mm copper bonded round conductor. Test Parameter: Salt Spray Test for test joint plate -No sign of Corrosion Tested as per IEC 62561-1 CAPE Type: TJRRE - G1 (Article No. 404 214) |
| 33 | Supply and Installation of Lightning counter - LCD screen shows the number of lightning strikes, hour and date of lightning events Buttons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, Complies with IEC/EN 62561-6. CAPE Type No: PRO LER (Article No. 400 999) |
| 34 | Supply and Installation of Rust resistant non corossive 10 mm dia Copper Bonded Steel round conductor used for Earth termination inside the concrete and soil. Test parameter: a) Short circuit current test for copper bonded conductor:Test 6 kA ratings, as per cross sectional area for 1 sec (IS3043/IEEE80); b)Electrical Resistivity before & after salt mist spray test: 0.25µΩm max. c)Tensile Test 290 to 510 N/mm². d)Adhesion no peel or crack & Bend test no seperation of Cu, e)Cu Coating thickness min. 70µm. Tested as per IEC 62561-2. CAPE Type: SRC 10 CU (Article No. 400 010) |
| 35 | Supply and Installation of Stainless steel SS 304 Grade Conductor Holder for fixing the 8 -10 mm dia round conductor on the wall . Test Parameter: a) Mechanical Load b) Environmental Test Tested as per IEC 62561-4 CAPE Type: CH 8-10 (Article No. 400 213) |
| 36 | Supply and Installation of CAPE make UL Listed Maintenance Free Copper bonded Earth rod of 3048mm length having the dia of 14.2 mm with copper coating thickness of 254 microns. The rod has been tested for Dimension, Marking, Tensile Strength, Salt mist, coating thickness, Electrical resistivity test before and after corrosion test as per IEC 62561-2 & UL 467. CAPE Type No. CBR 1410 (Article No. 300 010) Supply and Installation of CAPE make earth enchancing mineral compound tested for leaching and TCLP with NABL accredited Lab as per IEC 62561-7 -25 kg CAPE Type: PROSAN 25 (Article No. 300 832) Supply and Installation of CAPE make Earth rod clamp made for terminating cable / flat conductor. CAPE Type: ERC 1417 SS (Article No. 300 463) + CAPE Type: CPES 8 (Article No. 401 504) Supply and Installation of CAPE make Earth Chamber Inspection Pit made up of Plastic withstand load of 60kN CAPE Type: EC 290 (Article No. 300852) |
| 37 | SURGE PROTECTION DEVICE Nominal AC voltage -240V Maximum Continuous Operating Voltage- 300V(LN)/305V(P-NE) Nominal Discharge Current - 20Ka(L-N)/50Ka(P-NE) Maximum Discharge Current - 65Ka(L-N)/100Ka(P-NE) Impulse Discharge Current - 12.5Ka(L-N) Voltage Protection Level - 1500V (L-N) Response Time - <100ns(L-N) Over Current Protection - 315 A Shortcircuit protection - 25KA/50KA TOV With stand 120Min. - 442V(L-N) TOV With stand 200ms.- 1200V(N-PE) Model - T1H-300-3+1-R Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
TodayBid Submission Deadline
Online submission via eProcurement portal.
TodayTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender