Housing Urban and Rular Development Government Departments Closing in 3 days TDR #56924819

Tender For Supply Installation Testing and Commissioning of Fire Pump At Court Complex Balotara

Issued by Government Departments · Jodhpur, Rajasthan
Tender Value
16.02 Lakhs
Estimated cost
Bid Submission
15 Aug 2026
3 days left
EMD
32040
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jodhpur → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Supply Installation Testing and Commissioning of Fire Pump At Court Complex Balotara

BOQ

Name of Work:- SITC of Fire Pump at Court complex Balotara
Sl. No. Item Description
1Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.
2(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
3(B) Material of construction : Pump Casing - PN-16,Cast Iron, Impellor - Bronze/SS-304, Shaft - SS 410, Packing - Mechanical Seal
4(C)Pump shall be capable of delivering not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
5(D) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed 2900 / 1500 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (LoveJoy type) coupling , coupling guard complete in all respect .
6( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.
7(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. or by Third Party like RITES / PDIL / EIL
8(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM
9(H) Pumpset to be placed on Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x 40mm x 5 mm ( Cost of RCC Foundation to be paid Extra See Chapter -23).
101620 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage, 2900 RPM
111620 LPM suitable for 70 Mtr Head End Suction Back pull type Single Stage, 2900 RPM
12Supplying, Installation, Testing & Commissioning of Diesel Engine Driven fire fighting duty pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F, G and H.
13(A) End Suction / Horizontal Axially split casing volute type Single / Multi stage Centrifugal pump complete for delivery of below mentioned discharge and Head
14(B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal
15(C)Pump shall be capable of delivering not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head
16(D) Heat Exchanger cooled Diesel Engine as per NFPA 20 developing suitable BHP for the below mentioned discharge at 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter upto 10 M length (with LRB insulation & Alum. Cladding), with muffler, Diesel tank of 300 Lts capacity (made out from 2 mm thick MS sheet with filling Cap) with drain cock, Diesel level Indicator, Suitable MS angle iron stand for placing tank, first Filling of Diesel tank.
17(E) Diesel Engine Control panel comprising Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication, Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter,
18(F) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. or by Third Party like RITES / PDIL / EIL
19(G) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM
20(H) Pumpset to be placed on Suitable size Existing Reinforced cement concreat (M-30) foundation with foundation bolt, Nosing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra See Chapter -23)
211620 LPM suitable for 56 Mtr Head End Suction Back pull type Single Stage 2400 RPM
22Supplying, Installation, Testing & Commissioning of Electrical Driven fire fighting duty Jockey pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A, B, C, D, E,F and G
23(A) Horizontal End suction Single / Multi Stage Centrifugal Back pull type pump complete for delivery of below mentioned discharge and Head
24(B) Material of construction : Pump Casing - PN-16,Cast Iron, Impellor - Bronze/SS-304, Shaft - SS 410, Packing - Mechanical Seal
25(C) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 2900 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Lovejoy type) coupling , coupling guard complete in all respect .
26(D) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads.
27(E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Physical presence of Department’s representatives. or by Third Party like RITES / PDIL / EIL
28(F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM
29(G) Pumpset to be placed on Suitable size Reinforced cement concrete (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra see chapter - 23 )
30180 LPM suitable for 56 Mtr Single Stage
31Supplying, Installation, Testing & Commissioning of submersible type dewatering pump of stainless steel casing and Cast iron impellor of discharge and head given below complete with all accessories suitable for operation on 230 V, single phase/415 V /3 phase, 50 Hz. AC supply complete with starter for automatic operation including water level sensing device / float switch inter connection with submersible cable etc. as required.
32180 LPM with 10 mtr head
33Providing and fixing 20/25 mm dia. (PN - 1.6, Type-S1, Flanged, ISI marked) air release valve confirming to IS - 14845 : 2000 with Double Flange isolating valve (pressure rating PN 1.6) complete with 1 no. Matching Flanges (Minimum 10 mm thick), nuts, bolts, washers, gaskets etc as required.
34Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C ' class (Heavy) pipes conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications including cutting, screwing, welding etc. & forged steel fittings like elbows, tees, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts including cutting hole and chase in brick walls and making good the same. complete with painting of one coat of Red Oxide and two or more coat of synthetic enamel paint of Signal red shade complete as required. (Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs.).
35200 mm dia, 6.0 mm thick
36Supplying and fixing cylindrical air vessel of continuous welded construction for pump room made of 450 mm dia,fabricated out of 10 mm thick dished ends and 8 mm thick MS sheet, 2000 mm in height with flanged connection, Provision for 25 mm dia drain valve,air release valve, safety valve pressure gauge as required accessories and painting with two coats of Red Oxide and two coat of Signal red enamel paint including the tank installed on suitable vertical legs. The legs shall be provided with M.S. Angle of size 75 mm x 75 mm x 5 mm at the bottom. The legs shall be grouted in cement concrete foundation. as required. ( Air Release valve, Drain valve, PRV, Pressure Gauge shall be Paid Extra ).
37Supplying and Fixing of PN 16 Flanged Y strainer fabricated out of cast iron body, SS 304 strainer with perforated screen with 3 mm. dia holes in existing MS / GI pipe complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets etc as required of following sizes.
38200 mm dia
39200 mm dia
40Supplying and Fixing of PN 16 Cast Iron swing check type reflux (Non return) Valve / Non return valve with SS / Bronze flap confirming to IS:5312 (part1) : 2004 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes.
4180 mm dia
42100 mm dia
43150 mm dia
44200 mm dia
45Supplying and Fixing of PN 16 Butterfly Valve (Wafer Type) with S.G Iron Disc and confirming to IS:13095 complete with 2 no. Matching Flanges (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following sizes.
4650 mm dia
4780 mm dia
48100 mm dia
49150 mm dia
50200 mm dia Gear Operated
51Supplying and Fixing of PN 16 Brass/GM Ball valves with screwed end, SS Ball including teflon tape etc. as required.
5225 mm dia.
53Providing and Fixing of PN16 Resilient rubber lined single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe including Matching Flange (Minimum 16 mm thick), nuts, bolts, washers, gaskets, etc as required of following Sizes.
5480 mm Dia. x 150 mm OAL
55100 mm Dia. x 150 mm OAL
56150 mm Dia. x 150 mm OAL
57Incoming : 400 A, 50 kA, 4 pole MCCB, Ics = 100% Icu rating, Digital Voltmeter (0-500 V) with selector switch, Digital Ammeter (0-250A) with selector switch and CTs, LED type RYB Indicating lamp, ON, OFF Trip Indicating lamps, Aluminium TPN Busbar 500 Amps.
58Outgoing Main Fire Pump: 200 A, 50 kA, 4 pole MCCB, Ics = 100% Icu rating, with suitable HP fully automatic DOL starter as per type-2 coordination with all accessories, internal wiring required for automatic operation, Digital Ammeter with selector switch and LED type ON, OFF Trip Indicating lamp, selector switch for local/remote, auto /manual/OFF operation - 1 Set
59Outgoing Jockey Pump: 100 A, 50 kA, 4 pole MCCB, Ics = 100% Icu rating, with suitable HP fully automatic DOL starter as per type-2 coordination with all accessories, internal wiring required for automatic operation, Digital Ammeter with selector switch and LED type ON, OFF Trip Indicating lamp, selector switch for local/remote, auto /manual/OFF operation - 1Set
60Diesel Engine Control Panel : Comprising of Automatic / Manual selector switch and 3 attempts starting device, timers and relays as required push buttons, Start / Stop in Manual mode Indicating lamp for high / low lub. Oil pressure, High water temperature indication, Battery charger suitable for for 12V/ 24 V DC with boost and trickle selector switch, 0-30 V DC voltmeter, 0-20 A Dc ammeter, All standard accessories and relays for automatic operation of Engine
61System controller : Designing, supply Installation testing and commissioning of system controller to control operation main Electrical fire pump, jockey pump, Terrace pump in sequence as per requirement, consisting of relays, timers sensors, annunciation window for fault indication complete as required. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56924819
AUTHORITY Government Departments
TENDER VALUE 16.02 Lakhs
LAST DATE 15-08-2026
Authority
Authority Name Public Works Department
Work Description Tender for Supply Installation Testing and Commissioning of Fire Pump At Court Complex Balotara
Basic Detail
Tender No NIT No.33 of 2026-27 of E.E. PWD Elect.Dn.II Jodhpur
Bidding Type Tender
Location
City Jodhpur
State Rajasthan
Key Dates
Publish Date 10 Aug 2026
Submission Date 15 Aug 2026
Open Date 17 Aug 2026
Finance
Tender Value 16.02 Lakhs
Tender Fee 500
EMD 32040
Exemption Available
Document List
3646adce-7cc7-414d-98e1-373bef22c798.html
BOQ_1040058.xls
Tendernotice_1 (34).pdf
Tendernotice_2 (5).pdf
Tendernotice_3 (2).pdf
Tendernotice_4 (2).pdf
Tendernotice_5 (1).pdf
Tendernotice_6.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 10, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 15, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 3 days
Aug 17, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 5 days

Tender Documents

Download All (ZIP) ↓
html

3646adce-7cc7-414d-98e1-373bef22c798.html

xls

BOQ_1040058.xls

pdf

Tendernotice_1 (34).pdf

pdf

Tendernotice_2 (5).pdf

pdf

Tendernotice_3 (2).pdf

pdf

Tendernotice_4 (2).pdf

pdf

Tendernotice_5 (1).pdf

pdf

Tendernotice_6.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders