Tender For Repair And Replacement Of Lt Panel Feeder Piller Box, Panel And Other Connected Work At Technical Area Under Ge (I) R&D Pashan
Tender Value
Ref. Documents
Estimated cost
Bid Submission
29 Aug 2026
21 days left
EMD
96000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair And Replacement Of Lt Panel Feeder Piller Box, Panel And Other Connected Work At Technical Area Under Ge (I) R&D Pashan
BOQ
| Sl. No. | Item Description |
| 1 | Supply, install test and commissioning in repair of LT Panel Board CPRI approved cubical with KIOSK type made of 3.15 mm thick outdoor type with IP 65 grade of protection dustproof and vermin proof with ingress pretection CRCA sheet, powder coated, with support of 50mm x 50mm x 6mm angle iron bottom frame with double hinged rear openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved aluminium bus bar of capacity 600 Amps- 04 Nos, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations complete testing and commissioning complete all as specified and directed and shall be consisting the following (i) Incomer(a) MCCB 4 pole thermal/magnetic setting, 400 Amp, 415 Volts 50 KA– 01 No (b) Bus bar chamber with electrolytic aluminium bus bar suitable for 600 amps capacity for 3 phase and neutral (all connection inside the panel shall be through aluminium strip) connected duly supported with FRP insulators including colour code heat shrieked insulating sleeves -(ii) Out going (a) MCCB 4 pole 200 Amp, 415 Volts 36 KA – 01 Nos(b) MCCB 4 pole 125 Amp, 415 Volts 36 KA – 04 No(c) Panel mounted type digital multifunctional energy meter A, V, Z, KW, PF CT operated, LT 3 phase, 4 wire - 01 No(d) LED type indicating lamp for phases and neutralNote: All MCCB having Spreader links with direct Rotary handles. |
| 2 | Supply, install test and commissioning in repair of LT Panel Board CPRI approved cubical with KIOSK type made of 3.15 mm thick outdoor type with IP 65 grade of protection dustproof and vermin proof with ingress pretection CRCA sheet, powder coated, with support of 50mm x 50mm x 6mm angle iron bottom frame with double hinged rear openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved aluminium bus bar of capacity 750 Amps- 04 Nos, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations complete testing and commissioning complete all as specified and directed and shall be consisting the following (i) Incomer(a) Bus bar chamber with electrolytic aluminium bus bar suitable for 750 amps capacity for 3 phase and neutral (all connection inside the panel shall be through aluminium strip) connected duly supported with FRP insulators including colour code heat shrieked insulating sleeves -(b) MCCB 4 pole, 500 Amp, 415 Volts 36 KA– 01 No (ii) Out going (a) MCCB 4 pole 320 Amp, 415 Volts 36 KA – 01 Nos(b) MCCB 4 pole 125 Amp, 415 Volts 36 KA – 01 No(c) MCCB 4 pole 100 Amp, 415 Volts 36 KA – 02 No (d) Panel mounted type digital multifunctional energy meter A, V, Z, KW, PF CT operated, LT phase, 4 wire - 01 No(e) LED type indicating lamp for phases and neutral |
| 3 | Supply, install test and commissioning in repair of LT Panel Board CPRI approved cubical with KIOSK type made of 3.15 mm thick outdoor type with IP 65 grade of protection dustproof and vermin proof with ingress pretection CRCA sheet, powder coated, with support of 50mm x 50mm x 6mm angle iron bottom frame with double hinged rear openable shutters of each feeder control unit with locking arrangement in front and back openable inspection doors PVC sleeved aluminium bus bar of capacity 400 Amps- 04 Nos, for each phases and neutral fixed on suitable insulator all housed in suitable bus bar chamber and provision and fixing of digital Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable cable glands etc fixed on suitable PCC foundations complete testing and commissioning complete all as specified and directed and shall be consisting the following :- (i) Incomer(a) MCCB 4 pole, 250 Amp, 415 Volts 25 KA– 01 No (b) Bus bar chamber with electrolytic aluminium bus bar suitable for 400 amps capacity for 3 phase and 01 neutral (all connection inside the panel shall be through aluminium busbar) connected duly supported with FRP insulators including colour code heat shrieked insulating sleeves - (ii) Out going (a) MCCB 4 pole 125 Amp, 415 Volts 25 KA – 03 No(b) MCCB 4 pole 100 Amp, 415 Volts 25 KA – 02 Nos(c) MCB 4 pole 63 Amp, 415 Volts 10 KA-02 Nos(d) MCB SPN 32 Amps,220 Volts, 15 KA - 02 Nos(e) Panel mounted type digital multifunctional energy meter A, V, Z, KW, PF CT operated, Lt, 3 phase, 4 wire - 01 No(f) LED type indicating lamp for phases and neutral |
| 4 | Supply install testing and commissioning in replacement of 22 KV outdoor type Polymer based gang operated air brake switch triple pole, suitable for verticle mounting complete with GI operating rod of suitable length for operating mechanism worked from ground level complete in both OFF and ON positions, for current rating upto 200 Amps,each pole consist of galvanised steel base HT insulators as per BSS/ISS non ferrous knife and spring loaded contacts, arcing horns of adequate section to brake magenetizing current of the transformers. All ferrous parts hot dipped galvanised and non ferrous parts heavelly tinned to withstand weather complete all as specified and directed. |
| 5 | Supply and Fixed in replcement of Polymer based dropout fuse unit complete set suitable and including for 22 KV, HT outdoor and dropout type of capacity 200 Amps including jumper connections with copper flexible designed jumper and testing and commissioning all as per the directions of Engr-in-charge. |
| 6 | Supply and Fix in repair of MCCB 4pole, 630 Amps, 50 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed. |
| 7 | Supply and Fix in repair of MCCB 4pole, 400 Amps, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed. |
| 8 | Supply and fix in repair of MCCB 4pole, 250 Amps, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed. |
| 9 | Suppl and fix in repair of MCCB 4pole, 200 Amps, 25 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed. |
| 10 | Supply and fix in repair of MCCB 4pole, 125 Amps, 25 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed. |
| 11 | Material and labour for service wire 2 core 6.0 sqmm PVC insulated unsheathed aluminium conductor cable 2x 6 sq mm including replacing the un serviceable cable complete all as specified and directed. |
| 12 | Material and labour for earthing in repairs complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level) with the top edges of plate not less than 1.5 mtrs below normal ground level connected to GI wire 4.0 mm dia by means of GI nuts, bolts check nuts and washers earth lead protected by 15 mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 of SSR part 1 and all as specified including testing on completion all as specified and directed. Notes : The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40 mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8 mm dia TMT bars @150 mm C/C both ways ,GI funnel with GI watering pipe 20 mm dia med grade ,wire mesh, protection pipe 40 mm dia GI pipe light grade for earth lead upto 7.50 m long complete. |
| 13 | Material and labour for Earthing in reapirs complete with hot dip galvanized steel pipe in pipe electrode, outer pipe 76 mm dia medium grade and inner pipe 32 mm dia including testing 3 mtr long and having 50x6 mm terminal on inner pipe to connect earthing strip with 14 mm dia holes for nut bolts. buried directly and vertically in ground with top edge at 30 cm below ground level after making bore hole of 100 mm dia and 3.3 mtr deep using suitable mechanical drilling machine (for drilling near the specified bldg) connected with galvanized steel earthing lead of 32 x 6 mm strip with minimum two Nos of GI nut, bolts and connected to test point from earthing pit. The electrode pipes should be filled with 2x 25 Kg bags of carbon based earthing compound. The compound shall be highly conductive, hygroscopic, non magnetic, non corrosive in nature and have best moisture retaining qualities! with ph value between 7-9, connected to the earthing test point, fiber reinforced plastic pit not less than 300x300 mm with pit cover, including necessary returning, filling and removal of extra soil complete all as specified and directed. |
| 14 | Material and labour for Earth contunity conductor or main earthing strip fixed to wall on recessed or burried in ground or drawn in conduit/pipe fixed to poles or any other indicated situation for loop earthing as required 25/4 mm size galvanised strip complete all as specified and directed. |
| 15 | Material and labour for Earth contunity conductor or main earthing lead fixed to wall on recessed or burried in ground or drawn in conduit/pipe fixed to poles or any other indicated situation for loop earthing as required 32x6 mm size galvanised strip complete all as specified and directed. |
| 16 | Material and labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed. |
| 17 | Supply and fixing in replacement Automatic Street Light Switch using NATURE SWITCH for automatic switching of Street Lights based on LUX level of Natural Light. The Sensor (Nature Switch) along with suitable Power Contactor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade special moulding compound conforming to IP54.The Contactor, MCB and Circuit Wiring should suitable enough to take load of 12 kW load equally distributed over 3-phase .Contactor Rating: 40.Amps (4-pole).MCB (single-pole) Rating: 40.Amps (3 nos.) |
| 18 | Supply, fixing, testing and commissioning of Automatic Power Factor Correction (APFC) Panel 120 KVAR in steps of (25 KVAR - 2 Nos,20 KVAR - 2 Nos ,10 KVAR - 02 Nos, 5 KVAR - 02 Nos) indoor type 16 gauage, Including MCCB 250 Amps, 4 pole with rupting capacity 36 KA -01 No (incoming) and providing suitable contactors, relays, micro processed based 8 stage APFC relay auto/manual mode with backup TP/SP MCBs on each capacitor banks, Ammeter, Voltmeter, Selector switch, CTs, duly internal wired with suitable size bus bar 3 phase and neutral. Capacitor panel shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels, nut, bolts, washers, etc and making connection with suitable size of XLPE LT cable and shallbe powder coated complete all as specified and directed. Make for Panel board CPRI approved, |
| 19 | Material and labour for disconnecting from existing main taking out from LT panal board for servicing & overhauling LT panel/ LT ACB panel of any make 400 to 1000 Amp, 50Hz 415V AC including taking out existing mechanism complete with servicing of operating machnism, testing of triping mechanism complete to make it funtioning smoothly and including replacement of unserviceable spares and fixing in its original postion with all connections and testing complete.Note : Spare parts are to be paid separetly under respective items here in after. |
| 20 | Supply only Following spare parts suitable LT ACB suitable 400A-1000 A Capacity.(a) Main isolating contact (Male and Female) jaw type complete inclubing fixing accessories |
| 21 | (b) Shunt Trip coil/ Closing coil 415 VAC suitable for 800 amps ACB |
| 22 | (c) Under voltage tripping divice (UVT) 415 volts |
| 23 | (d) Single phase CTS at rating 800/5A |
| 24 | Material and labour for in repair LT Panel/ Feeder piller of any size including Welding work if requied including door hinges, locking arrangemet and complete scraping to old paint and applying double coat synthetic paint over a coat of redoxide primer complete all as specified and directed. |
| 25 | Material and labour for Fault Finding of defective or short circuit unserviceable under Ground 1.1KV LT cable with mobile fault finding instrument and accessories, findout locating fault or place of short cicuit.Note: Contractor should include quoated rates without time limit up to fault finding. Please Enable Macros to View BoQ information |
| 26 | Material and labour for Fault Finding of defective or short circuit unserviceable under Ground 1.1KV LT cable with mobile fault finding instrument and accessories, findout locating fault or place of short cicuit.Note: Contractor should include quoated rates without time limit up to fault finding. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 08, 2026
11:30 IST
Tender Published
Tender notice published.
TodayAug 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 21 daysSep 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 28 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender