BOQ
| Sl. No. | Item Description |
| 1 | Supplying & drawing following sizes of FRLS PVC insulated copper conductor single core cable in / on the existing surface / recessed, PVC / steel conduit as reqd. |
| 2 | 3 x 1.5 Sq.mm.. |
| 3 | 3 x 4 Sq.mm.. |
| 4 | 3 x 6 Sq.mm.. |
| 5 | Supply and drawing steel armoured, XLPE insulated, PVC intersheathed copper conductor 3 core round cable 1100 volt grade as per IS 7098 (Part 1) 1988 Complete as required. |
| 6 | 3 core armoured 2.5 sq.mm |
| 7 | S & F metal box of following sizes ( nominal size ) on surface or recess with suitable size of 3 mm phenolic laminated sheet cover in the front I/c painting etc as reqd. |
| 8 | 250 mm x 300 mm x 100 mm deep |
| 9 | Supply and & fixing following modular switch/ socket on the existing modular plates & switch box including connection but excluding modular plate etc. as reqd. |
| 10 | 5/6 Amp one way switch |
| 11 | 15/16 Amp. one way switch |
| 12 | 3 Pin 5/6 Amp. socket outlet |
| 13 | 6 Pin 15/16 Amp. socket outlet. |
| 14 | S & F following size modular base and cover plate for following modular metal boxes etc as required. |
| 15 | 3 module |
| 16 | 4 module |
| 17 | Supply and fixing of 32 x 12.5 mm DLP mini- trunking white-system with independent cover etc. as required complete. |
| 18 | Supply and fixing of following accessories suitable for 32 mm x 12.5 mm size plastic trunking white system. |
| 19 | End cap |
| 20 | internal / external angle |
| 21 | changeable flat angle |
| 22 | flat junction |
| 23 | Supply and fixing of 32 x 20 mm DLP mini- trunking white-system with independent cover etc. as required complete. |
| 24 | Supply and fixing of following accessories suitable for 32 mm x 20 mm size plastic trunking white system. |
| 25 | End cap |
| 26 | internal / external angle |
| 27 | changeable flat angle |
| 28 | flat junction |
| 29 | Supply and fixing of 105 x 50 mm DLP trunking white-system but without cover and partition etc. as required complete. |
| 30 | Supply and fixing of following accessories suitable for 105 mm x 50 mm size plastic trunking white system. |
| 31 | 85 mm flexible cover |
| 32 | End cap |
| 33 | Internal angles- adjustable from 80°-100° |
| 34 | external angles- adjustable from 60°-120° |
| 35 | flat junction |
| 36 | flat angles |
| 37 | separation partitions |
| 38 | Joints for 85mm width cover |
| 39 | base joints |
| 40 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 41 | 6 way (4 + 18), Double door |
| 42 | 12 way (4 + 24), Double door |
| 43 | S & F MCB of following pole and rating 240/415 volts, 10kA, 'C' series in the existing MCB DB complete with connection, testing & commissioning etc as reqd. |
| 44 | Single Pole 6 amp to 32 amp |
| 45 | Single Pole & Neutral 6 amp to 32 amp |
| 46 | Supplying and fixing following rating and pole, 240/440 V, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 47 | 63 amp double pole RCCB |
| 48 | Supply, fixing, testing & commissioning MCB of following pole and rating 240/415 volts 'C' curve 10kA in the existing MCB DB complete as reqd. |
| 49 | Triple pole & Neutral 40 amp to 63 amp |
| 50 | Supply, fixing connecting & commissioning of 3 pin Plug top 16 Amp. as reqd. Anchor |
| 51 | LED Down lighter (SMD Type) (System lumen efficacy >135 lm/Watt)Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast/ Extruded aluminium Body including trim |
| 52 | 12 -15 watt |
| 53 | 18 watt |
| 54 | LED Down lighter (COB Type) (System lumen efficacy ≥ 120 < 135 lm/Watt)Supplying, installation, Testing & Commissioning of LED Recessed/ surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80 , UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing Complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast/ Extruded aluminium Body including trim with Aluminium Reflector |
| 55 | 12 -15 watt |
| 56 | LED Panel light 2x2 ft. (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K/ 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast /Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 57 | 36 watt |
| 58 | LED Batten light (System lumen efficacy >135 lm/Watt)Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS: 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI ≥80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 59 | 18-22 watt |
| 60 | LED Flood Light, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt)Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66, IK-10, CRI ≥70, under voltage and over voltage protection, EMI-EMC as per CISPR -15, lenses for beam angle 30 deg-120deg as per the application and the project requirement deg., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq. mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminium housing suchthat LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 61 | 50 watt |
| 62 | 150 watt |
| 63 | Supply,Installation,Testing and commissioning LED light fittings integrated (with lamps) including connection,nut bolts, washer and screw etc. after removing old complete and submitting the dismantle in store as required. |
| 64 | LED Bulkhead fitting 10 watt, 120 lm/W, IP65; |
| 65 | LED Foot Light in-recess, 7 watt, 3000K, IP 65 die casted aluminium powder coated; Make_Havells, model RECT 7 W 3000 K, cat_LHEOABP5I46H007 |
| 66 | LED Post Top Lantern 40 watt (Make_Crompton Cat.No.LPTO-40-CDL-M) |
| 67 | Supplying, Installation, Testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars/Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight (Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
| 68 | 1 Output per phase and suitable for single phase supply |
| 69 | Brush Less Direct Current (BLDC) Fan without RemoteSupply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req. |
| 70 | 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum) |
| 71 | Supply, Installation, testing and commissioning of exhaust fan of following sizes,1Ǿ AC power supply,50 Hz in the existing opening I/c connection, rag bolts complete as reqd. |
| 72 | 300mm |
| 73 | 380 mm |
| 74 | 450 mm |
| 75 | Supply and fixing of louver for exhaust fan of following sizes with rag bolts as reqd. |
| 76 | Supply, fixing, testing and commissioning wall fan, 400 mm dia,1Ǿ AC power supply,50 Hz complete as required. |
| 77 | Supplying and fixing capacitor of following rating suitable for ceiling fan / exhaust fan / air-curtain etc. |
| 78 | 2.5mfd |
| 79 | Dismantling and fixing/refixing of LED light fittings integrated (with lamps) including connection,nut bolts, washer and screw etc. after removing old complete as required. |
| 80 | Upto 3 Meter |
| 81 | Above 3 meter and upto 6 Meter |
| 82 | Above 6 meter and upto 9 Meter |
| 83 | Above 9 meter and upto 12 Meter |
| 84 | Locating fault in wiring rectifying removing & restoring supply the same & making good the damages etc as reqd. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender