Tender For Provision Of 2X100 Kva Ups For Glf Including Aicmc For 5 Years At Puducherry Airport.
Tender Value
93.65 Lakhs
Estimated cost
Bid Submission
28 Aug 2026
5 days left
EMD
2.80 Lakhs
Bank guarantee accepted
Document Fee
1180
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pondicherry → Puducherry
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of 2X100 Kva Ups For Glf Including Aicmc For 5 Years At Puducherry Airport.
BOQ
| Sl. No. | Item Description |
| 1 | SH I: SITC of UPS |
| 2 | 2x100 KVA Capacity, 3-phase input/3-phase output online UPS with Isolation Transformer and Battery Bank:Supply, Installation, Testing and Commissioning of 2x100KVA capacity, 3-phase input/3-phase output online UPS with double conversion type advance IGBT technology with suitable rated (min K-4 Rated) copper wound 120 KVA capacity isolation transformer at input of each UPS with MCCB and soft starter for parallel redundancy also to drive constant current regulators with 100% unbalanced load at full load condition. The UPS shall have built in 100% rated automatic static by pass, Manual by pass facilities for maintenance, active input power factor correction, phase sequence corrector, pure sine wave output, input/output isolation, compatibility with generator supply, cold start capability, EMI/RFI noise filter, advanced communication-RS232/RS 485 ports and user friendly LCD display and run in parallel redundant system configuration for equal sharing of load, battery management features integrated with main UPS controller, suitable to operate at 415V +/- 15%, 50Hz, 3 Phase supply and operating voltage range of 330V to 480V, suitable IP rated enclosure and capable to take 2 phase and single phase loads on 3 phase output of UPS with 100% unbalanced and necessary safety protections along with suitable size MCCB inside etc complete as required. |
| 3 | The job also includes supply, installation, testing and commissioning of Two battery bank sets of required/suitable size with required number of 12V VRLA SMF batteries suitable to give a backup time of minimum 30 minutes per each UPS along with battery racks/enclosure, suitable rated battery circuit breaker, interconnection between batteries as well as battery bank to UPS and interconnections between isolation transformer to UPS with suitable insulated copper conductors, connectors, glanding & terminations etc. complete as required. (Entire system shall be provided with 2 years Warranty) |
| 4 | SH-II Associated Electrical works |
| 5 | UPS Input panel:Design, Fabrication ,Assembling , Supply, Installation ,Testing and Commissioning of UPS Input panel (TTA Assembly), Indoor Cubical type, Floor mounted , free standing, dust & vermin proof conforming to IEC 61439 suitable for 415V, 3Ph, 4 wire ,50Hz AC supply system fabricated in compartmentalized design of Form 3B and Ingress protection of IP 42, made from CRCA sheet steel of 2mm thick for frame work and covers and 3mm thick for gland plates i/c cleaning and finishing complete as per OEM process for powder coating in approved shade, extendable type, DMC/SMC busbar supports , with bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, provision for cable entry from bottom of the panel and as per technical specification with all accessories. |
| 6 | Two No. of 250 A, 36 KA (ICu=ICs), 4P MCCB with Microprocessor Based Releases (L&T MTX 2.0 / Equivalent) for OC/SC/EF Protection and ROM as Incomers, Phase Indication Lamps, ON/OFF/TRIP Indication Lamps, Resin cast CT operated Digital Multifunction Meter (EM 6400 or Equivalent), Phase Barriers, Spreader Links etc., as required. |
| 7 | Two Nos. of Four Module Type 1+2 SURGE PROTECTION DEVICE (SPD), conforming to IEC – 61643, having 100KA 10/350 micro seconds neutral to earth, 50 KA 10/350 micro sec line to neutral, with limiting voltage less than 1.5 KV connected to Incoming Side of Incomers I and II. |
| 8 | One No. 250A, 36 KA, 4P MCCB with ROM and ON/OFF Indication Lamps as Buscoupler with Mechnical Interlock with Incomer I and II complete etc., as required. |
| 9 | 4 No. 250 A, 36 KA, 4P, MCCB with Microprocessor Based Releases (L&T MTX 2.0 / Equivalent) for OC/SC/EF Protection and ROM as Outgoings, ON/OFF/TRIP Indication Lamps, Resin cast CT operated Digital VAF meter etc., as required. |
| 10 | 4 Nos. of 63 A, 25 KA, 4P MCCB with TM Releases for OC/SC Protection and ROM as Outgoings, ON/OFF/TRIP Indication Lamps, Digital VAF Meter etc., as required. |
| 11 | One Set of 400 Amps Al. Bus Bars with at Par Neutral Bus Bars as required. |
| 12 | Copper Earth bar of size 25 x 5 mm for both vertical and horizontal run. |
| 13 | All connections between busbar and Switchgear & between Switchgear & terminal block with with suitable Buslinks for Outgoing switchgear rating > 100 Amps, all accessories such as fuses, MCBs, auxillary contactors, auxillary switches, spreader links & phase barriers for all outgoing MCCBs etc., complete as required. |
| 14 | All connections between busbar and Switchgear & between Switchgear & terminal block with with copper cable of 1.5 times switchgear rating for Outgoings (< 100 Amps), all accessories such as fuses, MCBs, auxillary contactors, auxillary switches, spreader links & phase barriers for all outgoing MCCBs etc., complete as required. |
| 15 | Total (2.01 to 2.10) |
| 16 | UPS Output panel:Design, Fabrication ,Assembling , Supply, Installation ,Testing and Commissioning of UPS Input panel (TTA Assembly), Indoor Cubical type, Floor mounted , free standing, dust & vermin proof conforming to IEC 61439 suitable for 415V, 3Ph, 4 wire, 50Hz AC supply system fabricated in compartmentalized design of Form 3B and Ingress protection of IP 42, made from CRCA sheet steel of 2mm thick for frame work and covers and 3mm thick for gland plates i/c cleaning and finishing complete as per OEM process for powder coating in approved shade, extendable type, DMC/SMC busbar supports , with bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, provision for cable entry from bottom of the panel and as per technical specification with all accessories. |
| 17 | Two No. of 250 A, 36 KA (ICu=ICs), 4P MCCB with Microprocessor Based Releases (L&T MTX 2.0 / Equivalent) for OC/SC/EF Protection and ROM as Incomers, Phase Indication Lamps, ON/OFF/TRIP Indication Lamps, Resin cast CT operated Digital Multifunction Meter (EM 6400 or Equivalent), Phase Barriers, Spreader Links etc., as required. |
| 18 | One No. 250A, 36 KA, 4P MCCB with ROM and ON/OFF Indication Lamps as Buscoupler with Mechnical Interlock with Incomer I and II complete etc., as required. |
| 19 | 4 No. 125 A, 25 KA, 4P, MCCB with TM Releases for OC/SC Protection and ROM as Outgoings, ON/OFF/TRIP Indication Lamps, Digital VAF Meter etc., as required. |
| 20 | 4 Nos. of 63 A, 25 KA, 4P MCCB with TM Releases for OC/SC Protection and ROM as Outgoings, ON/OFF/TRIP Indication Lamps, Digital VAF Meter etc., as required. |
| 21 | One Set of 400 Amps Al. Bus Bars with at Par Neutral Bus Bars as required. |
| 22 | Copper Earth bar of size 25 x 5 mm for both vertical and horizontal run. |
| 23 | All connections between busbar and Switchgear & between Switchgear & terminal block with with suitable Buslinks for Outgoing switchgear rating > 100 Amps, all accessories such as fuses, MCBs, auxillary contactors, auxillary switches, spreader links & phase barriers for all outgoing MCCBs etc., complete as required. |
| 24 | All connections between busbar and Switchgear & between Switchgear & terminal block with with copper cable of 1.5 times switchgear rating for Outgoings (< 100 Amps), all accessories such as fuses, MCBs, auxillary contactors, auxillary switches, spreader links & phase barriers for all outgoing MCCBs etc., complete as required. |
| 25 | Total (3.00 to 3.9) |
| 26 | Supply of following size of PVC/XLPE insulated PVC sheathed Copper conductor armoured power cable of 1.1 KV grade conforming to IS-7098 Part-I / IS 1554 Part 1 amended upto date etc. complete as required. |
| 27 | 3.5C x 95 sqmm |
| 28 | 3 core x 50 Sq.mm |
| 29 | Supplying and Making end termination with brass compression gland and Copper lugs for following PVC insulated and PVC sheathed / XLPE insulated 1.1KV grade cables as required. |
| 30 | 3.5C x 95 sqmm |
| 31 | 3 core x 50 Sq.mm |
| 32 | Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, indicator lamps and extension of buslinks etc., as required. |
| 33 | 125A, 36KA , 4pole MCCB |
| 34 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 5 kV grade of following size in the existing masonry open duct as required. a)Upto 35 sq. mm upto 95 Sqmm |
| 35 | Earthing with Copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 36 | Providing and fixing 25 mm X 5 mm Copper strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 37 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 38 | SH III: All Inclusive Comprehensive Maintenace contract (AICMC) except replacement of batteries after DLP |
| 39 | AICMC Cost except Provision of Batteries for 1st year after 2 years of DLP (3.09% of SITC cost i.e on item No.1) |
| 40 | AICMC Cost except Provision of Batteries for 2nd year after 2 years of DLP (10% Percentage increase on 1st Year AICMC)) |
| 41 | AICMC Cost except Provision of Batteries for 3rd year after 2 years of DLP (10% Percentage increase on 2nd Year AICMC)) |
| 42 | AICMC Cost except Provision of Batteries for 4th year after 2 years of DLP (10% Percentage increase on 3rd Year AICMC)) |
| 43 | AICMC Cost except Provision of Batteries for 5th year after 2 years of DLP (10% Percentage increase on 4th Year AICMC)) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysAug 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents