Tender For Construction Of 3.15Mva 33/11Kv Receiving Station At Rajgarh Distt. Ramban In Respect Of Std-Udh Ur Scheme Code : Pddss2627100651
Tender Overview
Project Description
Tender for Construction Of 3.15Mva 33/11Kv Receiving Station At Rajgarh Distt. Ramban In Respect Of Std-Udh Ur Scheme Code : Pddss2627100651
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-Aug-2026 | CorrigendumTechSpecs | Technical Bid | 27-Aug-2026 |
| 2 | 21-Aug-2026 | CorrigendumTechSpecs | Technical Bid | 05-Sep-2026 |
| 3 | 27-Aug-2026 | Extension Notice | Date | 05-Sep-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Survey, Supply, Installation , Testing and Commissioning for 33 kV Line BAY at Receiving Station Rajgarh |
| 2 | 33kV VCB (36KV,1250 A,26.2 KA, outdoor type Make Megawin, Crompton Greaves Pascal, Stelmec ,etc . |
| 3 | 33KV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter,Ammeter,Annunciation Windows with annunciation relays, 3-phase Trivectometer-5Amps DLMS Compliant with RS-485 Port |
| 4 | 33KV Isolator with earthing blade 36KV,1250Amp, Outdoor 3-Pole 25kA |
| 5 | 33KV Isolator without earthing blade 36KV,1250Amp, Outdoor 3-Pole 25kA |
| 6 | 33KV Current Transformer (33KV ,1-phase, multi ratio multi core outdoor 1 no per phase) |
| 7 | 33KV Voltage Transformer (33KV/110V,1-phase, multi core outdoor 1 no per phase) |
| 8 | 33KV Lightening Arrestor (30 kv,10kA, Station Class,ZnO,Polymer)gap less |
| 9 | 33KV Polymer Post Insulator 36kv,170kv Impulse, Creepage distance 1224mm |
| 10 | Control Cables |
| 11 | 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. a |
| 12 | ii) 4 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 13 | iii) 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 14 | Pipe Strcutures |
| 15 | Nominal Bore 200,5.9mm thick |
| 16 | Galvanised Steel Structures |
| 17 | Galvanised Nuts & Bolts |
| 18 | Conductor and Hardware |
| 19 | Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay) |
| 20 | Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat. |
| 21 | Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering |
| 22 | Survey, Supply, Installation , Testing and Commissioning for TRANSFORMER BAY at Receiving station Rajgarh |
| 23 | 33kV VCB (36KV,1250 A,26.2 KA, outdoor type Make Megawin, Crompton Greaves Pascal, Stelmec ,etc . |
| 24 | 33kv C&R Panel along with O/C, E/F relays , mimic diagram, Voltmeter, Ammeter, Annunciation windows with annunciation relays, 3-Phase Tri-Vector Smart meter- % amps, DLMS Compliant including earthing. Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 25 | 33KV Current Transformer (CTR 250/125-5A,1- phase multi-core, outdoor,1No. Per phase) on along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards. |
| 26 | 33 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m |
| 27 | 30KV Lightening Arrestors(30 kV 10 KA Polymer, ZnO, Gapless) |
| 28 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards. |
| 29 | 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc. |
| 30 | 4 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc. |
| 31 | 2 core 2.5mm2 Control Cable copper Armoured, 1.1KV Grade, ISI, FRLS of make Havells, Polycab, KEI etc. |
| 32 | Galvanised Pipe/ Steel Structures |
| 33 | Galvanised Nuts & Bolts |
| 34 | Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay+ One No Transformer Bay) |
| 35 | Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat. |
| 36 | Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering |
| 37 | Power Transformer |
| 38 | Transportation of 33/11KV 3.15MVA Power Transformer from Central store to Rajgarh Receiving station and its erection, testing and commissioning |
| 39 | 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 40 | 6 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 41 | 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 42 | SITC of 11 kV INDOOR SWITCHGEAR OF 33/11 kV SUBSTATION |
| 43 | 11 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Seimens, Megawin, Pascal, or equivalent :- including Smart meters Trivector. |
| 44 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (5Sets Station type 1 for Power Tx)) |
| 45 | 11 kV 3- Core XLPE 120 mm² armoured, FRLS |
| 46 | 11 kV 3- Core XLPE 400 mm² armoured, FRLS |
| 47 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 120 sqmm single core(Indoor) |
| 48 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 120 sqmm single core (outdoor ) |
| 49 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (indoor) |
| 50 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (outdoor) |
| 51 | 11 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch. |
| 52 | 11kV GO set , AB Switch 3-Phase, 3-Pole, 200 Amp |
| 53 | Galvanised iron of sorts |
| 54 | 09 Mtr. Long Pole(ST-410 SP33) |
| 55 | 120 mm² PVC LT Cable 4 Core, armoured, FRLS |
| 56 | Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole |
| 57 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip for ST poles |
| 58 | 100 kVA,11/0.433KV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) |
| 59 | Earthing of 63KVA substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 60 | MCCB 200 Amp with box |
| 61 | COMMON MISCELLENOUS WORKS |
| 62 | HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room |
| 63 | Providing & Laying of Earthmat by Using G.I. Flat of Size 50 mm x 8mm as grounding Conductor.The mesh Size shall 2 m x 2 m.The Burial Depth of G.I. Flat Shall be minimum 600 mm.The work involves the excavation of trenches for burial of grounding flat,Laying of G.I.Flat including welding & Backfilling of Trenches |
| 64 | Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip. |
| 65 | Supply, Errection, Testing & commisioning of Battery Bank 32v 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant of make Exide Amaron or Tata etc. |
| 66 | Supply, Errection, Testing & commisioning of Float-Cum-boost Charger with full wave rectification for 220v, 1 Phase 50HZ AC input supply suitable for charging of Battery Bank 32V, 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant. |
| 67 | Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories |
| 68 | Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A),Rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 69 | Fire Extingiusher Co₂ Type of 4.5 kg capacity for control room (with ISI mark) |
| 70 | 3 Sand Bucket Fire Extingiusher including MS stand |
| 71 | Civil /Misc Works |
| 72 | (Development of land) Earthfilling/Cutting upto desired FGL (As decieded by Engineer incharge during detailed Engineering)by Way of Removing Weeds,Wild Grass and endulation if any including disposal of surplus material |
| 73 | Earth work for construction of approach road in rough excavation, banking excavated earth in layers not exceeding 20 cm in depth, breaking clods, watering, rolling each layer with 1/2 tonne roller or wooden or steel rammers, and rolling every 3rd and top-most layer with power roller of minimum 8 tonnes and dressing up in embankments for roads, flood banks, marginal banks and guide banks or filling up ground depressions, lead upto 50 m andlift upto 1.5 m in all kinds of soil: |
| 74 | Providing and laying cement concrete in retaining walls/Drains 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 75 | Chainlink Fencing of 33 kV Yard of Substation by way of Mass Concrete in Foundations and chainlink fencing of 6 ft height |
| 76 | Providing & Fixing of double frame Gate(Min 4000 mm wide & 2000 m high) with 50 dia G.I.Tube in outer frame & 10mm/20 mm Sq rods welded to tubular frame (Final Design to be approved by Engineer incharge).There shall be provision of drop Bolts of 16 mm dia M.S. Rod & suitable Concrete Pockets for holding Bolts.Wheels at bottom & flat arrangement for smooth opening & closing shall be provided |
| 77 | Construction of R.C.C. Pillars for holding of gate including cost of material & labour.(Design of Reinforcement & sizing shall be finalised by Enginer incharge |
| 78 | RCC Cable trench (1:2:4) including excavation and disposal of un-wanted soil. for laying of 11 KV XLPE Power Cable and control cable from power transformer, VCB and other equipments to control room and for outgoing cables from control room to outgoing structures including cable duct covers (cable duct covers should be covered with Angle Frames using angle 45x45x5 mm and 8 mm Tar Steel @ 200 c/c & M-20 Concrete) |
| 79 | BUILDING: A. Control Room Buildingon ground floor complete with Column and Beam structures with 1 no J.E. Room , 1 Store room, 1 Battery Room and a main hall including aluminium windows, cable ducts for power and control cable, Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures)White Washing of entire building , painting of doors and windows etc. Overhead /undergroung water Storage tanks . 2 nos of office tables and 6 nos of chairs , staircase . Water Supply . Septic Tank complete with Sanitary Fittings including kota stone floor .complete in all respects |
| 80 | BUILDING:B .Staff Quarters on 1st floor with Column and Beam structures including Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures) White Washing of entire building Complete in all respectsainting of doors and windows etc. Overhead water Storage tanks . Pantry Room with all the Fittings. Water Supply . including marble flooring ,Furniture(including 2 single Beds, 4 Chairs, 2 table, Matress, Curtains)(Note: The Contractor shall submit the building drawing in all respects i.e. structral / architechural prepared by authorised Architect for approval from the dept for execution of works.) |
| 81 | 33/11 kV Power Transformer Foundation as per REC standards |
| 82 | Auxillary Transformer Foundation as per REC standards |
| 83 | 33 kV Equipment Foundation & Gantry foundation as per REC standards |
| 84 | 33 KV Yard Concreting with 1: 4 :8 with 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick. |
| 85 | 33 kV Yard Lighting with 6 nos 9 mtr ST poles each having 2 x 100 Wt LEDs street lights of reputed brand complete with earthing , cement bottoming GI brackets,cable etc . All the lights should be controlled from the control room with installation of control panel and having separate SPN for each light |
| 86 | Safety Tool kit |
| 87 | Crimping Tool Kit complete set for cable of different sizes upto 630 sqmm |
| 88 | Rubber Mats( 2 mtr x 2 mtr x 25 mm) |
| 89 | Conventional Earthing -GI Plate Earthing with 600mm X 600 mm X 6 mm, GI Plate, GI Flat 50 x 6 mm, GI Pipe, 40 mm Dia with Charcoal salt & good earth 10 ft deep pit etc. as per REC standards . Complete job |
| 90 | 33 KV Hand Gloves(set of 2) |
| 91 | 11 KV Hand Gloves(set of 2) |
| 92 | RainCoats |
| 93 | Safety Belt |
| 94 | Gum boots |
| 95 | Safety Helmet for electrician |
| 96 | Digital Meggar 5000 mega Ohm |
| 97 | Earth Resistance Tester |
| 98 | Emergency light/ Torch 5 Watt chargeable |
| 99 | Multimeter |
| 100 | 33KV high voltage live phase detector |
| 101 | Extendable Aluminium Ladder 25 feet |
| 102 | Aluminium Bus Bar 75 x 10 mm |
| 103 | GI Flat 50 x 6 mm and 20 x 5 mm for risers and earthing of cable trenches and yard fencing. |
| 104 | Earthing Rod (set of 3) |
| 105 | Multimeter |
| 106 | 33KV high voltage live phase detector |
| 107 | Extendable Aluminium Ladder 25 feet |
| 108 | Aluminium Bus Bar 75 x 10 mm |
| 109 | GI Flat 50 x 6 mm and 20 x 5 mm for risers and earthing of cable trenches and yard fencing. |
| 110 | Earthing Rod (set of 3) |
| 111 | Survey, Supply, Installation , Testing and Commissioning for ERECTION 33 KV LINE FOR PROVIDING POWER SUPPLY TO 33/11 KV RECEIVING STATION AT VILLAGE RAJGARH OF DISTT. RAMBAN.. |
| 112 | Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 113 | GI Channel iron X-arm of different sizes including clamps,Ties and braces for multi pole structures |
| 114 | GI Channel iron V cross-arm with top bracket of different sizes including clamps,Ties and braces for single pole structures |
| 115 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 116 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm (alongwith Dog fitting) |
| 117 | PG clamps for 100 mm2 ACSR Conductor |
| 118 | Galvinized Nuts and Bolts |
| 119 | Danger Plates with Clamps |
| 120 | Anti-Climbing Device with Clamps |
| 121 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 122 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 123 | Aluminium Joint sleeves |
| 124 | Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) including 5 No existing Poles |
| 125 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 126 | 100 mm2 ACSR conductor |
| 127 | Guard netting |
| 128 | Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 4 daysCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 4 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender