Public Administrative Department Local Bodies Closing in 8 days TDR #56890144

Tender for Tender for Work Of Installing Fire Hydrant System, Sprinkler And Fire Alarm System In Municipal Corporation Jaipur Headquarters Building.

Issued by Local Bodies · Jaipur, Rajasthan
Tender Value
1.17 Crore
Estimated cost
Bid Submission
17 Aug 2026
8 days left
EMD
2.35 Lakhs
Bank guarantee accepted
Document Fee
2360
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Work Of Installing Fire Hydrant System, Sprinkler And Fire Alarm System In Municipal Corporation Jaipur Headquarters Building.

BOQ

Name of Work:- uxj fuxe t;iqj eq[;ky; Hkou esa Qk;j gkbMsªV flLVe] fLaizdyj ,oa Qk;j vykeZ flLVe LFkkfir djus dk dk;ZA
Sl. No. Item Description
1Supply, Installation, Testing & Commissioning of: Single headed, SS ISI marked oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63mm dia instantaneous type female outlet complete with SS cap and G.I. chain, twist release type plug and all accessories as per 13:5290-1983 (Type 'A')
2Supply, Installation, Testing & Commissioning of: First-Aid Fire Hose Reel wall mounting swinging type complete with drum, bracket, ball valve and 20mm dia.x 30M long high pressure Hose Reel tubing as per IS:444 with Gun Metal shut-off nozzle having 5mm dia. orifice. The Hose Reel shall strictly confirm to IS : 884-1985
3Supply, Installation, Testing & Commissioning of: Non-percolating flexible hose (RRL type-'A') ISI marked (IS:636) 63 mm dia x 15 M long complete with instantaneous type SS/ Gun Metal 63 mm dia. IS marked Male and female couplings (IS:903) bound and riveted to hose pipe with Gun Metal rivets and 1.5 mm Gun Metal wire
4Supply, Installation, Testing & Commissioning of: SS/ Gun Metal 63mm dia short size branch pipes with 20 mm dia nozzle with 63mm instantaneous coupling ISI marked (IS: 903)
5Providing & fixing standard fireman's axe with heavy insulated rubber handle.
6Supply, Installation, Testing & Commissioning of Gun Metal Fire Brigade connection (Suction collecting head) consisting of 63 mm dia instantaneous type male coupling with built-in check valves and 150 mm dia. flanged outlet complete with bolts, nuts and rubber insertions as required as per IS:904-1983
74 - Way
8Supply, Installation, Testing & Commissioning of: Weather proof hose cabinets fabricated from 16 g M.S. Sheet with full glass door and locking arrangement, suitable to accommodate one Hydrant landing valve, 2 nos. 15 M long hose and 1 No branch pipe. The cabinet shall be painted with one coat of primer and finished stove enamelled \\"Fire Red\\", \\"Fire Hose\\" written on front including suitably mounted on a raised masonry platform as required. (Approx 0.75mx0.6 m x 0.25 m) (750 x 600 x 250 mm)
9Supply, Installation, Testing & Commissioning of: Air cushion tank (air-vessel) 450 mm dia. x 200 MM high with dished top, made of minimum 6 mm thick M.S. pipe/plate complete with 25 mm dia. Brass Air Valve (Ball valve, pressure gauge type), 25 mm dia. Stop with brass stop cock, nipple, tees, elbow, pipe and all accessories as required incl. fixing brackets.
10Supply, Installation, Testing & Commissioning of slim seal dual type non-return valves (PN 1.6) complete with matching flanges, rubber insertion, nuts, bolts and washer etc. of following sizes.
11150 mm dia
12Providing and fixing Slim seal Butterfly valves (PN 1.6) complete with matching flanges rubber insertion, nuts. bolts and washer etc. of following sizes
13150 mm dia nominal bore
14100 mm dia nominal bore
1580 mm dia nominal bore
16Supplying, Installation, Testing and Commissioning of orifice plate made of 6 mm thick stainless steel with orifice of required size in between flange & landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 kg/cm2 complete with rubber gasket, GI bolts, nuts, washers etc. as required.
17Providing and fixing Ball valve with hard chrome plated ball inside PTFE (Teflon) seat & ring with chrome plated centre handle with female BSP threads complete: in all respects.
1825 mm dia nominal bore
19Providing and fixing Mild Steel Pipe (IS: 1239 Part-1) heavy class including cutting, welding/serving etc. and providing all fittings viz. Flanges. Bends,Tees, Elbow, Reducers, Clamps. Hangers etc. including cutting holes and chases in brick or RCC walls/slabs and making good the same to the approval of engineer/consultant complete including painting with one coat of primer and two or more coats of enamel paint of approved make and shade including steel work.
20250 mm dia
21200 mm dia
22150 mm dia
23100 mm dia
2480 mm dia
25Providing, Fixing, Jointing, Testing & Commissioning of Heavy duty MS 'C' class (Heavy) pipe conforming to IS 3589 / 1239 part-I for hydrant and sprinkler applications in Existing trench with cement concrete block as supports including cutting, welding etc & forged steel fittings like elbows, tees, tapers, reducer with cleaning,wrapping and coating of the pipe with 4 mm thick tar based polymaric corrosion protection tape including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrosion complete in all respect. ( Pipe to be tested @ 10Kgf/Sqcm for 2 Hrs. & Excavation of Trench and refilling of trench to be paid extra). All as per pre approved by Engineer in-charge.
26200 mm dia, 6.0 mm thick
27150 mm dia
28100 mm dia
2980 mm dia
30Supplying, Installation, Testing & Commissioning of
31Electrical Driven fire fighting duty Terrace pump as per TAC and IS 12469-1988., Factory assembled in Pump make OEM suitable for automatic operation and consisting of following details given as A,B, C, D, E, F, G and H.
32a) Horizontal End suction Centrifugal Back pull type pump completefor delivery of below mentioned discharge and Head
33b) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal
34c) Squirrel cage induction motor (IE-3 Class) suitable for 3 phase, 415 V, 50 HZ, Ac supply , Class -F Insulation, Synchronous speed not Exceeding 3000 RPM, T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible (Love Joy type) coupling , coupling guard complete in all respect .
35d) Common bed plate fabricated from mild steel channel for installation of pump and Motor including anti vibration pads. (E) The Hydrostatic tests (2 times of design operating head or 1.5 times the shut off head whichever is higher) and performance tests (to determine developed head, Pump BHP and efficiency v/s Flow) of pumps along with trip test shall be carried out at manufacturer’s works in Virtual / Physical presence of Department’s representatives (F) Physical & Chemical Test reports of i) Pump casing (ii) Impeller (iii) Shaft (iv) Shaft sleeve and Dynamic Balance certificate is to be submitted by OEM (G) Suitable size Reinforced cement concreat (M-30) foundation with foundation bolt, Nozing Angle of size 40mm x40mm x5 mm ( Cost of RCC Foundation to be paid Extra ) (H) Weather proof hood fabricated from 5mm thick UV stablised FRP sheet supported by 50 mm x 50 mm x 5 mm Angle Iron fram above pumpset to protect it from weather All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR .900 LPM with 35 mtr head
36SUPPLY, INSTALLATION TESTING & COMMISSIONING OF:
37a) Electrical Motor Driven Automatic pressurisation (Jockey) pumping set consisting of the following as per specifications. Horizontally mounted centrifugal type single/multi-stage fire pump for building pressure loss due to any leakage in the system and capable to deliver approx 180 LPM against a total head of 70 M with all accessories pressure gauge etc. as required As per approved make
38b) Squirrel cage induction motor totally enclosed fan cooled type at 2900 RPM suitable for 415 Volts + 10% - 15% 3 phase. 50 HZ A.C. supply of suitable capacity for the above pump with synchronous speed of 1500/3000 RPM confirming to IS: 325 & duly coupled with above pump coupled with flexible coupling including earthling as per relevant Indian Standard and specifications.
39c) Common bed plate for mounting Pump and Motor fabricated of suitable M.S.Channel as per manufacturer's recommendations.
40d) Suitable RCC Pump foundations as per manufacturer's design 4 Nos Dunlop Anti-vibration (cushy foot) heavy duty mounting pads.
41Providing and fixing Ball valve with hard chrome plated ball inside PTFE (Teflon) seat & ring with chrome plated centre handle with female BSP threads complete: in all respects.
4250 mm dia nominal bore
43Supply, fixing, testing and commissioning in position the following Y - STRAINER in Pump Suction Water line complete with flanges etc as per specifications & drawings.
44150 mm dia MS pipes
45Providing and fixing resilient rubber neoprene lined single arch vibration eliminators suitable for raw water up to 450C temperature working pressure 7kg and test pressure 14 kg/ cm2.
46150 mm dia
47SITC of Pressure Switche of pressure range 3-15 Bar for Main, Jockey, Terrace pump and Diesel pumps Etc. as Required (Control Cable from Pressure switch to Panel to be Paid Extra).
48Providing & fixing Stainless Steel Pressure Gauge with dial of 150 mm Diameter size and range 0 to 16 kg/cm2 with 3/8\\" BSP bottom entry, Ball valve, SS Syphon Tube all fittings etc, duly calibrated before installation in MKS and FPS units, Accuracy Level +/- 1% including Making Drilling in Existing MS Pipe Etc. as required.
49Providing and fixing 20/25 mm dia. (PN - 1.6, Type-S1, Flanged, ISI marked) air release valve confirming to IS -4845 : 2000 with Double Flange isolating valve (pressure rating PN 1.6) complete with 1 no. Matching Flanges (Minimum 10 mm thick), nuts, bolts, washers, gaskets etc as required. All as per pre approved by Engineer in-charge.
50Providing and placing on terrace (at all floor levels) polyethylenewater storage tank ISI : 12701 marked with cover and suitablelocking arrangement and making necessary holes for inlet, outletand overflow pipes but without fittings and the base support for tank
51Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply including allCPVC plain & brass threaded fittings i/c fixing the pipe with clampsat 1.00 m spacing. This includes jointing of pipes & fittings with onestep CPVC solvent cement and testing of joints complete as perdirection of Engineer in-charge.
5215 mm nominal outer dia .Pipes.
5320 mm nominal outer dia .Pipes.
5425 mm nominal outer dia .Pipes.
5532 mm nominal outer dia .Pipes.
56Brick work with FPS bricks of class designation 75 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand)
57Cement plastering including T&P, scaffolding, material and complete labour, including cost of water, curing, racking of joints etc. with 12 mm cement plaster of mix : including Providing /mixing of synthetic fibers compulsorily complying with IS 16481:2022 of 06 mm/12 mm length to be mixed @ 0.25% by weight of Cement i.e. 125 gms per 50 kg Cement up to 900 gms per cum of Concrete/ mortar 1:6 (1 cement : 6 fine/ coarse sand)
58Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring, shuttering, finishing and reinforcement - All work upto plinth level 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size)
59Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.
60Fire Alarm System
61SITC of UL, ULC listed and FM approved (UL 864 listed, 10th Edition) 32-bit Microprocessor based Intelligent Addressable, Peer-to-Peer networkable, 2 loops, expandable up to 2-loop FACP (Fire Alarm Control Panel). FACP shall accommodate up to 2 nos. of 12V/50AH batteries in its own housing and shall have a battery charging capacity of (up to) 2 nos. of 12V/100 AH housed externally.
62Additional 2 Loop
63SITC of UL, ULC listed and FM approved Active Serial Repeater Panel with 80 ch. LCD display with supervised power supply from FACP. Repeater Panel shall monitor and control (Scroll, Acknowledge, Reset & Mute) all the events of the FACP to which it is connected and it shall have Port Vectoring / Event Filtering capability of showing only ALARMS, TROUBLES or SUPERVISORY or customized combinations of user selected events.
64SITC of UL, ULC listed and FM approved Intelligent Addressable Optical Smoke detector with base. The optical sensor element shall have multiple selectable sensitivity levels from 0.2% Obs/ft to 3.1% Obs/ft. The detector shall have operating temperature range from -9°C to 50°C and humidity tolerance range up to 95% RH, Non-Condensing.
65SITC of UL, ULC listed and FM approved Intelligent Addressable Rate of Rise cum Fixed Temperature Heat Detector along with base. Rate-of-Rise temperature detection element shall have two selectable settings of 8° C & 11° C (or closer to this value not deviating by 1°C) and Fixed temperature sensing shall be independent of rate-of-rise sensing and shall have two selectable settings of 57° C & 68°C (or closer to this value not deviating by 1°C). The detector shall have operating temperature range from 0°C to 50°C and humidity tolerance range up to 95% RH, Non-Condensing.
66SITC of UL, ULC listed and FM approved Intelligent Addressable Double Action Indoor Application Manual Pull Stations / Manual Call Points suitable for wall/column mounting. MCP shall have red coloured housing with molded, raised-letter operating instructions of contrast colour. The MCP shall latch mechanically upon operation and shall remain so until manually reset with its key by an authorized operator. The MCP shall have operating temperature range from 0°C to 50°C and humidity tolerance range up to 93% RH, Non-Condensing.(IP65 rated)
67SITC of UL, ULC listed and FM approved Addressable Notification Devices (Hooter with Strobe). Hooter with Strobe unit shall sit directly on addressable NAC (Notification Appliance Circuit) of FACP, fully supervised and powered from FACP. Hooter and Strobe elements of the combined unit shall have independent activation & deactivation criteria. Hooter shall stop at alarm \\"Acknowledge\\" and the Strobe shall stop at panel \\"Reset\\". The Hooter and Strobe element of Hooter cum Strobe combined unit shall be selected and triggered independently from FACP for performance check and maintenanace. Hooter with Strobe unit shall have provision to be tested by a hand-held field diagnostic tool in \\"Silent Mode\\" and \\"Full Operation Sound Mode\\".
68SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator with base for isolating shorted, dewired and loose circuits between two successive fault, isolators with automatic resetting arrangement etc. as required. All as per pre approved by Engineer in-charge.
69SITC of UL 10th edition / EN54 / VDS certified Addressable control (input/output) modules/ Relay Module for shutting down lifts, Hooters, AHU's, Acknoledgement of Sprinkler system with potential free contact monitoring Etc. as Required. All as per pre approved by Engineer in-charge.
70SITC of Response Indicators outside the rooms for getting fire indications of detectors installed above false ceiling area interconnecting to loop cable complete as required Please Enable Macros to View BoQ information
71SITC of Response Indicators outside the rooms for getting fire indications of detectors installed above false ceiling area interconnecting to loop cable complete as required Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56890144
AUTHORITY Local Bodies
TENDER VALUE 1.17 Crore
LAST DATE 17-08-2026
Authority
Authority Name Department Of Local Bodies
Work Description Tender for Work Of Installing Fire Hydrant System, Sprinkler And Fire Alarm System In Municipal Corporation Jaipur Headquarters Building.
Basic Detail
Tender No 18 EXECUTIVE ENGINEER HQ
Bidding Type Tender
Location
City Jaipur
State Rajasthan
Key Dates
Publish Date 07 Aug 2026
Submission Date 17 Aug 2026
Open Date 17 Aug 2026
Finance
Tender Value 1.17 Crore
Tender Fee 2360
EMD 2.35 Lakhs
Exemption Available
Document List
BOQ_1036211.xls
e8856efc-8652-4f96-a5b5-36d5bc46e32f.html
eproc18xenhq.pdf
Tendernotice_1 (31).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 17, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Aug 17, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_1036211.xls

html

e8856efc-8652-4f96-a5b5-36d5bc46e32f.html

pdf

eproc18xenhq.pdf

pdf

Tendernotice_1 (31).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender