Tender For Provn Of Earthing And Lightning Protection System (Lps) For Bldg No P-194 And Improvement Of Earthing And Unserviceable Cables/Lt Panels And Connected Items Of Instlns At Ratnuchak Mil Stn Under Ge Kaluchak.
Tender Value
43.17 Lakhs
Estimated cost
Bid Submission
27 Aug 2026
18 days left
EMD
86400
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kaluchak → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Earthing And Lightning Protection System (Lps) For Bldg No P-194 And Improvement Of Earthing And Unserviceable Cables/Lt Panels And Connected Items Of Instlns At Ratnuchak Mil Stn Under Ge Kaluchak.
BOQ
| Sl. No. | Item Description |
| 1 | S&F in repair Air termination, single pointed copper rod 12mm dia and 300mm long and fixed complete all as specified and as directed. |
| 2 | S&F Copper strip 32mm x 6mm fixed on suitable size porcelain insulator and screws/nuts/washers for extension of roof conductor or down conductor above ground on wall complete all as specified and directed. |
| 3 | S&F GI Pipe,Medium grade 32mm dia bore for installation of air termination rod all as required and directed. |
| 4 | S&F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed incl 3 nos. 8mm dia 25mm long hex.Head screw. complete all as specified and directed. |
| 5 | Supply, installation, testing and commissioning of chemical earthing system using 90x60cmx5mm copper earth plate as electrode and 50x6mm copper earth strip conductor in accordance with IS 3043 and IEEE 80 standards. Technical Specifications of Earthing electrode copper plate of size 900 mm (L) x 600 mm (W) x 5 mm (T), Copper Strip of 50 mm (Width) x 6 mm (Thickness), copper material of electrolytic copper, chemical compound of high conductive earthing, pit size of 1.2 M (L) x 0.9 M (W) x 1.5 M (D), earthing resistance is below 5 ohms, chemical earthing compound, charcoal/bricks bats, water, clamps, bolts and nuts, earthing lead etc all as specified and directed. |
| 6 | Supply, installation, testing and commissioning of chemical earthing system using 90x60cmx5mm copper earth plate as electrode and 32x 6mm copper earth strip conductor in accordance with IS 3043 and IEEE 80 standards. Technical Specifications of Earthing electrode copper plate of size 900 mm (L) x 600 mm (W) x 5 mm (T), Copper Strip of 32 mm (Width) x 6 mm (Thickness), copper material of electrolytic copper, chemical compound of high conductive earthing, pit size of 1.2 M (L) x 0.9 M (W) x 1.5 M (D), earthing resistance is below 5 ohms, chemical earthing compound, charcoal/bricks bats, water, clamps, bolts and nuts, earthing lead etc all as specified and directed. |
| 7 | M&L Earthing in replacement complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed and testing on completion. |
| 8 | M&L Earthing in replacement complete with copper earth plate 60cmx60cmx3.15mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using copper strip 20 x 3 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, copper earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed and testing on completion. |
| 9 | M&L under ground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armored, electric power cable (heavy duty) with aluminium conductor, 1100 volts (earthed) grade cross sectional area 400 sqmm, 3.5 core laid in trenches/ pipes/ ducts/ wall/ boarings with necessary cable lugs and glands, nuts, bolts and washers etc and testing including disconnecting and taking out of existing LT cable of any type and size complete all as specified and directed.Note:-Excavation and earth, sand coushioning and protection for cable work shall be measured and paid separately. |
| 10 | All as per item No. 09 here-in-before but cross-sectional area 240 sqmm, 3.5 core complete all as specified and directed. |
| 11 | All as per item No. 09 here-in-before but cross-sectional area 185 sqmm, 3.5 core complete all as specified and directed. |
| 12 | All as per item No. 09 here-in-before but cross-sectional area 95 sqmm, 3.5 core complete all as specified and directed. |
| 13 | All as per item No. 09 here-in-before but cross-sectional area 70 sqmm, 3.5 core complete all as specified and directed. |
| 14 | All as per item No. 09 here-in-before but cross-sectional area 50 sqmm, 3.5 core complete all as specified and directed. |
| 15 | Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth; for trench of cable/foundation of pole and stay etc and getting out in Soft/loose soil complete all as specified and as directed. |
| 16 | Material and labour for sand cushioning for protection of underground cable consolidated and compacted with clean dry sand all as specified and as directed (Compacted thickness shall only be measured and paid) |
| 17 | Material and labour for well burnt bricks,Sub class 'B' bricks, best quality locally available laid flat, dry in trenches for cable protection complete all as specified and as directed |
| 18 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in Soft/loose soil complete all as specified and as directed |
| 19 | Removing excavated material to a distance n.exc 50 mtr and depositing where directed at level n.exc 1.5 mtr above the starting point all as specified and as directed. |
| 20 | M&L for GI pipe 100 mm dia \\"light grade\\" ISI marked, laid in trenches/ on floors/on, pole/road for cable protection including necessary joints / fittings including taking up / down and removing old unserviceable GI pipe complete all as specified and directed . |
| 21 | All as per Srl item No 20 here-in-before but 80mm dia complete all as specified and directed. |
| 22 | All as per Srl item No 20 here-in-before but 50mm dia complete all as specified and directed. |
| 23 | All as per Srl item No 20 here-in-before but 40mm dia complete all as specified and directed. |
| 24 | M&L for Cutting/Boring of road/Hard standing to a size of 30 cm in width and not exceeding 90 cm in depth for laying of protection pipe/water line/Cable including returning filling, Including spreading and providing PCC in 1:2:4 B1 using 20 mm grade stone aggregate for the top 100mm layer, complete all as specified and directed. |
| 25 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick exept inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 500 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 400 Amps 4 pole 36 KA - 01 No (Incomer)(b) MCCB fixed thermal and fixed magnetic100 Amps 4 pole 16 KA - 01No (Outgoing)(c)MCCB fixed thermal and fixed magnetic 63 Amps 4 pole 16 KA - 05 Nos (Outgoing - 04 Nos & Spare-01)(d) R,Y,B Indicators -01 Set(e) Digital Multifunction meter incl necessary CTs (set of three) - 1 set |
| 26 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick except inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 500 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 320 Amps 4 pole 36 KA - 01 No (Incomer)(b) MCCB fixed thermal and fixed magnetic125 Amps 4 pole 18 KA - 03 Nos (Outgoing)(c)MCCB fixed thermal and fixed magnetic 63 Amps 4 pole 16 KA - 02 Nos (Outgoing - 01 & Spare-01)(d) R,Y,B Indicators -01 Set(e) Digital Multifunction meter incl necessary CTs (set of three) - 1 set |
| 27 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick exept inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 600 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 400 Amps 4 pole 36 KA - 01 No (Incomer)(b) MCCB fixed thermal and fixed magnetic100 Amps 4 pole 18 KA - 02 Nos (Outgoing)(c)MCCB fixed thermal and fixed magnetic 63 Amps 4 pole 16 KA - 03 Nos (Outgoing - 02 & Spare-01)(d) R,Y,B Indicators -01 Set(e) Digital Multifunction meter incl necessary CTs (set of three) - 1 set |
| 28 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick exept inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 600 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 400 Amps 4 pole 36 KA - 01 No (Incomer)(b) MCCB fixed thermal and fixed magnetic 250 Amps 4 pole 36KA - 02 Nos (Outgoing -01 & Spare - 01))(c)MCCB fixed thermal and fixed magnetic 63 Amps 4 pole 18 KA - 02 Nos (Outgoing - 01 & Spare-01)(d) R,Y,B Indicators -01 Set(e) Digital Multifunction meter incl necessary CTs (set of three) - 1 set |
| 29 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick exept inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 600 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 320 Amps 4 pole 36 KA - 01 No (Incomer)(b) MCCB fixed thermal and fixed magnetic 200 Amps 4 pole 36 KA - 01No (Outgoing -01)(c) MCCB fixed thermal and fixed magnetic 100 Amps 4 pole 18 KA - 02 Nos (Outgoing - 01 & Spare-01)(d) R,Y,B Indicators -01 Set(e) Digital Multifunction meter incl necessary CTs (set of three) - 1 set |
| 30 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick exept inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 600 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 400 Amps 4 pole 36 KA - 01 No (Incomer)(b)MCCB fixed thermal and fixed magnetic 200 Amps 4 pole 36 KA - 02 Nos (Outgoing)(c) MCCB fixed thermal and fixed magnetic 125 Amps 4 pole 18 KA - 01 No (Outgoing)(d) MCCB fixed thermal and fixed magnetic 63 Amps 4 pole 18 KA-03 Nos (Outgoing-02 Nos & Spare-01) (e) R,Y,B Indicators -01 Set(f) Digital Multifunction meter incl necessary CTs (set of three) - 1 set |
| 31 | S&F for LT panel cubical type of suitable size, 415 volt, factory made CPRI approved dust proof vermin proof (Kiosik type) for outdoor use made out of CRCA sheet 3.15 mm thick exept inner sheath OG 2 mm powder coated, machine pressed, both side opening in two halves with provision of rubber beading and locking system, inciuding aluminium bus bar of 600 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers each MCCB/ cubical switch shall have be independent opening, panel should be monthed on angle iron frame and legs (vertcal height of legs not less than 30 cm exept in PCC) made from angle of size 50x50x5 mm, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer legs grouted in PCC(1:3:6) type B-2(using 40 mm graded stone aggregate) complete including all connection/ control wiring with suitable size of copper conductor cable, including danger notice sticker, comprising the following accessory including testing complete all as specified and directed.(a)MCCB microprocessor based 320 Amps 4 pole 36 KA - 01 No (Incomer)(b)MCCB fixed thermal and fixed magnetic 125 Amps 4 pole 18 KA - 03 Nos (Outgoing-02 Nos & Spare-01)(c) MCCB fixed thermal and fixed magnetic 63 Amps 4 pole 18 KA-02 Nos (Outgoing-01 No & Spare-01) (d) R,Y,B Indicators -01 Set(e) Digital Multifunction meter incl necessary CTs (set of three) - 1 set Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysAug 29, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender