Tender For Provision Of Various Capacity Ups For Various Locations At Bathinda Mil Station Under Ge (Utility) Bathinda
Tender Value
24.75 Lakhs
Estimated cost
Bid Submission
29 Aug 2026
21 days left
EMD
49500
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bathinda → Punjab
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Various Capacity Ups For Various Locations At Bathinda Mil Station Under Ge (Utility) Bathinda
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installations, testing and commissioning of 30 KVA 3 Phase online UPS with SMF battery for 30 Minutes backup time with all necessary accessories required for connection of UPS complete and specification are following: -1. Rating: - 30KVA/27KW2. Output power factor: 0.93. Topology: True online double conversion, transformer free4. Rectifier/Inverter Bridge: IGBT based5. Parallel configuration: Up to 10 units in parallel configuration6. Nominal input voltage; 3 × 380 V / 220 V + N, 3 × 400 V / 230 V + N, 3 × 415 V / 240 V + N7. Voltage tolerance: For loads < 100 % (–10%, +15 %), < 80 % (–20 %, +15 %), < 60 % (–30 %, +15 %)8.Input distortion (THDi): ≤ 4% at 100% load9.Input Frequency, tolerance: 50Hz/60Hz, -30% to +40%10. Input PF: 0.99 at 100 % load11. Rated short-time withstand current 10 kA for 1.5sec12. Automatic input phase reverse correction: Inbuilt13. Rated output voltage: 3 × 380 V / 220 V + N, 3 × 400 V / 230 V + N, 3 × 415 V / 240 V + N |
| 2 | 14. Voltage tolerance; < +/- 1% (static), < +/- 4% Dynamic (Step load 0%-100% or 100%-0%)15. Voltage distortion: < 2 % linear load, < 4 % non-linear load (IEC / EN62040-3)16. Frequency: 50 or 60 Hz17. Frequency tolerance: Synchronized with mains < +/- 2 % or (selectable for bypass operation) < +/- 4 % Free running +/- 0.1 %18. Overload capability: 10 min.: 110% or 1 min.: 135% (at cos phi 1)19. Permissible unbalanced load: 100 % (all 3 phases regulated independently)20. Crest factor 3:121 Overall efficiency95% at 75% to 100% load; 95.5% at 25% to 50% load22 Eco-Mode efficiency at 100% load 99%23 Phase Angle Tolerance (With 100% Unbalanced load) +/- 0 deg.24 Bypass operation +/- 10 %25 Output short capability (RMS) for 40 ms 2.1 x In26 Fault clearing capability current (RMS) on static-bypass for 10 ms approx. 10 x output rated current (In) (RMS) |
| 3 | 27 Max slew-rate 1 Hz/sec28 Storage temperature –25 to +55 °C29 Operating temperature 0 to 40 °C30 Max. altitude (above sea level) 1000m (3300ft) without de-rating31 Audible Noise with 100% / 50% Load 85 dBA at 1m32 Degree of protection IP 2033 Pollution Degree 234 Relative Air-humidity Max. 95% (non-condensing)35 Battery backup 30 mins36 Battery type 12V SMF, Flexible battery configuration 37 Maximum discharge current as per manufacturer standard38 Maximum Battery Charger Current As per manufacturer standard39 End of discharge voltage 1.75V/cell |
| 4 | 40 Battery Charging Curve Ripple free; IU (DIN 41773)41 Temperature compensation charging Required42 Battery Test Automatic and periodically (adjustable)43 LCD display Measurements Battery Runtime, Output Frequency, Voltage & Current, Output Frequency, Output Power, Active Power, Reactive Power, Apparent Power, Bypass Voltage, Bypass Frequency, Rectifier Voltage, Battery Temperature, Discharge Current, Charge Current, DC Voltage, Run Time (MIN) & Capacity (%)44 Set Up User Language, Date & time, Battery test, operation with Gen-Set & Password, command transfer load to inverter, transfer load to bypass |
| 5 | 45 Event Log Screen1. Logging Control; a log of the last 99 events is stored in the Power Management Display.2. All events and alarms are indicated with their date and time of appearance.3. Every stored event is identified with a sequential number and time stamp46 Indicator Status - AlarmOFF - No alarm conditionsRED - Alarm condition47 Line 1 GREEN - Mains rectifier available RED - Mains rectifier not available48 Line 2 GREEN - Mains bypass available RED - Mains bypass not OK or not available OFF - UPS is turned off49 Bypass GREEN - Load on bypass (Bypass- or Eco-Mode) OFF - Bypass not operating (switched off)50 inverter GREEN - Load on inverter RED - Inverter fault or load not transferable to inverter OFF - Inverter not operating (switched off)51 Battery OFF - UPS is turned off GREEN- Battery connected and OK RED - Fault condition of the battery (alarm)Flashing GREEN - Battery in discharge Flashing RED - battery low or disconnected Please Enable Macros to View BoQ information |
| 6 | 45 Event Log Screen1. Logging Control; a log of the last 99 events is stored in the Power Management Display.2. All events and alarms are indicated with their date and time of appearance.3. Every stored event is identified with a sequential number and time stamp46 Indicator Status - AlarmOFF - No alarm conditionsRED - Alarm condition47 Line 1 GREEN - Mains rectifier available RED - Mains rectifier not available48 Line 2 GREEN - Mains bypass available RED - Mains bypass not OK or not available OFF - UPS is turned off49 Bypass GREEN - Load on bypass (Bypass- or Eco-Mode) OFF - Bypass not operating (switched off)50 inverter GREEN - Load on inverter RED - Inverter fault or load not transferable to inverter OFF - Inverter not operating (switched off)51 Battery OFF - UPS is turned off GREEN- Battery connected and OK RED - Fault condition of the battery (alarm)Flashing GREEN - Battery in discharge Flashing RED - battery low or disconnected Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 21 daysAug 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓