Tender For Supply, Installation, Testing and Commissioning & Upgradation Of 11Kv Feeder Lines Near Receiving Station And Electric Sub-Stations At Skims Soura
Tender Value
1.98 Crore
Estimated cost
Bid Submission
29 Aug 2026
0 days left
EMD
3.96 Lakhs
Bank guarantee accepted
Document Fee
10000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Srinagar → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Supply, Installation, Testing and Commissioning & Upgradation Of 11Kv Feeder Lines Near Receiving Station And Electric Sub-Stations At Skims Soura
BOQ
| Sl. No. | Item Description |
| 1 | VCB Panel |
| 2 | Supply, Installation, testing & commisioning of 11 kV, (2 + 6), VCB Panel Board(Detailed Specifications specified in Annexure - V of the Tender document) |
| 3 | Supply, Installation, testing & commisioning of 11 kV Bus Coupler with Adaptor Panel |
| 4 | Supply, Installation, testing & commisioning of 11kV, Gapless Surge Arrestor,9 kV ,10 kA ,LA with Polymer housing, Stn. Type (10 Sets) |
| 5 | Supply, Installation, testing & commisioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch |
| 6 | Supply, laying, testing & commisioning of 11 kV, 400 mm², 3-Core, Armoured, XLPE Cable (with one spare length), FRLS |
| 7 | Supply, laying, testing & commisioning of 11 kV, 50 mm², 3-Core, Armoured, XLPE Cable (with one spare length), FRLS |
| 8 | Supply, Installation, testing & commisioning of 11 kV Heat Shrinkable Cable Termination Kit for incoming Cable |
| 9 | a) 11 kV Indoor Heat Shrinkable Cable Termination Kit |
| 10 | b) 11 kV Outdoor Heat Shrinkable Cable Termination Kits |
| 11 | Supply, Installation, testing & commisioning of 11 kV Outdoor Heat Shrinkable Cable Termination Kit |
| 12 | a) 11 kV Indoor Heat Shrinkable Cable Termination Kit |
| 13 | b) 11 kV Outdoor Heat Shrinkable Cable Termination Kit |
| 14 | Supply, Installation, testing & commisioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch |
| 15 | Providing and erection of 11 Mtr. Long Pole (ST-410 SP56) with Base Plate and Top Cap cover confirming to IS 2713 with up to date amendments |
| 16 | Providing and fixing of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 17 | Providing and fixing of Galvanised iron of sorts |
| 18 | Cement bottoming 1:2:4 mix as per Standards 0.70 cum / Pole |
| 19 | Earthing with copper earth plate 600 mm × 600 mm × 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal coke and salt as required. The Job includes providing, laying and fixing of 25 × 5 mm Copper strip to be laid from the earth plate (gas-welded with the plate) upto a height of 300 mm above the ground level. |
| 20 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25×3mm |
| 21 | Providing and applying Red Oxide |
| 22 | Providing and applying Aluminium Paint |
| 23 | Providing and fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting |
| 24 | Providing and fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 25 | Providing and fixing of GI Channel/Angle/Flat of sizes including clamps for L.A Set/G.O Set/Horn Gap |
| 26 | Providing and fixing of Galvanized Nuts and Bolts. |
| 27 | Providing and fixing of GI V cross-arm with top Bracket including clamp |
| 28 | Underground 11kV Line |
| 29 | Making Road cut in macadamised/bituminous surface for laying of utility services, including dismantling of existing pavement, excavation up to 1.0 m depth, upto 1.2m width, refilling with available excavated material in layers, watering, ramming, consolidation, and restoration of pavement crust including WBM/WMM base and 50 mm thick macadamised surface to original condition, excluding the cost of pipes but including cost of labour, T&P, carriage of materials, disposal of surplus material, and clearance of site and all incidental charges complete. |
| 30 | Making road cut in tile-paved footpath for laying of utility services, including careful dismantling of tiles, excavation up to 1.0 m depth, upto 1.2m width, refilling with suitable material in layers, compaction, and restoration of footpath including sub-base and re-laying of tiles to original pattern, excluding the cost of pipes but including cost of tiles (if damaged), bedding mortar, carriage, labour, and clearance of site and all incidental charges complete. |
| 31 | Making road cut in turfed footpath/earthen berm for laying of utility services, including removal of turf, excavation up to 1.0 m depth, upto 1.2m width, refilling with excavated earth in layers, compaction, dressing, and restoration of surface to original condition, complete, excluding the cost of pipes but including labour, carriage, and clearance of site and all incidental charges complete. |
| 32 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part ll complete with fitting and cutting, jointing etc.direct in ground (>450 mm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc.,complete as required. |
| 33 | 300 mm dia (OD-300 mm & ID-255 mm nominal) |
| 34 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size),complete as per standard design including. excavation, reinforcement, shuttering, finishing and all allied items required for complete job including making the site good after completion of work as directed by engineer in charge.Inside size 90x80 cm and 60 cm deep including C.I. cover with frame (Medium /Heavy duty) as per requirement at site. |
| 35 | 11kV Cable |
| 36 | Supply, laying, testing & commisioning of 11 kV, 400 mm², Single Core, Armoured, XLPE Cable, FRLS |
| 37 | Supply, Installation, testing & commisioning of 11 kV Heat Shrinkable Cable Termination Kit for incoming Cable |
| 38 | Supply, Installation, testing & commisioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch |
| 39 | Providing and erection of 11 Mtr. Long Pole (ST-410 SP56) with Base Plate and Top Cap cover confirming to IS 2713 with up to date amendments |
| 40 | Providing and fixing of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 41 | Cement bottoming 1:2:4 mix as per Standards 0.70 cum / Pole |
| 42 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm |
| 43 | Providing and fixing of 11 kV Gapless Surge Arrestor, 9 kV, 10 kA, LA with polymer housing, Stn. Type |
| 44 | Providing and fixing of Galvanized Nuts and Bolts. |
| 45 | Providing and laying of 100 mm² ACSR Conductor (Dog) |
| 46 | Providing and fixing of GI Barbed Wire for Anti Climbing |
| 47 | Sundry items like Aluminium lugs, Jumpers, binding Tape |
| 48 | Supplying and erection of stay set complete (galvanised) with 12/90 mm dia. × 1.8 m long stay rod, anchor Plate of size 45cm x 45cm x7.5mm, thimble, stay clamps, turn buckle (20mm x 60cm), 7/4.00mm dia GI Stay wire and strain Insulator etc. in Cement concrete 1:3:6 (1 Cement, 3 coarse Sand, 6 graded stone aggregate 40mm nominal size) foundation including excavation and re-filling etc., as required. |
| 49 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection / terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 50 | Upgradation of 11kV Feeder |
| 51 | Providing and erection of 11 Mtr. Long Pole (ST-410 SP56) with Base Plate and Top Cap cover confirming to IS 2713 with up to date amendments |
| 52 | Providing and fixing of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 53 | Providing and fixing of Galvanised iron of sorts |
| 54 | Cement bottoming 1:2:4 mix as per Standards 0.70 cum / Pole |
| 55 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm |
| 56 | Providing and fixing of 11 kV Gapless Surge Arrestor, 9 kV, 10 kA, LA with polymer housing, Stn. Type |
| 57 | Providing and fixing of Galvanized Nuts and Bolts. |
| 58 | Providing and laying of 100 mm² ACSR Conductor (Dog) |
| 59 | Providing and fixing of GI Barbed Wire for Anti Climbing |
| 60 | Providing and fixing of GI V cross-arm with top Bracket including clamp |
| 61 | Providing and fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting |
| 62 | Providing and fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 63 | Supply, Installation, testing & commisioning of 11 kV Isolator, Double Break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 29, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
TodayAug 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender