Defence Statutory Bodies & Commissions/Committees Closing in 17 days TDR #56869093

Tender For Repair Replacement Of Security Lights, Poles, Timers, Switches, Cables And Various Stp Related Maintenance Wks Under Md And Otm Accn Of Phase-I (Rupa, Gachham, Birpur, Dp, Bomdila And Dahung) With Allied Em Worksatgetanga

Issued by Statutory Bodies & Commissions/Committees · kameng, Arunachal Pradesh
Tender Value
79 Lakhs
Estimated cost
Bid Submission
03 Sep 2026
17 days left
EMD
1.43 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
kameng → Arunachal Pradesh
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair Replacement Of Security Lights, Poles, Timers, Switches, Cables And Various Stp Related Maintenance Wks Under Md And Otm Accn Of Phase-I (Rupa, Gachham, Birpur, Dp, Bomdila And Dahung) With Allied Em Worksatgetanga

BOQ

Name of Work:-
Sl. No. Item Description
1Supply, laying & testing in repalcement cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100V grade with stranded aluminium conductor of size 16 sqmm 4 core including taking down of old unserviceable UG cable/service wire complete all as specified and as directed.Note : Earth work, sand filling & PCC cover laying shall be measured and paid separately
2Description all as per item No 1 above but of size 16 Sqmm 2 core complete all as specified and as directed.
3Description all as per item No 1 above but of size 10 Sqmm 2 core complete all as specified and as directed.
4Laying only in repalcement cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 1100V grade with stranded aluminium conductor of different sizes including taking down of old unserviceable UG cable/service wires complete all as specified and as directed.Note : (i) LT XLPE Cable will be issued from MES Store.(ii) Earth work, sand filling & PCC cover laying shall be measured and paid separately.
5Supply and laying galvanised tube light grade ISI marked of size 40 mm dia incl all fittings in trenches/fixed on pole/wall/floor or laid in position complete all as specified and as directed.
6M & L for road cutting incl necessary excavation 45 cm wide and 90 cm in depth as in trenches in any type of soils/rock for laying LT UG cable through pipe after laying /through the cable trenches will be filling top with M&L PCC (1:3:6) type C-1 using 20 mm grdaeds stone aggregates from top over 15 cm thick hard good of broken boulders , 63 mm gauge over 15 cm bolders 100 mm dia over filled and rammed earth to make good the disburbed surface etc complete all as specified and as directed.
7Supply and laying HDPE pipe PN10, ISI marked, for cable protection on pole/wall/floor or in trenches and drain/culvert etc complete with necessary clamps, nuts, bolts, washers sockets complete with all fitting of size 50 mm bore complete all as specified and as directed. by Engineer-in-charge.
8S&F in replacement Junction box for luminaires ,weather proof made out of HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole mounting type comprising of four pole copper connectors of 16 Amps capacity with 6 Amp MCB single pole , of minimum size (300 x 200 x 105 mm), fixed on pole with MS, clamps (30 x 5 mm) with necessary nuts, washer and incl applying two coats of synthetic enamel paint over a red oxide primer on steel surface/clamps complete all as specified and as directed.
9S & F in replacement of GI brackets for fixing LED street light fitting fabricated out of GI tubing 32 mm dia, medium grade, 1.2 mtr long , bend to 120 degree shape by cutting, welding and well finishing including MS clamp of flat iron of size (32 x 4 mm) -02 Nos complete for steel poles as per site requirement with nut, bolt & washers for fixing of GI bracket complete all as specified and as directed.
10M&L for replacement of new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 35 watt complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including taking down of old unserviceable street light any type/any capacity complete all as specified and as directed.
11M&L for replacement of new generation energy saving and environmental friendly long life LED street light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 45 watt complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including taking down of old unserviceable street light any type/any capacity complete all as specified and as directed.
12Description all as per item No 10 above but of capacity 60 Watt complete all as specified and as directed.
13Description all as per item No 10 above but of capacity 90 Watt complete all as specified and as directed.
14M&L for replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 70 watt complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including taking down of old unserviceable street light any type/any capacity complete all as specified and as directed.
15Description all as per item No 13 above but of capacity 120 Watt complete all as specified and as directed.
16Description all as per item No 13 above but of capacity 200 Watt complete all as specified and as directed.
17Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-31) 9 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with two coats of aluminium paint over one coat of red oxide primer and incl taking down existing old unserviceable poles complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) complete all as specified and as directed.Note :- Excavation incl earth work and PCC foundation will be measured and paid separately.
18M& L for cable 1.5 sqmm 3 core PVC insulated multistranded copper cable with PVC insulated copper conductor with PVC cover for connection between Junction box and street light with all as spd complete all as specified and as directed.
19Supply , fixing and testing of Street light Panel including 3 phase automatic street light switch using integrated sensor based NATURE SWITCH for automatic switching of street lights .The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof , termite proof and FR graded SMC junction box conforming of IP 54 degree of ingress three phase 12 KW lightning load capacity including mounting bracket , cable glands, openable doors with lock complete all as specified and as directed. The contactor MCB and circuit wiring should suitable enough to take load of 12 KW equally distributed over three phase and street light timer should be comprising of following:- (a). Input MCB (3 Nos) rating 63 Amps (b).Contactor MCB (3 Nos) rating 63 Amps (c).Out put MCB (3 Nos) rating 63 Amps (d).Three phase circuit wiring with multistranded copper wire.
20Supply, fixing and testing of Street light Panel of single phase automatic street light switch using integrated sensor based NATURE SWITCH for automatic switching of street lights . The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof , termite proof and FR graded SMC junction box conforming of IP 54 degree of ingress single phase 8KW lightning load capacity including mounting bracket , cable glands, front openable doors fitted with hinges & locking arrangment complete all as specified and as directed. The contactor MCB and circuit wiring should suitable enough to take load of 12 KW equally distributed over three phase and street light timer should be comprising of following:- (a). Input MCB rating 63 Amps SPN (b).Contactor MCB rating 63 Amps (c).Out put MCB rating 63 Amps (d).Single phase circuit wiring with multistranded copper wire.
21Supply, fixing and testing of Street light timer of single phase multifunction digital time switches using integrated sensor based for automatic switching of street lights complete all as specified and as directed.
22M&L PCC in mix (1:4:8) type D2 with 40 mm graded aggregate for poles / filling in mass concrete complete all as specified and as directed.
23M&L for PCC (1:3:6) Type C2 for erection of pole in base with 40 mm gradede coarse agreegete complete all as specified and as directed.
24M & L for PCC (1:2:4) type B-1 (using 20mm graded stone aggregates) as in coping etc including from work for poles complete all as specified and as directed. by Engr-in-charge.
25Excavation in trenches in any type of soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles/fencing posts etc and getting out hard & densile soil complete all as specified and as directed.
26Excavation in trenches in any type of soil not exc 1.5 mtrs wide and not exc 3 mtr in depth for laying of pipe/ cables/ poles/fencing posts etc and getting out hard & densile soil complete all as specified and as directed.
27Returning fitting in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed.
28Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed.
29M & L for laying of fine, clean sand (river sand) free from sharp materials and stone particals in trenches for cushioning of cable 8 cm thick under cable and 15 cm thick over the cable including gently punning complete all as specified and as directed. Note:- The total thickness of sand shall be measured 18 cm after punning.
30Supplying and laying un-reinforced precast concerete cable cover, class LV, type 1 flat size (250 mm x150 mm x 40 mm) for cable protection , laid flat ie length of cable cover shall be laid across the cable, complete casted with PCC (1:2:4) Type B1 using 20mm graded crushed stone aggregate all as specified and directed
31Material and labour for painting steel tubular pole/ angle iron bracket pole (410 SP -31) 11 mtr long, complete with throughout entire length of pole preperation of new or old painted steel surface exceeding 10cm width or girth, including cleaning, washing and applying two coat of aluminium paint anticorossive over a coat of red oxide primer on outer sufaces of poles/pipes complete all as specified and as directed.
32Material & labour for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5mtr below the normal ground level connected to galvanised wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron.Earth wire protected by GI pipe 15 mm bore(medium grade) and connected to main switch board or main control board as directed and as specified and shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 40 cm x 40cm x 5cm reinforced with 8mm dia TMT bars @ 15cm C/C with one handle for lifting made out of 8mm dia bar, funnel, wire mesh, 20mm dia GI pipe medium grade for watering, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil and testing complete all as specified and as directed by Engineer-in-Charge.
33Supply only Effluent Standard P30 (Dewatering cationic Polymer) used in liquid form in MBBR STPs complete all as specified as directed
34Supply only Effluent Standard E22 (Moving Bed Boifilm Reactor Media) used MBBR STPs complete all as specified as directed
35Supply only Effluent Standard B23 (Oxydation strains) aerobes and facultative strains used to degrade organic compounds in MBBR STPs complete all as specified as directed
36Supply only Effluent Standard S52 used in chlorine contact tank for final effluent disinfection to kill pathogenic microorganisms in MBBR STPs complete all as specified as directed
37Supply only Effluent Standard C25 (Inorganic liquid Coagulant) is a highly Inorganic liquid Coagulant that removes suspended solids, turbidity, colour and organic matters from waste water effectively used in MBBR STPs for maintaning PH complete all as specified as directed
38Dismantling of air blower with motor unit mechanically/electrically of 2-4 HP 3 phase 415 Volt of any make installed at Sewage treatment plant for repair / replacing of the following accessories complete all as specified and directed.
39oil level indicator
40Oil seal
41Breathing plug
42Bearing
43V -belt
44Drain plug
45Bearing cover
46Gear Set
47Pressure relice valve
48Dowl pin
49Air filter
50Pressure guage
51Bellows
52Pulley spacer
53O ring
54Rotor set
55Dismantling of non clog sewage pump set with motor unit mechanicall/electrically of 2 HP 3 phase 415 Volt of any make insalled at Sewage treatment plant for repair / replacing of the following accessories complete all as specified and directed.
56Bearing housing of non clog sewage pump
57Delivery casing of non clog sewage pump
58Impeller of non clog sewage pump
59Gland of non clog sewage pump
60Cover NDE of non clog sewage pump
61Shaft Sleeve of non clog sewage pump
62Mounting Casing of non clog sewage pump
63Wear plate of non clog sewage pump
64Bear shaft of non clog sewage pump
65External fan PVC of non clog sewage pump
66Mechanical Seal of non clog sewage pump
67Flange of non clog sewage pump
68Bearing Cover of non clog sewage pump
69Fan Cover of non clog sewage pump
70Ball bearing of non clog sewage pump
71M & L for opening up short circuited electric motor of Sewage pump set having capacity 2 HP 3 phase AC 440 Volts, cutting and removing the short circuited stator winding coils complete and re-winding the same with super enamelled copper conductor wires of appropriate size as per the existing gauge including cleaning of slots, all necessary insulating materials, varnishing, drying and testing on load complete all as specified.
72M & L for opening up short circuited electric motor attached with air blower installed STP plant of 3-4 HP capacity 3 phase AC 440 Volts, cutting and removing the short circuited stator winding coils complete and re-winding the same with super enamelled copper conductor wires of appropriate size as per the existing gauge including cleaning of slots, all necessary insulating materials, varnishing, drying and testing on load complete all as specified.
73S & F of PVC fan blade for motors of 5 HP capacity complete all as specified.
74M & L for motor end ball / roller bearing with good quality grease suitable for 5 HP capacity pump sets complete all as specified and directed.
75M & L for carrying out replacement of CI pump impeller of 5 HP capacity complete all as specified and directed.
76M & L for DOL starter in replacement of suitable for electric motors in sheet enclosure Type MN, AC 3 Phase, 415 Volt, 50 Hz with thermal over load relay range 2-6 Amps 2 HP incl provision of mounting arrangement with MS flat strips 40 mm x 5 mm thick of suitable length and shape duly drilled and embedded to wall incl making good disturbed surfaces complete all as specified and directed.
77M & L for DOL starter in replacement of suitable for electric motors in sheet enclosure Type MN, AC 3 Phase, 415 Volt, 50 Hz with thermal over load relay range 6-10 Amps 5 HP incl provision of mounting arrangement with MS flat strips 40 mm x 5 mm thick of suitable length and shape duly drilled and embedded to wall incl making good disturbed surfaces complete all as specified and directed.
78M & L for FASD starter in replacement of suitable for electric motors in sheet metal enclosure Type MN, AC 3 Phase, 415 Volt, 50 Hz with thermal over load relay range 40-80 Amps of capacity 50/60 HP incl provision of mounting arrangement with MS flat strips 40 mm x 5 mm thick of suitable length and shape duly drilled and embedded to wall incl making good disturbed surfaces complete all as specified and directed. Please Enable Macros to View BoQ information
79M & L for FASD starter in replacement of suitable for electric motors in sheet metal enclosure Type MN, AC 3 Phase, 415 Volt, 50 Hz with thermal over load relay range 40-80 Amps of capacity 50/60 HP incl provision of mounting arrangement with MS flat strips 40 mm x 5 mm thick of suitable length and shape duly drilled and embedded to wall incl making good disturbed surfaces complete all as specified and directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56869093
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 79 Lakhs
LAST DATE 03-09-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair Replacement Of Security Lights, Poles, Timers, Switches, Cables And Various Stp Related Maintenance Wks Under Md And Otm Accn Of Phase-I (Rupa, Gachham, Birpur, Dp, Bomdila And Dahung) With Allied Em Worksatgetanga
Basic Detail
Tender No 8660/E8
Bidding Type Tender
Location
City kameng
State Arunachal Pradesh
Key Dates
Publish Date 06 Aug 2026
Submission Date 03 Sep 2026
Open Date 10 Sep 2026
Finance
Tender Value 79 Lakhs
Tender Fee 1000
EMD 1.43 Lakhs
Exemption Available
Document List
BOQ_877301.xls
eaa7c071-7043-4cbd-b517-f24acad45124.html
Tenderdocuments8660.rar
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 06, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Sep 03, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Sep 10, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 24 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_877301.xls

html

eaa7c071-7043-4cbd-b517-f24acad45124.html

rar

Tenderdocuments8660.rar

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail