Tender For Repair/Maintenance Of Dg Sets, Amf Panels , Control Panels, Voltage Stabilizers, Isolation Transformers, Air Compressors ,Earthing/Lightning Protection And Connected Work Of Different Capacity In West Wing In Tech Area Af Station Gwalior

Issued by Statutory Bodies & Commissions/Committees · Gwalior, Madhya Pradesh
Tender Value
48 Lakhs
Estimated cost
Bid Submission
28 Aug 2026
16 days left
EMD
96000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Gwalior → Madhya Pradesh
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maintenance Of Dg Sets, Amf Panels , Control Panels, Voltage Stabilizers, Isolation Transformers, Air Compressors ,Earthing/Lightning Protection And Connected Work Of Different Capacity In West Wing In Tech Area Af Station Gwalior

BOQ

Name of Work:- REPAIR/MAINTENANCE OF DG SETS, AMF PANELS , CONTROL PANELS, VOLTAGE STABILIZERS, ISOLATION TRANSFORMERS, AIR COMPRESSORS ,EARTHING/LIGHTNING PROTECTION AND CONNECTED WORK OF DIFFERENT CAPACITY IN WEST WING IN TECH AREA AF STATION GWALIOR
Sl. No. Item Description
1M/L for Maintenance and servicing of standby DG Set of Capacity 500 KVA complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , check & clean air cleaner , change air cleaner elements, check coolant level & make up the same ,drain the fuel filter & water separator ,filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the u/s brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including M&L for changing of V-belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/ coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temprature , coolent temprature, frequency , load current , battery charging , fuel consumption etc complete all as spicified and directed by Enginner in Charge Make - Cummins , Kirloskar ,Greaves cotton with AMF Panel.
2All as per Item No . 1 here-in -before but for : 400 KVA DG set .Make:- `Kirloskar with AMF panel
3All as per Item No . 1 here-in -before but for : 320 KVA DG set .Make:- Kirloskar with AMF panel
4All as per Item No . 1 here-in -before but for : 250 KVA DG set .Make:- Kirloskar with AMF panel
5All as per Item No . 1 here-in -before but for : 200 KVA DG set .Make:- `Kirloskar with AMF panel
6All as per Item No . 1 here-in -before but for : 160 KVA DG set .Make:- Kirloskar/Cummins with AMF panel
7All as per Item No . 1 here-in -before but for : 125 KVA DG set .Make:- Cummins with AMF panel
8All as per Item No . 1 here-in -before but for : 100 KVA DG set .Make:- Kirloskar/Mahindra with AMF panel
9All as per Item No . 1 here-in -before but for : 63 KVA DG set .Make:- Kirloskar with AMF panel
10All as per Item No . 1 here-in -before but for : 40 KVA DG set .Make:- Kirloskar with AMF panel
11All as per Item No . 1 here-in -before but for : 20 KVA DG set .Make:- `Kirloskar with AMF panel
12All as per Item No . 1 here-in -before but for : 15 KVA DG set .Make:- `Kirloskar with AMF panel
13All as per Item No . 1 here-in -before but for : 7.5 KVA DG set .Make:- `Crompton greaves with AMF panel Note for BOQ Item No 1.00 to 13.001. Engine oil for refilling will be measured and paid Seprately 2. Coolant for make up will be measured & paid separately3. DHPP will be issued by dept for testing and top up in tank only. 4. The Make of Fuel filter , Oil Filter , V belt & component will be as per existing or suitable make. 5. The rate quoted against item No. 1.00 to 13.00 is deemed to be inclusive of any break down attendance / rectification during contract period with in 72 hours of complaint received. failing which penalty @ 3000.00 per day will be recoverd from work done statemenet till rectification . 6. The servicing of Dg set shall be carried out only by the OEM team/rep and after servicing the service report shall be submitted to the JE/Engr in charge 7. A register for record of servicing & break down attendence shall be maintained by contract duly signed by JE /Engineer-in -Charge .
14Supply, installation, testing and commissioning in replacement of factory made AMF panel Outdoor type,Doubledoor , cubical type front operated, totally enclosed, dust and vermin proof, floor mounted made out of CRCA sheet 3.15 mm thick , powder coated with all control wiring from front, oprated panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 125 KVA,415V, 3 phase 50 Hz 4 wire system including Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status with announciator, Push button for engine start/stop, 320 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 320 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with in build seperate chamber for On load change over switch with the the same having capacity of 320 Amps - 02 Nos ( for Main & DG by pass system), Copper busbar having 600A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge.
15Supply, installation, testing and commissioning in replacement of factory made AMF panel Outdoor type,Doubledoor , cubical type front operated, totally enclosed, dust and vermin proof, floor mounted made out of CRCA sheet 3.15 mm thick , powder coated with all control wiring from front, oprated panel shall have provision for termination of UG cable for incomming / outgoing and necessary gland plates including cable termination with cable glands shall be provided at bottom of the panel suitable for DG set 160 KVA,415V, 3 phase 50 Hz 4 wire system including Auto main supply failure monitor (AMF) control relays, voltage & current sensors, supply failure timer, restoration timer control unit incorporating automatic engine start/stop/Auto/manual/test, indicators for load/mains status with announciator, Push button for engine start/stop, 250 Amps 4 Pole Power contactors with OLR relay - 02 Nos and MCCB 4 Poles 250 Amps 36 KA rating with ics=100%icu with adjustable thermal over load and magnetic short circuit releases - 2 Nos, with in build seperate chamber for On load change over switch with the the same having capacity of 250 Amps - 02 Nos ( for Main & DG by pass system), Copper busbar having 400 A rating for phase & Neutral which is duly insulated with proper colour coding , One battery charger in built for charging batteries with 24V 20A SCR Controlled Battery Charger , selector switch and DC voltmeter & Ammeter all as specified and directed by Engineer-in-charge.
16Supply and fix in replacement of Lead acid battery, 12 volt, 180 AH Confirming to IS 14257-1995 Complete all as specified and directed.
17Supply and fix in replacement of Lead acid battery, 12 volt, 150 AH Confirming to IS 14257-1995 Complete all as specified and directed.
18Supply and fix in replacement of Lead acid battery, 12 volt, 100 AH Confirming to IS 14257-1995 Complete all as specified and directed.
19Supply and fix in replacement of Lead acid battery, 12 volt, 80 AH Confirming to IS 14257-1995Complete all as specified and directed.
20M& L for replacement of Stainless steel hinges heavy duty for DG SET Canopy Door (4x4)\\" complete with fixing accessories all as specified and directed
21M & L for overhauling of complete of DG set 50KVA by disconnecting and removing the following parts from the engine, and refixing/re-assembling the new parts on site/workshop as mentioned below complete all as specified and directed by Engr-in-Charge. (a)Valve,intake (b) Bearing,coonecting rod (c) seal,oil (d) Seal, O ring (e) Sender-pressure (f) Valve,exhaust (g) collet valve (h) spring, valve (i) Gasket Cylinder head (j) Camshaft (k) Kit, Engine piston (l) Cover, accessory drive (m) Injector (n) Pin, Piston (o) Retainer , Valve spring (p) Gasket, Gear cover (q) Sensor-Temperature.Note: The rate quoted shall be inclusive of transporting of the complete engine to the workshop and back and all incidental charges.
22Material and labour for dismantling and taking out the complete Alternator assembly of 400 KVA DG Set with the help of Hydra, taking out to the workshop, removing of complete burnt out copper coil , clean the field surface of the coil ,rewinding of Mainfield coil with approved suitable gauge super enamel insulated copper winding wire with necessary insulating materials, warnishing , drying out , reassembling and bring back to orgins at installation and re-assembling /re-fixing the complete set, testing and commissioning complete all as specified and directed by Eng-in-charge.
23Material and labour for dismantling and taking out the complete Alternator assembly of 500 KVA DG Set with the help of Hydra, taking out to the workshop, removing of complete burnt out copper coil , clean the field surface of the coil ,rewinding of Mainfield coil with approved suitable gauge super enamel insulated copper winding wire with necessary insulating materials, warnishing , drying out , reassembling and bring back to orgins at installation and re-assembling /re-fixing the complete set, testing and commissioning complete all as specified and directed by Eng-in-charge.
24Material and labour for dismantling and taking out and rewinding of Excitation field coil of 500 KVA DG Set and rewinding of approved suitable gauge super enamel insulated copper winding wire with necessary insulating materials, replacement of suitable bearing, reassembling and transportation to workshop and bring back to orgins at installation and fixing,testing and commissioning complete all as specified and directed by Eng-in-charge.
25M&L in replacement of Gen set controller display KG 645 KOEL Green,SEDMAC including necessary programming , restoring the data testing and commissioning complete all as specified and directed.
26M&L in replacement of Gen set controller displayEMS 907 including necessary programming , restoring the data testing and commissioning complete all as specified and directed.
27Supply only Engine oil SAE 20W-40W
28Supply only fan belt /V-Belt of size B-53 complete all as specified
29All as per item No 28 above but of size B-58
30All as per item No 28 above but of size B-64
31All as per item No 28 above but of size B-70
32All as per item No 28 above but of size B-143
33Supply only coolant for radiator all as specified and directed.
34M & L for spray painting the Generator Set including acoustic enclosure and corresponding AMF panel complete with existing colour coding of any capacity after preparation of rough unequal surface and applying two coats of synthetic enamel paint over coat of primer on old steel surface by spray painting in and including lettering and marking i.e Engine make, Engine Sl No, Alternator make, Alternator Sl No etc all as specified and directed by Engineer-in-charge.
35S & Fix in repair/replacement of Automatic voltage regulator (AVR) full wave phase controlled adjustable (0-95V) 6A/12A Suitable for DG Set 40 to 200 KVA including connecting and testing complete all as specified and directed
36S & Fix in repair, replacement of Automatic voltage regulator (AVR) full wave phase controlled adjustable (0-95V) 6A/12A Suitable for DG Set AVR(MODEL AS440)S/F STAMFORD and other equal models of 400/500 KVA including connecting and testing complete all as specified and directed
37M & L Repair / overhauling radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc of 320 KVA DG Set all as required and as directed.Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
38M & L Repair / overhauling radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc of 400 KVA DG Set all as required and as directed.Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
39M & L Repair / overhauling radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc of 500 KVA DG Set all as required and as directed.Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
40M & L Repair / overhauling radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc of 125 KVA DG Set all as required and as directed.Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
41M & L Repair / overhauling radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc of 100 KVA DG Set all as required and as directed.Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
42M & L Repair / overhauling radiator assembly of DG set by disconnecting and removing from the engine, dismantling the top and bottom chambers, descaling the sediments, scales, corrosion etc. by means of acid, cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets including arresting leakages, if any and fixing to the engine with new hoses, clips etc of 200 KVA DG Set all as required and as directed.Note: The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
43M&L in replacement of radiator assembly of DG set by disconnecting and removing from the engine of 160 KVA DG set complete all as specified and directed.
44M&L in replacement of radiator assembly of DG set by disconnecting and removing from the engine of 100 KVA DG set complete all as specified and directed.
45M & L Repair / overhauling Self starter assembly, 12 Volt DC of DG Make: Delco Remi / Lucas TVS assembly of DG Set by disconnecting and removing from the engine, cleaning of all accessories, replacing of worn out parts such as rotor, vendex ,carbon brushes, bushes, contact plates, jumping leads and seals, revarnishing the field coil, armature and re-assembling the same and re-fixing into the engine including testing all as per original manufacturer's instructions and as directed. NOTE :- 1. The rate quoted by the contractor is deemed to be include for transportation of the item from site to the workshop as applicable and back.
46M & L Repair / overhauling Self starter assembly, 24 Volt DC of DG Make: Delco Remi / Lucas TVS assembly of DG Set by disconnecting and removing from the engine, cleaning of all accessories, replacing of worn out parts such as actuator ,gear, solenoid coil ,carbon brushes, bushes, contact plates, jumping leads and seals, revarnishing the field coil, armature and re-assembling the same and re-fixing into the engine including testing all as per original manufacturer's instructions and as directed. NOTE :- 1. The rate quoted by the contractor is deemed to be include for transportation of the item from site to the workshop as applicable and back.
47Supply and fix in repair fuel shutup solenoid valve, 24 volts, suitable for 500 KVA DG set NOTE:- All items to be from manufacturerer's / manufacturers authorised stockiest/ distributor/ dealer only and also the contractor always keep minimum required quantities in hand as a pro-active/ preventive maint/ breakdown
48All as per Item No . 47 here-in -before but for : 400 KVA DG set .
49All as per Item No . 47 here-in -before but for : 250 KVA DG set .
50All as per Item No . 47 here-in -before but for : 160 KVA DG set .
51All as per Item No . 47 here-in -before but for : 125 KVA DG set .
52All as per Item No . 47 here-in -before but for : 100 KVA DG set .
53All as per Item No . 47 here-in -before but for : 63 KVA DG set .
54S & Fix in replacement of SMPS based Battery charger module 24 volt 15/20A Amps having CC,CV, trickle,float and boost charging mode suitable for AMF Panels of DG Set 200/250/320/500 KVA capacity
55S & Fix in replacement of SMPS based Battery charger module 12 volt 15/20A Amps having CC,CV, trickle,float and boost charging mode suitable for AMF Panels of DG Set 40/63/100/125/160 KVA capacity
56S & Fixing in repairs Lub oil pressure transducer suitable for DG set upto 500 KVA system all as directed by Engineer-in-Charge
57S & Fixing in repalacement of proximity Magnetic pickup for sensing RPM of DG set 250/380 KVA capacity with existing model all as directed by Engineer-in-Charge
58S & Fixing in replacement of Low lub oil pressure safety switch suitable for DG set 160/200KVA and connecting with DG set system, testing complete all as directed by Engineer-in-Charge
59S & Fixing in repairs High water temperature trip safety switch suitable for DG set 320/500KVA and connecting with DG set system, testing complete all as specifiied and directed by Engineer-in-charge
60S & Fixing in replacement of wiring harness for 160/200/250/320 KVA DG set with proper lugs /ferrules/nuts bolt with washers and testing the circuit as specified and directed by Engineer-in-charge
61S & F following items in AMF Panel of any description and in any position of capacity DG Set upto 500 KVA including checking AC/DC circuits, tightning of all power / control wiring connection and replacement of unserviceable control wiring with suitable size, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items to make AMF functional inclusing testing complete all as specified and directed.
62Pla relay 24 Volts DC, 11pin, 2 change over, cat part No. 2C/O – MPC -24D of pla make or equivalent of Eagle man.
63Pla relay 12 Volts DC, 11pin, 2 change over, cat part No. 2C/O – MPC -12D of pla make or equivalent of Eagle man.
64Ammeter size 96 mm X 96mm, flush mounted digital type, three phase of class 1.0 complete all as specified and directed.Make: HPL / Rishab / MECO / Schneider.
65Voltmeter size 96 mm X 96mm, flush mounted digital type, three phase, class 1.0 complete all as specified and directed. Make: HPL / Rishab / MECO / Schneider.
66Frequency meter size 96 mm X 96mm, flush mounted digital type, three phase, class 0.2 complete all as specified and directed.Make: HPL /Rishab / MECO / Schneider.
67Under voltage relay suitable for 3 phase 415 volts, AC supply complete all as specified and directed.
68Engine starting relay with sequence timer & master timer suitable for 12 / 24 Volts DC supply complete all as specified and directed. Make: L&T/PIC / Aditya Electronic
69Electronic timer, time range from 3 seconds to 10 seconds , suitable of 12/ 24 Volts, 50 Hz, AC supply complete all as specified and directed.Make: L&T/PIC / Aditya Electronic
70LED Indicator 22.5mm for 12 /24 volts AC/DC supply complete all as specified and directed.Make: L&T/ BCH / Seimens / ABB.
71MCB single pole, 10 KA, rating 6 to 32 Amps ‘C’ series, 240 volts complete all as specified and directed.
72M&L for repairing of canopy of DG set by carrying out repairing of door with replacement of broken hinges including nuts, bolts/welding etc as per requirement, cleaning of base of foundation and painting with black paint MS channel with two coats including touching of paint at cannopy where required complete all as specified and directed
73Material and labour for dismantling and taking out and rewinding of stator assembly of 500 KVA DG Set and rewinding of approved suitable gauge super enamel insulated copper winding wire with necessary insulating materials reassembling and transportation to workshop and bring back to orgins at installation and fixing,testing and commissioning complete all as specified and directed by Eng-in-charge.
74All as per item No 63 above but of Capacity 400 KVA DG set.
75All as per item No 63 above but of Capacity 320 KVA DG set.
76All as per item No 63 above but of Capacity 250KVA DG set.
77All as per item No 63 above but of Capacity 100 KVA DG set.
78All as per item No 63 above but of Capacity 40 KVA DG set.
79S & F in repair governor control unit for electronic governor suitable for DG Sets of capacity 500 KVA complete all as specified and directed.
80All as per item No 69 above but of Capacity 160 KVA DG set.
81All as per item No 69 above but of Capacity 200 KVA DG set.
82All as per item No 69 above but of Capacity 320 KVA DG set.
83All as per item No 69 above but of Capacity 400 KVA DG set.
84S&F in repair Actuator ETR fuel control unit of cummins/Kirloskar make DG sets of 320-400 KVA capacity complete all as specified and directed.
85M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 800 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
86M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 600 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
87M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 400 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
88M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 320 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
89M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 250 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
90M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 100 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
91M&L in replacment of AMF Power contactor , 4 pole, 415 Volts, 63 Amps, 50 Hz, AC , with 2 NO and 2 NC contacts including any modification to existing panel frame size and fixing new contactor with connecting bars to the main busbar, incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
92S & F in replacement of Digital Multifunctional Panel meter for measuring Voltage ( 0-500V min ) ,(0-600A) Current , P.F,frequency on existing AMF panel including necessary P.T & C.T's with all connected acccessories all as specified and directed
93S & F in replacement of push button switch with NO/NC contacts 415 V ,6A , with add on Aux Contacts and connected acccessories all as specified and directed
94S & Fix in replacement of Rotatory selector switch 3/4 way 10A for Panel meter including connection as all as specified.
95M&L in replacment of MCCB, 3 poles 415 Volts, 100 Amps, 16 kA, 50 Hz, AC, adjustable type in the existing AMF panel board/sheet metal enclosure including any modification to existing panel frame size and fixing new MCCB with connecting bars to the main busbar and connecting up incoming/out going cables with suitable lugs and testing complete all as specified and as directed.
96All as per item No 85 here in before but MCCB 3 pole, 125 Amps, breaking capacity Icu = 16 KA.
97All as per item No 85 here in before but MCCB, 4 pole, 160 Amps, breaking capacity Icu = 36 KA.
98All as per item No 85 here in before but MCCB, 4 pole, 200 Amps, breaking capacity Icu = 36 KA
99All as per item No 85 here in before but MCCB, 4 pole, 250 Amp, breaking capacity Icu = 36 KA
100All as per item No 85 here in before but MCCB, 4 pole, 320 Amp, breaking capacity Icu = 36 KA
101All as per item No 85 here in before but MCCB, 4 pole, 400 Amps, breaking capacity Icu =36 KA
102All as per item No 85 here in before but MCCB, 4 pole, 600 Amps, breaking capacity Icu = 50 KA
103All as per item No 85 here in before but MCCB, 4 pole, 800 Amps, breaking capacity Icu = 50 KA
104Supply and fix PVC insulated multistranded FRLSH copper round cable suitable for DG sets battery terminal lead of size 16 Sqmm all as specified Make :- polycab/finolex/havells
105Supply and fix in replacement of gunmetal battery connecting terminal suitable for 12v/24v battery all as specified and directed
106supply only spray can 500ml for cleaning electrical contacts and decarbonizing electrical parts all as specified and directed .Make : CRC/WD-40/3M
107M & L in replacement of flywheel with gear tooth assembly suitable for DG 40 KVA DG and align center/level between alternator and engine and testing complete all as specified and directed by engineer in charge
108S&F DG Set specification display board made out of flexible acrylic sheet of Size 2 x 3 feet background of blue colour with white letters of size 50/40mm for alongwith all fixing arrangements different type and model of DG Set as per sample and as directed by the Engr-in-Charge including removing old existing damaged board and accessories all as directed
109M&L in repair for necessary PCC (1:2:4) type B2 ,40 mm graded aggregate for foundation of DG Set, AMF Panel,Pathway to DG Set for making the smooth access from Road complete all as specified and directed.
110M&L in repair for necessary PCC (1:3:6) type C1 , 20 mm graded aggregate for foundation of DG Set, AMF Panel,Pathway to DG Set for making the smooth access from Road complete all as specified and directed.
111M&L for earthing complete with galvanised steel plate electrode 600x600x6mm thick buried directly in ground (top edge of the plate should not be less than 1.50Mtrs below ground level) connected to GI strip 36×6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel connected to earthing test point all as specified incl 20 mm GI tubing medium grade and necessary fitting for protection of GI strip incl laying of charcoal dust and common salt in alternate layers of 150mm th, PCC chamber using PCC(1:3:6) type C-1 using 20mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally up to 150mm below ground level, GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on Electrical plate No.3 of SSR Part-I (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results (in white) on a black painted M.S. Plate (size 300x300x3mm th) duly welded with angle iron of size 40X40x5mm, 60cm long, fixed with the earth pit chamber by grouting complete all as specified and directed.Note :- (i) GI strip and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing.(ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for PCC chamber and PCC cover as per SSR part-1.
112M& L in replacement of Diode set suitable for Genarator capacity 500 kva complete all as specified and directed.
113M& L in replacement of Diode set suitable for Genarator capacity 400 kva complete all as specified and directed.
114M& L in replacement of Diode set suitable for Genarator capacity 320 kva complete all as specified and directed.
115M& L in replacement of Diode set suitable for Genarator capacity 125 kva complete all as specified and directed.
116M& L in replacement of Diode set suitable for Genarator capacity 100 kva complete all as specified and directed.
117M&L in replacement of Gen set controller display HMI 211 including necessary programming , restoring the data testing and commissioning complete all as specified and directed.
118M&L in replacement of Gen set controller display POWERCOM including necessary programming , restoring the data testing and commissioning complete all as specified and directed.
119M&L in replacement of Gen set controller display POWER START500 (PS-500) including necessary programming , restoring the data testing and commissioning complete all as specified and directed.
120M&L in replacement of Gen set controller display POWER START 600(PS-600) including necessary programming , restoring the data testing and commissioning complete all as specified and directed.
121M&L for opening of Generator Engine Head of capacity 200 KVA Generator by taking out complete Engine section using Hydra and taking the complete engine section to the authorised workshop and replacement of unserviceble or burned out spare parts as follows. (a) Engine piston -06 Nos (b) Engine Liner -06 Nos (c) Ring set - 06 Nos (d) Head Packing Kit set - 01 Nos (e) Main bearing kit- 01 set (f) CR Bearing - 01set (g) Thrust washer (h) water seperator - 01 Nos (i) Oil lubrication sensor - 01 Nos (j) Inlet valve - 06 Nos (k) Exhaust valve - 06 Nos (l) Hose pipe set - 1 Set (m) O ring set - 01 set (n) Anabond - 04 Nos (o) Cylinder Head cover gasket -06 Nos (p) Turbo Job - 01 Nos (q) Fuel pump and injector - 01 Set (r) Stem seal set - 06 Nos .
122M&L for opening of Generator Engine Head of capacity 320 KVA Generator by taking out complete Engine section using Hydra and taking the complete engine section to the authorised workshop and replacement of unserviceble or burned out spare parts as follows. (a) Engine piston -06 Nos (b) Engine Liner -06 Nos (c) Ring set - 06 Nos (d) Head Packing Kit set - 01 Nos (e) Main bearing kit - 01 set (f) CR Bearing kit - 01 set (g) Thrust washer (h) water seperator - 01 Nos (i) Oil lubrication sensor - 01 Nos (j) Inlet valve - 06 Nos (k) Exhaust valve - 06 Nos (l) Hose pipe set - 1 Set (m) O ring set - 01 set (n) Anabond - 04 Nos (o) Cylinder Head cover gasket -06 Nos (p) Turbo Job - 01 Nos (q) Fuel pump and injector - 01 Set (r) Stem seal set - 06 Nos .
123M&L for opening of Generator Engine Head of capacity 125 KVA Generator by taking out complete Engine section using Hydra and taking the complete engine section to the authorised workshop and replacement of unserviceble or burned out spare parts as follows. (a) Engine piston -04Nos (b) Engine Liner -04 Nos (c) Ring set - 04 Nos (d) Head Packing Kit set - 01 Nos (e) Main bearing kit - 01 set (f) CR Bearing kit - 01 set (g) Thrust washer (h) water seperator - 01 Nos (i) Oil lubrication sensor - 01 Nos (j) Inlet valve - 04 Nos (k) Exhaust valve - 04 Nos (l) Hose pipe set - 1 Set (m) O ring set - 01 set (n) Anabond - 04 Nos (o) Cylinder Head cover gasket -04 Nos (p) Turbo Job - 01 Nos (q) Fuel pump and injector - 01 Set (r) Stem seal set - 04 Nos .
124M&L in replacement of Engine Head piston suitable for Generator capacity 500 KVA complete all as specified and directed.
125M&L in replacement of Engine Head piston suitable for Generator capacity 400 KVA complete all as specified and directed
126M&L in replacement of Engine Liner with O ring suitable for Generator capacity 500 KVA complete all as specified and directed.
127M&L in replacement of Engine Liner with O ring suitable for Generator capacity 400 KVA complete all as specified and directed.
128M&L in replacement of Engine Main bearing kit suitable for Generator capacity 500 KVA complete all as specified and directed.
129M&L in replacement of Engine Main bearing suitable for Generator capacity 400 KVA complete all as specified and directed.
130M&L in replacement of Engine CR bearing suitable for Generator capacity 500 KVA complete all as specified and directed.
131M&L in replacement of Engine CR bearing suitable for Generator capacity 400 KVA complete all as specified and directed.
132M&L in replacement of Engine Cylinder head cover gasket suitable for Generator capacity 500 KVA complete all as specified and directed.
133M&L in replacement of Engine Cylinder head cover gasket suitable for Generator capacity 400 KVA complete all as specified and directed.
134M&L in replacement of Engine Fuel pump suitable for Generator capacity 500 KVA complete all as specified and directed.
135M&L in replacement of Engine Fuel pump suitable for Generator capacity 400 KVA complete all as specified and directed.
136M&L in replacement of Engine PC Nozle suitable for Generator capacity 500 KVA complete all as specified and directed.
137M&L in replacement of Engine PC Nozle suitable for Generator capacity 400 KVA complete all as specified and directed.
138M&L in replacement of Engine water pump seperator suitable for Generator capacity 500 KVA complete all as specified and directed.
139M&L in replacement of Engine water pump seperator suitable for Generator capacity 400 KVA complete all as specified and directed.
140M&L in replacement of Oil pump suitable for Generator capacity 500 KVA complete all as specified and directed.
141M&L in replacement of Oil pump suitable for Generator capacity 400 KVA complete all as specified and directed.
142Calibration of gen set Display controller and resetting the complete set from OEM team Only with the help of Laptop complete all as specified and directed.
143Attending of daily wise complaints of any capacity of DG Set and connected AMF panel and identify the faults whether electrical/mechanical with the help of a skilled technician and a helper using with proper tools and accessories and same shall be mentioned on Job Card Received from JE and kept the same on record with the sign of JE complete all as specified and directed.
144Disconnecting of existing DG set connection of any capacity or any size and AMF panel including all the electric connectons and shifting of the same to the location as per requirement with the help of Hydra/crane/open trolley with all necessary electric connections and testing of the DG set atleast 1 hr with full load or as per existing complete all as specified and directed by Engr-in-Charge.
145Supply only Battery distilled water for refilling of drained out sealed lead acid battery of any capacity complete all as specified and directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56869089
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 48 Lakhs
LAST DATE 28-08-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maintenance Of Dg Sets, Amf Panels , Control Panels, Voltage Stabilizers, Isolation Transformers, Air Compressors ,Earthing/Lightning Protection And Connected Work Of Different Capacity In West Wing In Tech Area Af Station Gwalior
Basic Detail
Tender No 8900/1687/GWL/E8
Bidding Type Tender
Location
City Gwalior
State Madhya Pradesh
Key Dates
Publish Date 06 Aug 2026
Submission Date 28 Aug 2026
Open Date 04 Sep 2026
Finance
Tender Value 48 Lakhs
Tender Fee 500
EMD 96000
Exemption Available
Document List
TENDER1687.pdf
Tendernotice_1.pdf
10ac2a91-b32e-41da-9846-82d81584a5c0.html
BOQ_877285.xls

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 06, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 16 days
Sep 04, 2026

Bid Opening Date

Technical bids will be opened and evaluated.