Tender For Repair And Maintenance Of 33/11/.415 Kv Damaged Cable And Electrical Breakdown Including Fault Detection, Localization, Rectification Works In 11/.415Kv Underground Cable Network, Overhead Lines And Lt Panels At Nsb -Iii, Panchwati, 1/5 Gr
Tender Overview
Project Description
Tender for Repair And Maintenance Of 33/11/.415 Kv Damaged Cable And Electrical Breakdown Including Fault Detection, Localization, Rectification Works In 11/.415Kv Underground Cable Network, Overhead Lines And Lt Panels At Nsb -Iii, Panchwati, 1/5 Gr, Dcn Palam, Tigris, 69 Med Regt, 512 Lt Ad, 972 Tpt, 261 Arty Bde, 8 Engr, Sho, Dhruv Mess, 3 Jak Rif, Echs, 147 Fd Wksp, Karam Vihar, Signal Coy, Mod Line, Sanyat Line, Old Base Power House, Sikhawati Line, New Npg, Old Npg, Hazipeer Line, Daps School, Afmsd, 17 Jak Rif, Blood Bank, 262 Transit C , 285 Wksp, Signal Coy, 629 Tpt Asc In The Area Of Age (U) E/S - I, Under Ge (U) Elect Supply Deihi Cantt-10
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 13-Aug-2026 | AMENDMENT NO 1 | Other | 26-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 11 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed by Engr-in-Charge.Note: (a) 11 KV HT cable & joints shall be measured and paid for separately under respective items of schedule.(b) Retrieved old serviceable cable cover will be laid in trenches for cable protection. If extra PCC cover and sand required at site shall be measured and paid separately under respective items of BOQs.(c) Excavation and earth work will be measured and paid for separately under respective items of schedule. |
| 2 | All as per item Ser No 1 here in before but 1100 Volt LT cables complete all as specified and directed by Engr-in-Charge. |
| 3 | Taking up/down of existing /old under ground LT/HT cable of any size from tranches/pole/wall for relaying/refining at other /new location complete all as specified and directed by Engr-in-Charge.Note :- (i) Excavation and earth work where required shall be measured and paid separately under respective item. |
| 4 | Refixing/relaying of existing/old underground HT/LT cable of any size in new location (in trenches) for rerouting of existing underground cable complete all as specified and directed by Engineer-in-Charge. Note :- (i) Excavation and earth work where required shall be measured and paid separately under respective item. (ii) Extra cable required for rerouting will be measured and paid separately under Item no 18.00 & 19.00 respectively. |
| 5 | Material and labour for disconnecting faulty /burnt end or portion of cable by removing the cable from loop including necessary excavation & earth work , suitable size of thimble LT tap, relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 25 Sqmm 3.5/4 core to 240 Sqmm 3.5 core of LT cable to LT Panel/pole/main switch complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply and fixing of Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable complete all as specified and directed by Engr-in-Charge of following size :- |
| 7 | 95 Sqmm 3 core. |
| 8 | 120 Sqmm to 185 Sqmm, 3 core. |
| 9 | 240 Sqmm to 300 Sqmm 3 core |
| 10 | Supply and fixing of Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable complete all as specified and directed by Engr-in-Charge of following size :- |
| 11 | 95 Sqmm 3 core. |
| 12 | 120 Sqmm to 185 Sqmm, 3 core. |
| 13 | 240 Sqmm to 300 Sqmm 3 core |
| 14 | Supply and fixing of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored aluminum conductor cable complete all as specified and directed by Engr-in-Charge of following size :- |
| 15 | 95 Sqmm 3 core. |
| 16 | 120 Sqmm to 185 Sqmm, 3 core. |
| 17 | 240 Sqmm to 300 Sqmm 3 core |
| 18 | Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armored heavy duty aluminum conductor 1100 Volts grade complete all as specified and directed by Engr-in-Charge for the following sizes :- |
| 19 | 25-50 Sqmm x 3.5 core/ 4 core |
| 20 | 70-185 Sqmm x 3.5 core |
| 21 | 240-400 Sqmm x 3.5 core |
| 22 | Material and labour for excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and leveling of bottom surface to required level all as specified and directed by Engineer- in- Charge. |
| 23 | Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed by Engr-in-Charge. Note : Measurement shall be taken after punning down. |
| 24 | Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm. complete all as specified and directed by Engr-in-Charge. |
| 25 | All as per srl item No 12 here-in-before but using old cable cover obtained under srl item No 10 here in before complete all as specified and directed by Engr-in-Charge. |
| 26 | S&F of sub class B bricks having minimum compressive strength 75Kg/Sqcm laid in trenches for cable protection etc complete all as specified and directed by Engr-in-Charge. |
| 27 | All as per srl item No 14.00 here-in-before but using old bricks obtained under srl item No 10 here in before complete all as specified and directed by Engr-in-Charge. |
| 28 | Material and labour for returning filling in, including spreading, leveling, watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed by Engr-in-Charge. |
| 29 | Material and labour for removing excavated material (i.e. soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge. |
| 30 | Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testingcomplete all as specified and directed by Engr-in-Charge of following sizes :- |
| 31 | 95 sqmm 3 core. |
| 32 | 120 sqmm 3 core. |
| 33 | 150 sqmm 3 core. |
| 34 | 185 sqmm 3 core |
| 35 | 240 sqmm 3 core |
| 36 | 300 sqmm 3 core |
| 37 | Supply, laying, jointing, testing and commissioning in replacement LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armored, with multistranded aluminum conductors, IS-1554 marked, laid in trenches complete all as specified and directed by Engr-in-Charge of the following sizes:-Note :- Excavation, earth work, cable protection, sand fillings, cable joint shall be measured and paid separately. |
| 38 | 16 Sqmm 4 core |
| 39 | 25 Sqmm 4 core |
| 40 | 35 Sq mm 3.5 core. |
| 41 | 50 Sq mm 3.5 core. |
| 42 | 70 Sqmm 3.5 core |
| 43 | 95 Sqmm 3.5 core |
| 44 | 120 Sqmm 3.5 core |
| 45 | 150 Sqmm 3.5 core |
| 46 | 185 Sqmm 3.5 core |
| 47 | 240 Sqmm 3.5 core |
| 48 | 300 Sqmm 3.5 core |
| 49 | Material and labour for boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 80 to 100 mm bore and making good both ends complete all as specified and directed by Engr-in-Charge. |
| 50 | S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah complete all as specified and directed by Engr-in-Charge of following bore sizes :- |
| 51 | 40 mm |
| 52 | 50 mm |
| 53 | 80 mm |
| 54 | 100 mm . |
| 55 | S&F of cable route indicator made of RCC (Nominal Mix) type B0 1:2:4 (12.5mm graded stone aggregate) with 8mm TMT Bar 150mm c/c of size 1m height X 60cm wide X 10cm thick tapered on top, visible above ground, duly painted with synthetic enamel paint of yellow colour base and letters with black paint. The description for writing for HT cable 33 /11KV as directed by Engr-in-charge complete all as specified and directed by Engr-in-Charge. NOTE:- Sample kept in Engr-in-Charge's office.Note : Rate for PCC 1:3:6 for foundation (min size 0.8mx0.3mx0.3m) of aggregate size 20mm including necessary excavation & earthwork for cable route indicator shall be deemed to be included in the item. |
| 56 | Material and labour for cutting and removing grass, vegetation bushes etc from surrounding 4 pole/6 pole, Transformer, LT panels, in and outside area of HT/LT Sub stn and removing all rubbish to a distance not exceeding 50 m complete all as specified and directed by Engr-in-Charge. |
| 57 | M&L for testing, setting & co-ordination of relay parameters consideration with incoming and outgoing feeders including following tests and setting complete as detalis mentioned as under :- (i) testing of following relays of control panel with secondary injection kit checking and programming of realy (ii) OVER CURRENT IDMT with pick upsetting ,TMS ,CTR |
| 58 | Material and labour for re-painting of existing transformer/RMU GI fencing of any sizes with apply of 2 coats of aluminum paint including rubbing with wire brush/emery paper to fencing and angle irons, at different location after disconnecting of HT supply from incoming and LT supply complete all as specified and directed by Engr-in-Charge. |
| 59 | Material and labour for spreading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surrounding area of outdoor RMU manually without damaging any equipments, cable or parts, spreading & leveling of finished gravel uniformly in layers n. exc. 15 cm thick watered and rammed to true surface complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 60 | Material and labour for spreading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surrounding area of outdoor RMU manually without damaging any equipments, cable or parts, spreading & leveling of finished gravel uniformly in layers n. exc. 15 cm thick watered and rammed to true surface complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 11 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender