Tender For Repair / Maintenance Of Lt Cables Switchgears And Lt Panels At Different Appt Houses And Otm Accn Inside Vijay Durg Under Ge (Vd) Kolkata
Tender Value
37.50 Lakhs
Estimated cost
Bid Submission
26 Aug 2026
18 days left
EMD
75000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kolkata → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair / Maintenance Of Lt Cables Switchgears And Lt Panels At Different Appt Houses And Otm Accn Inside Vijay Durg Under Ge (Vd) Kolkata
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth for laying of UG Cable/Pole/Stays, etc., getting out including forming bottom surface to required level and gradient in Soft/ Loose Soil and getting out, complete all as specified and as directed. |
| 2 | Excavation/Cutting Road/ Hardstanding in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth and getting out, complete all as specified and as directed. NOTE : Quoted Unit Rate shall deem to be included Materials and Labour required for repairing to damaged Road/ Hardstanding to match the existing Surfaces and Specifications. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 Cm in Soft/ Loose Soil, complete all as specified and as directed. |
| 4 | Removing excavated materials not exc. 50.00 Metre and depositing where directed at a level not exc. 1.50 Metre above the starting point, complete all as specified and as directed. |
| 5 | Supply & laying in Trenches Sub-class ‘B’ Bricks, kiln burnt, for Cable Protection, complete all as specified and as directed. |
| 6 | Laying in Trenches Bricks (Serviceable Bricks obtained from Item No. 9.00 here-in-after), for Cable Protection, complete all as specified and as directed. |
| 7 | M&L Sand Cushioning (dry) in Trenches/Ducts for protection of UG Cables (below, above and around the UG Cable laid) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180Cm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, punned thickness of Sand Cushioning only will be measured. |
| 8 | Supply Laying double wall corrugated HDPE Pipe 120mm Outer Dia, confirming to IS-16205 (Part-24) with couplers end cap & bends as required, laid in trenches for cable protection complete all as specified and directed. |
| 9 | Supply Laying double wall corrugated HDPE Pipe 120mm Outer Dia, confirming to IS-16205 (Part-24) with couplers end cap & bends as required, laid in trenches for cable protection complete all as specified and directed |
| 10 | Taking out of interlocking paver block, any shape or size and Re-laying the same after laying of LT cable of any size and also removing all vegetation, algae, grass etc, laid to proper slope & gradient over sand cushioning complete all as specified and directed.NOTE : Sand, if required for connection of cushioning level will be measured and paid seperately. |
| 11 | Supply and Laying of Machine pressed precast concrete interlocking paver block with grey cement and pigment of any shape and size as approved by GE conforming to IS-15658-2006 of 60 mm thickness, M-35 grade with 6 mm top layer of coloured rubberised anti abrasive material complete all as specified and directed. |
| 12 | Taking down unserviceable LT cable for repair/ replacement etc (from cable duct/underground trench/pole), stacking properly (cable, pipe and bricks) complete all as directed by the Engr-in-Charge of the following cross - sections :- (Note :- Necessary earth work to be measured and paid separately. |
| 13 | (a) 25 Sqmm to 50 Sqmm, 3.5 Core |
| 14 | (b) 75 Sqmm to 120 Sqmm, 3.5 Core |
| 15 | (c) 150 Sqmm to 185 Sqmm, 3.5 Core |
| 16 | (d) 240 Sqmm to 400 Sqmm, 3.5 Core |
| 17 | Supply, Laying and testing for replacement of XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall with saddles/Flat iron clamps as per site requirement /passing through pipe/pole complete of the following sizes and cross sectional area :-Note :- Necessary earth work to be measured and paid separately. |
| 18 | (a) 35 Sqmm, 3.5 Core |
| 19 | (b) 50 Sqmm, 3.5 Core |
| 20 | (c) 95 Sqmm, 3.5 Core |
| 21 | (d) 185 Sqmm, 3.5 Core |
| 22 | (e) 240 Sqmm, 3.5 Core |
| 23 | (f) 300 Sqmm, 3.5 Core |
| 24 | (g) 400 Sqmm, 3.5 Core |
| 25 | M&L for Relaying XLPE Under Ground Cable of any description (Serviceable Cable obtained from Item No. 10.00 here-in-before) 1100 Volt grade, after Fault rectification including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed of the following size and cross sectional area :- |
| 26 | (a) 10 Sqmm to 16 Sqmm 2/3½/4 Core |
| 27 | (b) 25 Sqmm to 50 Sqmm 3½/4 Core |
| 28 | (c) 70 Sqmm to 120 Sqmm 3½ Core |
| 29 | (d) 150 Sqmm to 185 Sqmm 3½ Core |
| 30 | (e) 240 Sqmm to 400 Sqmm 3½ Core |
| 31 | S&F Heat shrinkable straight through Jointing Kit suitable for 1100 volts grade XLPE insulated stranded aluminium conductor cable including testing on completion complete all as specified and directed by the Engr-in-Charge for the following size of cables :- |
| 32 | (a) 25 Sqmm to 50 Sqmm 3.5/4 core |
| 33 | (b) 70 sqmm to 150 Sqmm, 3.5 core |
| 34 | (c) 185 sqmm to 240 Sqmm, 3.5 core |
| 35 | (d) 300 sqmm to 400 Sqmm, 3.5 core |
| 36 | Dismantling/ Disconnecting electric connection of underground LT, XLPE Cable, 1100 volts upto 35 to 400 Sqmm from both sides and locating the fault in LT cable with fault locating machine in the entire length up to 1 Km complete testing after reconnecting and commissioning of cable complete all as specified and as directed. Note : The work will be executed after obtaining proper shutdown from Substation liase with JE E/M. |
| 37 | Supply and fix (in replacement) ACB, 800 amps, 4 pole, with microprocessor based release, Ics=50% of Icu, manual drawout type, with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1, internal battery, communication port, inbuilt USB port for software diagnosis, all accessories incl taking down existing ACB complete all as specified and directed. |
| 38 | S&F in repairs of MCCB, 630 amps, 4 pole, 50 KA, with microprocessor based release with electronic Sg (LSIg) protection unit, Ics=100% of Icu with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1 , internal battery, communication port, inbuilt USB port for software diagnosis, all accessories incl taking down existing MCCB complete all as specified and directed. |
| 39 | S&F in repairs of MCCB, 400 amps, 4 pole, 50 KA, with microprocessor based release with electronic Sg (LSIg) protection unit, Ics=100% of Icu with overload, short circuit & ground fault protections with inbuilt display for current metering with high accuracy of class 1 , internal battery, communication port, inbuilt USB port for software diagnosis, all accessories incl taking down existing MCCB complete all as specified and directed. |
| 40 | S&F in repairs of MCCB 4 Pole, 415 V, Adjustable type 320 Amps with breaking capacity 36 KA, Ics=100% of Icu with all accessories incl taking down existing MCCB complete all as specified and directed |
| 41 | S&F in repairs of MCCB 4 Pole, 415 V, Adjustable type 250 Amps with breaking capacity 36 KA, Ics=100% of Icu with all accessories incl taking down existing MCCB complete all as specified and directed |
| 42 | S&F in repairs of MCCB 4 Pole, 415 V, Adjustable type 200 Amps with breaking capacity 36 KA, Ics=100% of Icu with all accessories incl taking down existing MCCB complete all as specified and directed |
| 43 | S&F in repairs of MCCB 4 Pole, 415 V, Adjustable type 160 Amps with breaking capacity 36 KA, Ics=100% of Icu with all accessories incl taking down existing MCCB complete all as specified and directed |
| 44 | S&F in repairs of MCCB 4 Pole, 415 V, 100 Amps with adjustable type, breaking capacity 25 KA, Ics=100% of Icu with all accessories incl taking down existing MCCB complete all as specified and directed |
| 45 | S&F in repairs of MCCB 4 Pole, 415 V, 63 Amps with adjustable type, breaking capacity 25 KA, Ics=100% of Icu with all accessories incl taking down existing MCCB complete all as specified and directed |
| 46 | Dismantling carefully serviceable isolating LT Panel board of sizes 1500mm x 900 mm x 600 mm to 2500 mm x 2000mm x 900 mm, duly unscrewing/ opening front and back cover and cleaning complete bus bar chamber, tightening all the nuts, bolts incomming and outgoing terninals including cleaning the all switchgear/ accessories and replacement of cable gland and replacement of stainless steel hinges of size 100mm for panel board door fixed with welding machine incl applying one coat of synthetic enamel paint externally to panel board after scrubbing/cleaning the surface complete testing the Panel board till satisfaction of Engr-in-Charge, complete all as specified and directed. |
| 47 | S&F Cable Route Indicator made out of Cast Iron plate 80 mm dia fixed with MS angle iron 40x40x6mm having 60 Cm long showing MES LT Cable Size with voltage with two coats of synthetic enamel paint in blue colour over one coat of primer necessary Earth Work and Cement Concrete 1:2:4 (20mm graded crushed stone aggregates) Block of size 20x20x20 Cm including Taking out Unserviceable Cable Route Indicator, complete all as specified and as directed. |
| 48 | Taking out unserviceable LT panel board / FEEDER PILLER box (of any size) and Supply, install, commissioning and testing of Outdoor type LT panel board, cubical type, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 1000mm x 1200mm x 500mm, CPRI approved with front and back openable door (with locking arrangement) and making compartment for each MCCB separately, duly painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar 500 Amps of suitable size (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with aluminium lugs and strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and 02 Nos Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with angle iron frame with base 40 x 40 x 6 mm with legs not more than 450mm long including grouting with PCC (1:2:4) complete including earthing all as directed by the Engr-in-Charge including supply and fixing of the following accessories:- Make : Star Electric & Engg Co/ CPRI approved. |
| 49 | (a) MCCB dsign with thermal-magnetic releases of capacity 320A, 4P, 36 KA - 01 Nos (Incoming). Make : L&T |
| 50 | (b) MCCB dsign with thermal-magnetic releases of capacity 100 Amps, 25 KA - 04 Nos (Outgoing). Make : L&T |
| 51 | (c) MCB SPN 63 Amps - 012Nos. Make : L&T |
| 52 | (d) Digital Ammeter with Selector Switch - 01 Nos. Make : L&T |
| 53 | (e) Digital Voltmeter with Selector Switch - 01 Nos. Make : L&T |
| 54 | (f) MCB SP 6 Amps, 10 KA - 01 Nos. Make : L&T |
| 55 | (g) LED type indication lamp R Y B - 01 set. |
| 56 | (h) Current Transformer Ratio 400/5A - 03 Nos |
| 57 | Note:-(i) All incoming and outgoing cables, duly thimbled along with suitable size of brass cable glands, to be connected with accessories. (ii) All MCCB & Automatic Transfer Switch to be connected internally with suitable size of aluminium strip. |
| 58 | Materials and Labour for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized iron strip 25 X 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed. |
| 59 | Supply and fixing GI tubing 50mm bore (light grade) in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by Engineer-in-Charge. |
| 60 | Supply and fixing 80 mm bore galvanized iron pipe (light grade) with all fittings, fixed in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by the Engineer-in-Charge. |
| 61 | Supply and fixing 100 mm bore galvanized iron pipe (light grade) with all fittings, fixed in trenches/floor/fixed along pole for cable incl taking down old unsv pipe complete all as specified and as directed by the Engineer-in-Charge. |
| 62 | Note: Schedule of credit (SCHEDULE OF CREDIT) amount of Rs ________ mentioned on Page No ____ shall be deducted from the total quoted amount of BOQ. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 05, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysAug 27, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer