Tender For Operation & Running Maintenance Of Different Arws/Rws/Nrdwp/Ridf/Jjm Retrofitting Schemes Under The Jurisdiction Of Dws Sub-Division, Mohanpur/Sh: Repairing And Maintenance Of Existing Panel Board And Providing And Fitting Fixing Of Electr
Tender Overview
Project Description
Tender for Operation & Running Maintenance Of Different Arws/Rws/Nrdwp/Ridf/Jjm Retrofitting Schemes Under The Jurisdiction Of Dws Sub-Division, Mohanpur/Sh: Repairing And Maintenance Of Existing Panel Board And Providing And Fitting Fixing Of Electrical Features Of Different Dtw Scheme Under Mohanpur, Bamutia & Lefunga R.D Block During The Year 2026-27. (Gr-I)
BOQ
| Sl. No. | Item Description |
| 1 | Providing and fitting fixing of 6 feet x 4 feet x 1 inch (thickness) Gamair wood / plywood pannel board for fitting fixing of electrical items, in/c 2 nos MS angle post ( size 2 inch x 2 inch x 9 feet ), nuts & bolts etc. for irrection of the same by 1:1.5:3 cement concrete casting ( 1 feet x 1 feet x 2 feet) below the ground level and painting two or more coats & plastic paint as per specification and direction of the Engineer-in-charge. |
| 2 | Providing and fitting fixing with PVC insulated 3 core flat Copper cable conforming to relevent IS code for submerssible motor with all necessary equipment and fitting as required as per specification and direction of the Engineer-in-charge. |
| 3 | 10 sqmm |
| 4 | Providing and fitting fixing of moving iron type, Range 0-500 V, 96 mm x 96 mm size AC Volt meter ( L & T / AE make) with selector switch as a electrical instrument of the pannel board as per specification and direction of the Engineer-in-charge. |
| 5 | Providing and fitting fixing of moving iron type, Range 0-100/0-200 amps, 96 mm x 96 mm size AC Amps meter direct reading type ( L & T / AE make) with selector switch and CT coil as a electrical instrument of the pannel board as per specification and direction of the Engineer-in-charge. |
| 6 | Providing earthing with perforated 40 mm dia G.I. pipe (Medium class) ( 12 mm dia perforation ) , laying of 4 mm dia GI wire from earth electrode to panel, including excavating hole of 600 mm dia and refilling with Salt and Charcoal / coke in alternate layers of 300 mm , as per standard specification and direction of the Engineer-in-charge. |
| 7 | for 3-phase connection with 4.00 mtr. Long G.I. pipe |
| 8 | Providing and fitting fixing 3 phase indicating lamp fiited with panel board with three different colour lamps with batten holder complete as per specification and direction of the Engineer-in-charge. |
| 9 | Providing and fitting fixing heavy duty box type (Resin filled) power factor correction capacitor L & T make etc. complete as per specification and direction of the Engineer-in-charge. |
| 10 | 5-15 kVAr 440 V |
| 11 | Providing and fitting fixing steel sheet enclosed switch fuse unit (suitable for DIN fuses), triple pole with Neutral Link (TPN), 415/500 Volt, L & T / Havells / BCH make etc. complete as per specification and direction of the Engineer-in-charge. |
| 12 | i) 63 Amps |
| 13 | ii) 100 Amps |
| 14 | iii) 200 Amps |
| 15 | iv) 250 Amps |
| 16 | Providing and fitting fixing of Fully Automatic Star Delta type Motor starter ( 3 ph. 50 Hz, 415V, in Steel Sheet Enclosures with Contractors and Timer etc. complete suitable for submersible Pump L & T, BCH, ABB make as per specification and direction of the Engineer-in-charge. |
| 17 | 25 HP/18.5 kw Relay range within 13-21 + 10% |
| 18 | 35 HP/26 kw Relay range within 20-32 + 10% |
| 19 | 50 HP/37 kw Relay range within 28-42 + 10% |
| 20 | Providing and fitting fixing of Moulded Case Circuit Breaker (MCCB) of different Thermal release range , 415 + V, 50Hz (L & T, BCH, ABB make) as per specification and direction of the Engineer-in-charge. |
| 21 | ii) 32-40 Amps |
| 22 | Providing and fitting fixing of re-wireable porcelain type extended cutout of Havels make as per direction of the Engineer in charge. |
| 23 | i) 200 Amps. |
| 24 | ii) 320 Amps |
| 25 | Providing and fitting fixing of size 70 sq mm dowels copper tube terminal heavy dury ( cat No.CUS285) as per direction of the Engineer In charge. ( Dowell Make) |
| 26 | Providing and fitting fixing Single phasing preventor +selectable under voltage +selectable over voltage on delay 5 sec & off delay 15 sec phase asymmetry 10% L & T /BCH/HAVELS/Siemens etc. make complete as per specification and direction of the Engineer-in-charge. |
| 27 | Providing and fitting fixing 3 pole contactors type ML size Fr 1 AC 3 rating (A) 25 AC 1 Rating (A) 25 type ML 1.5 AUX. contacts 2 No. + 2 NC Cat No. SS91851 of L & T Make as per direction of Engineer in charge. |
| 28 | Providing and fitting fixing 3 pole contactors type ML size Fr 2 AC 3 rating (A) 32, AC 1 Rating (A) 40 type ML 2 AUX. contacts 2 No. + 2 NC Cat No. SS90701 of L & T Make as per direction of Engineer in charge. |
| 29 | Providing and fitting fixing 3 pole contactors type ML size Fr 2 AC 3 rating (A) 40, AC 1 Rating (A) 45 type ML 3 AUX. contacts 2 No. + 2 NC Cat No. SS90721 of L & T Make as per direction of Engineer in charge. |
| 30 | Providing and fitting fixing spare contact kit type ML 1.5 cat no.SS95305 of L & T make as per direction of the Engineer in charge. |
| 31 | Providing and fitting fixing spare contact kit type ML 2 cat no.SS95307 of L & T make as per direction of the Engineer in charge. |
| 32 | Providing and fitting fixing spare contact kit type ML 3 cat no.SS95309 of L & T make as per direction of the Engineer in charge. |
| 33 | Providing and fitting fixing spare coil type ML 1.5 cat no.SS90873 of L & T make as per direction of the Engineer in charge. |
| 34 | Providing and fitting fixing spare coil type ML 2/ML 3 cat no.SS90545 of L & T make as per direction of the Engineer in charge. |
| 35 | Providing and fitting fixing Thermal overload Relay type ML direct mounting of ML 2/ML 3 contactor ( directly operated) Relay Range (A) 20-32/28-42 (cat no. SS9185900EO, SS9185900FO) of L & T make as per direction of Engineer in charge. |
| 36 | Providing and fitting fixing Thermal overload Relay type ML direct mounting of ML 1.5 contactor ( directly operated) Relay Range (A) 10-15 (cat no. SS9185800BO) of L & T make as per direction of Engineer in charge. |
| 37 | Providing and fitting fixing Electronic timer type ST 100 operating voltage 360-415 V, 50 Hz for 3-30 secs of L& T make suitable for ML 2/ ML 3 L & T make starter ( cat no.ST803290000) as per direction of the Engineer in charge. |
| 38 | Providing and fitting fixing Push Buttom unit suitable for MN/DOL/FASD L & T make starter cat no.SS939410000 as per direction of the Engineer in charge. |
| 39 | Providing and fitting fixing Cylindrical fuse link HF size 14x51 rated current (A) 63 suitable for type FN 63/FNX 63 S-D-F and for HC fuse base of L&T make no. SF90158 as per direction of Engineer in charge. |
| 40 | Providing and fitting fixing DIN type fuse link HN size 00 rated current (A) 100 suitable for type HN 100/125/160/FNC 125/160 S-D-F and for HB fuse base cat no.SF94030 of L & T make as per direction of the Engineer in charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender