Tender For Repair/Maint And annual maintenance contract Of Fire Alarm System And Fire Fighting Alongwith Various Connected Items At Afs Under Ge (Af) Jorhat.
Tender Value
Ref. Documents
Estimated cost
Bid Submission
26 Aug 2026
20 days left
EMD
60000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jorhat → Assam
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Maint And annual maintenance contract Of Fire Alarm System And Fire Fighting Alongwith Various Connected Items At Afs Under Ge (Af) Jorhat.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, laying and testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq.mm, 2 core 1100 volts grade complete all as specified and as directed. |
| 2 | Supply, installation, testing and commissioning analogue addressable fire alarm control panel with 2 loop capacity having minimum 99 detector and 99 modules, 32 bit dual core microprocessor with 5 inch multi colour touch display annuciation to indicate power, alarm silenced, trouble, system trouble, disabled, test, supervisory, delay, audio alarm with push buttonb for acknowledge test reset complete with power supply of 24 DC suitable AH and 230 volts and back with a maintenance free battery backup system with the glowing and connecting up complete all as specified and as directed. |
| 3 | Supply, installation, testing & commissioning repeater annuciator panel with backlit, 80-character LCD fire annunciator that mimics the fire alarm control (FACP) display, provides system status indicator for ac power, alarm, trouble, supervisory and alarm silenced conditions. the repeater and the FACP communicate over a two wire serial interface employing the repeater-bus communication format, connected devices are powered via two additional wires by either the host FACP. the repeater display in english language text of system point information including device type, zone, independent point alarm, trouble or supervisory status as well as any custom alpha labels programmed into the control panel. it includes control switches for remote control of critical system functions (a key switch prevents unauthorized operation of the control switches) and connecting up, complete all as specified and as directed. |
| 4 | Supply, installation, testing & commissioning Addressable Type Fire Alarm Sounder/Siren Electronic cum strobe type Horizontal Single Stage Continuous Normal Operation for atleast 50 minimum with sound level 65 db to 120 db measured at 1.50 metre with sound output variation +5 db 3500 metre range and connecting up complete all as specified and as directed. |
| 5 | Supply, installation, testing & commissioning addressable type of Intelligent Loop Isolator with Mounting Base complying with EN-54 standard and LPCB approved with the specifications and connecting up complete all as specified and as directed. |
| 6 | Supply, installation, testing & commissioning addressable type of Manual Call Point, Resettable type and connecting up complete all as specified and as directed. |
| 7 | Supply, installation, testing & commissioning detector complying with and type certified to EN-45 Analogue addressable type multi-sensor detector with Heat and Smoke Combination Photoelectric/Optical with base with self built intelligence as per IS-11360 and connecting up complete all as specified and as directed. |
| 8 | Supply, istallation, testing & commissioning indoor detector complying with and type certified to EN-54 addressable type Flame Detectors with UV and IR detection capacity (Add up cost of module to be a complete set, the type of module shall be Relay Type Module) with self built intelligence and connecting up complete all as specified and as directed. |
| 9 | Comprehensive service/repair/maintenance and monthly visit for regular maintenance for the automation of intelligent addressable fire alarm control panel including checking testing and cleaning of loop card, main board, LCD display, Multisensor, sounder, MCP, Repeater Panel, Zone monitor Module, UV & IR detector, Remote Response indicator, Loop Isolator, Amplifier and Loud speakers carrying out normal repairs for the trouble free and efficient functioning of the entire fire alarm system by providing one engineer for Monthly visit complete all as specified and as directed and as specified NFPA 72 and Guidelines.Locations : CCR, Rt Cabin, Tech Flat Hanger, Butller Hanger, GCA Building, AFNET Building, Common IT Building, Armoury, IL Hanger, 49 SQN Hanger, 43 Sqn Hanger, BCR Building, SRE Building Logistic Section, Base Ops, 736 S&U, Signal Section, Avionic LabNotes:- (i) Cost of new components shall be paid for separately under relevant items of schedule 'A\\"(ii) Contractor's rep will visit minimum once in a month to every panel each location as mentioned above and take serviceability certificate duly signed by the user. |
| 10 | Dismantling, servicing of multisensor detector with heat and smoke combination photoelectric as per exact locations with the help of manufacturer's instructions and testing for exact fault locations including cleaning through air blower then reinstalling every six month complete all as specified and as directed |
| 11 | Serviceability and testing of UV & IR flame detector and its alignment to detect flame with Testing Kit and when directed complete all as specified and as directed |
| 12 | S&F as in repairs or replacement 12 V, 7 AH battery for inverter supply for back up to all FACP panel complete all as specified and as directed. Make: EXIDE/AMCO/AMARON |
| 13 | S&F as in repairs or replacement of Indoor addressable detectors complying with and type certified to EN-54 Addressable type multisensor detector with heat and smoke combination photoelectric / optical with base with self built intelligence complete all as specified and as directed.Make : GST/COOPER/BOSCH/SIEMENS |
| 14 | Supply only annunciating device remote response indicator complete all as specified and as directed.Make : GST/COOPER/BOSCH/SIEMENS |
| 15 | Supply only zone monitor module compatible with fire alarm control panel complete all as specified and as directed.Make : GST/COOPER/BOSCH/SIEMENS |
| 16 | Supply only GST200 rubber keypad F7.843.249 for FACP complete all as specified and as directed. |
| 17 | Supply only GST200 Loop Interface Board F2.908.828 (RoHS) for FACP complete all as specified and as directed. |
| 18 | Supply only GST200 power supply unit F2.932.069 (20100682) for FACP complete all as specified and as directed. |
| 19 | Supply only transformer 220V/27V-100W-R for FACP complete all as specified and as directed. |
| 20 | S&F SMPS adapter 24 V 2.0 Amp complete all as specified and as directed. |
| 21 | S&F RS485 network card for fire alarm control panel complete all as specified and as directed..NOTE : The contract sum shall be derieved by deducting the amount shown in Schedule of Credit attached to this tender from total amount of Schedule 'A'/BOQ. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 05, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysAug 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender