Tender for Repair/Maint Of Lt Distribution System And Allied Works Under Cijws Vairengte
BOQ
| Sl. No. | Item Description |
| 1 | E & M Division Items |
| 2 | Dismantling old unserviceable stay assembly complete including necessary excavation and demolition of concrete and removal from site complete all as per specified and directed |
| 3 | Dismantling of old ACSR conductor from Poles of any size and removal from site complete all as per specified and directed |
| 4 | Dismantling and taking down cross arms of MS channel or angle sections, clamps, nut and bolt, washers, back plate of any size/shape complete and removal from site complete all as per specified and directed |
| 5 | Dismantling of existing unserviceable GI pipe 80/40mm complete all as specified and as directed |
| 6 | Dismantling insulators any type any size complete all as per specified and directed |
| 7 | Dismantling of unserviceable LT pole of any type/size and removal from site complete all as per specified and directed |
| 8 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, laying of pipes, cables, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out soft/loose soil. |
| 9 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed. |
| 10 | Removing excavated materials (soils) not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed. |
| 11 | M & L for fine dry river sand cushioning by laying 8cm thick layer below the cable for making soft bed and 15cm above the cable and then punning down to its consolidated thickness of 18cm after the cable is laid all as specified in SSR Part-I complete all as specified and as directedNote: Only punned thickness of sand shall be considered for measurement purposes |
| 12 | M & L for Bricks; common burnt clay building bricks, sub-class ‘B’ locally available laid flat with width equal to length of brick over LT underground cable in trenches for mechanical protection of size 23cm X 11.5cm X 7.5cm thick complete all as specified and directed. |
| 13 | Material & Labour for PCC 1:4:8 type D2 using 40mm graded crushed stone aggregate as in foundation complete all as per specified and directed |
| 14 | Material & Labour for PCC 1:3:6 type C2 using 40mm graded aggregate as in copping/collar of poles and foundation of stay assembly etc complete all as specified and directed. |
| 15 | Material & Labour for PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate as in copping complete all as per specified and directed |
| 16 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 120sqmm 3-1/2 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 17 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 95sqmm 3-1/2 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 18 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 70sqmm 3-1/2 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 19 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 35sqmm 3-1/2 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 20 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 25sqmm 4 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 21 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 16sqmm 4 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 22 | Taking out/Dismantling of existing unserviceable UG Cable of after disconnetion from LT panel/feeder pillar and poles and Supply, Laying, jointing and testing in trenches or fixing or passing through pipe of LT XLPE cable insulated multi stranded aluminium conductor, 1100 volts grade heavy duty, cross sectional area 10sqmm 4 core served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed conforming to IS-7098 (Part-I)-1988 complete all as specified and as dirtected. |
| 23 | Supplying,laying, jointing, testing and commissioning of aluminium Aerial Bunched Cable XLPE insulated screened PVC bedded galvanised steel strip or wire armourred electric power cable (Heavy duty ) with aluminium conductor 1100 volts grade, cross sectional area 120 sqmm 4 core suitable for 11KV earthed systems all as specified and directed. |
| 24 | Re-routing /Re-Laying of old LT cables in trenches or passing through pipe, cross sectional area upto 50 Sqmm 3.5/4 core 1100 volts grade heavy duty cable XLPE Insulated multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed of following size Note:-Earth work, sand cushing etc paid separately in relevant items. |
| 25 | Re-routing /Re-Laying of old LT cables in trenches or passing through pipe, cross sectional area 50 Sqmm to 120sqmm 3.5 core 1100 volts grade heavy duty cable XLPE Insulated multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed of following size Note:-Earth work, sand cushing etc paid separately in relevant items. |
| 26 | Re-routing /Re-Laying of old serviceable LT cables in trenches or passing through pipe, cross sectional area 150 Sqmm to 240sqmm 3.5 core 1100 volts grade heavy duty cable XLPE Insulated multi stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or strip and over PVC sheathed completeNote:-Earth work, sand cushing etc paid separately in relevant items. |
| 27 | Boring under road and foot path for inserting 40/80 mm bore GI tubing for drawing UG cable using any method process complete all as per specified and directed. Note- GI Pipe to be paid in separate items . |
| 28 | Material and labour for 80 mm bore galvanized iron tube medium grade for cable protection pole ,plinth protection, road crossing, trenches, footpath etc, complete all as specified and directed including clamps, nut bolt and washers complete all as per specified and directed |
| 29 | Material and labour for 40 mm bore galvanized iron tube medium grade for cable protection pole ,plinth protection, road crossing, trenches, footpath etc, complete all as specified and directed including clamps, nut bolt and washers complete all as per specified and directed |
| 30 | Supply and fix in replacement of LT straight through joint out door type of size 6-16 sqmm to 120 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed. |
| 31 | Supply and fix in replacement of LT straight through joint out door type of size 25 to 50 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed. |
| 32 | Supply and fix in replacement of LT straight through joint out door type of size 70 to 120 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed |
| 33 | Supply and fix in replacement of LT straight through joint out door type of size 150 to 185 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed |
| 34 | Supply and fix in replacement of LT Indoor/Outdoor End termination joint out door type of size 6sqmm to 16 Sqmm 4/3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed |
| 35 | Supply and fix in replacement of LT Indoor/Outdoor End termination joint out door type of size 25sqmm to 50 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed |
| 36 | Supply and fix in replacement of LT Indoor/Outdoor End termination joint out door type of size 70 sqmm to 120 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed |
| 37 | Supply and fix in replacement of LT Indoor /Outdoor termination joint out door type of size 150 sqmm to 185 Sqmm 3.5 core suitable for PVC / XLPE power cables complete all as per specified and directed |
| 38 | Supply and fixing in replacement of MCCB 4 Pole 320 Amp 415 volt breaking capacity 18 KA with adjustable thermal and megnetic setting complete all as per specified and directed |
| 39 | Supply and fixing in replacement of MCCB 4 Pole 250 Amp 415 volt breaking capacity 18KA with adjustable thermal and megnetic setting complete all as per specified and directed |
| 40 | Supply and fixing in replacement of MCCB 4 Pole 200 Amp 415 volt breaking capacity 16 KA with adjustable thermal and megnetic setting complete all as per specified and directed |
| 41 | Supply and fixing in replacement of MCCB 4 Pole 125 Amp 415 volt breaking capacity 16 KA with adjustable thermal and megnetic setting complete all as per specified and directed |
| 42 | Supply and fixing in replacement of MCCB 4 Pole 63 Amp 415 volt breaking capacity 16 KA with adjustable thermal and megnetic setting complete all as per specified and directed |
| 43 | Supply and fixing ONLOAD Changerover 400 Amps 4 Pole 415 volt with adjustable setting compete as per specification confirms to IES 60947 complete all as per specified and directed |
| 44 | Supply and fixing ONLOAD Changerover 200 Amps 4 Pole 415 volt with adjustable setting compete as per specification confirms to IES 60947 complete all as per specified and directed |
| 45 | Supply and fixing ONLOAD Changerover 125 Amps 4 Pole 415 volt with adjustable setting compete as per specification confirms to IES 60947 complete all as per specified and directed |
| 46 | Supply and fixing ONLOAD Changerover 100 Amps 4 Pole 415 volt with adjustable setting compete as per specification confirms to IES 60947 complete all as per specified and directed |
| 47 | Supply and fixing ONLOAD Changerover 63 Amps 4 Pole 415 volt with adjustable setting compete as per specification confirms to IES 60947 complete all as per specified and directed |
| 48 | Supply & fixing Steel tubular swaged poles 9 mtr type 410 SP-31 complete with cast iron base plate ,finial taper plug, bolts,nuts & screws complete all as specified and as directed by Engr-in-ChargeNote: Earth work, PCC work shall be measured & paid separately. |
| 49 | Supply and Fixing ACSR conductor on poles including stringing and fixing in position and binding to insulators and jumpers, complete all as specified and directed. |
| 50 | Fixing only LT overhead line of ACSR conductor of any Size and span not exc. 50 Mtr including binding with aluminium conductor and jumper including trimming/ pruning/ dressing the tree branches and cleaning or creepers from poles complete all as per specified and directed |
| 51 | Supply and fixing cross arms, bracing supports clamps,ms sheet from structural steel sections including nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts in any shape or size complete all as per specified and directed |
| 52 | M & L for painting to internal and external surface of LT Feeder Pillar Box/Panel Boards various sizes with two coats of synthetic enamel paint over a coat making necessary surface preparation by scrapping old painted surfaces with wire brush/emery paper complete all as specified and as dirtected. |
| 53 | Supply and fix in replacement of Mild steel barrel tower bolts, 300mm long stove enamelled black, bright bolt With connected accessories fixed on front and rear side of the Doors for locking of LT FP Boxes complete all as specified and as dirtected. |
| 54 | Material and labour in replacement of clamps and back plates fabricated from structural steel sections size of upto 1.5x2mtr including nuts, bolts, washers, welding, bending, drilling holes for bolts, in any shape or size inclusive of one primer coat, one under coat and one finishing coat of aluminium paint all complete all as specified and as dirtected. |
| 55 | Material and labour in replacement of MS sheet Min 3mm thick for making doors of panel boards/feeder pillar boxes including taking out the old damaged doors complete all as specified and as dirtected. |
| 56 | M & L Replacement of LT panel corroded / damaged doors of panel boards/feeder pillar boxes fornt side by cutting, bending, welding existing MS sheet to suit with the existing MCCB's compartment including providing hinges ,door locking system complete all as specified and as dirtected. |
| 57 | Material and labour in replacement of bus bar made out of aluminium strip as per existing suitable size(R-Y-B) colour insulated sleeve for phases and black colour for netural with suitable size of clamps made out of flat iron, nuts, bolts and washers including cutting, bending, welding etc and suitable as per existing complete all as specified and as dirtected. |
| 58 | M & L for replacement of rusted/broken GI earth wire of 4.0mm bore for guard on Overhead line by providing reels and clamps and any other items required for fixing as per site requirement complete all as specified and directed by Engr-in-Charge. |
| 59 | S & F Heat Aerosol fire extinguishing device for protection panel,bus bar box ,DB from fire apray release time lessthan/equal 6S protected space 0.4 cum complete all as per specified and directed |
| 60 | Supply and fix Hot press moulded SMC junction box IP 65 with double door hinged plain walls of size 200x140x90mm including bus bar with including making suitable size hole for cable entry complete with cable terminals/connectors and other fittings fixed on poles/wall with MS flat iron nut bolts, washers and double compressor metal glands of suitable sizes etc complete all as per specified and directed |
| 61 | S & F PVC copper cable FRLSH insulated multistranded size 6 sqmm 4 core complete connection as per site requirments complete all as per specified and directed |
| 62 | Supply & fix in replacement of digital power factor meter in existing APFC panels of sutable size having range of 1/5 A and 110v/230v/440v with all acessories all as directed by Engr-in-charge |
| 63 | Supply and fix in replacement of digital volt meter with inbuilt selector switch of suitable size of 0-500 V range in existing panel complete all as per specified and directed |
| 64 | Supply and fix in replacement of digital ammeter with inbuilt selector switch of suitable size 0-250 amps range in existing panel complete all as per specified and directed |
| 65 | Supply and fix in replacement of CTs of ratio 200/5A indoor resin cast ring type used on existing panel complete all as per specified and directed |
| 66 | Supply and fix in replacement of CTs of ratio 100/5A indoor resin cast ring type used on existing panel complete all as per specified and directed |
| 67 | Supply and fix in replacement of CTs of ratio 50/5A indoor resin cast ring type used on existing panel complete all as per specified and directed |
| 68 | Supply and fixing in replacement of LED type indicator lamp (RYB) (Set of three) complete all as per specified and directed |
| 69 | Supply and fixing in replacement of Spreaders For LT Line for 4 wire heavy duty complete all as per specified and directed |
| 70 | Supply and fix in repair synthetic insulating rubber matting ISI mark for 11KV 2.50mm thickness size of Mat 2mtr X 1mtr) of confirming to IS:15652-2006 complete fixing on floor with suitable pasting material complete as per specification as directed by EIC |
| 71 | Dismantling of existing damaged unserviceable earth pits, test points, GI wire / GI Strip / copper strip of any size and M & L for new earth pit with Cover ,existing earth strip clamps properly,clean the earth pit, new funnel complete asper site requirment directed by Engr-in-Charge |
| 72 | M & L earthing complete with galvanised steel earth plate electrode 60 x 60x 6mm burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edged of the plate not less than 1.5 mtr below normal ground level, connected to galavanised iron earth lead by means of bolt, nut, check nut and washer of galavanised iron strip 32x6mm as earthing lead as shown in Electrical Plate No 3 of SSR Part I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/ loose soil, earth pit in PCC 1:3:6 type C1 using 20mm stone aggreate, funnel, 40mm bore GI medium grade water pipe, 15mm bore GI light grade earth lead protection pipe, CI frame and cover, wire, copper lugs, wire mesh, charcoal or coke and common salt in alterative layer all around the earth electrode compacted thickness 15 cm including excavation of hard /dense soil and earth work pit cover including disposal of surplus soil to a distance not excessding 50m, complete testing on completion all complete as shown in electrical plate No 3 of SSR Part I 2009 all as directed by Engr-in-Charge |
| 73 | M & L for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 Nos, 8 mm bore 25 mm long hex head screw complete all as per specified and directed |
| 74 | M & L for Earth continuity conductor or main earthing lead fixed to wall /floor connection of earthing lead to equipment fixed to poles or any other indicated situation for loop earthing etc as required 32X6 MM bore galvanised iron strip complete all as specified and as dirtected. |
| 75 | M & L Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps bolts and nuts of approved for LT 440 volts, of size 25cm X 15cm complete all as per specified and directed |
| 76 | Only labour for cleaning the Surrounding area (not less than 2.5mtr X 2.5 mtr) of Two/Four pole structure, LT panel area cutting the bushes,grass by root and leveling the soils, dressing the cables and two coat white wash on the panel foundation ,earth pit near around the LT Panel etc complete all as per specified and directed |
| 77 | M & L for writing of LT panel number with black/blue colour on panels/feeder pillar box by professional painter with suitable size, height and width complete all as per specified and directed |
| 78 | M & L for praparation and clening of existing surface and applying two coat White wash on prepared surface complete as per specified and as directed by Engr-in-Charge |
| 79 | Supply and fix in replacement of fornt mounting Add on auxilary contact blocks of MO type as per existing NO+NC includling 2.5mm copper control cable upto 0.5 meter complete all as per specified and directed |
| 80 | Supply and fix in replacement of Side mounting Add on auxilary contact blocks of MO type as per existing NO+NC includling 2.5mm copper control cable upto 0.5 meter complete all as per specified and directed |
| 81 | Supply and fix in replacement of Spare coil contact as per sample as per site requirment complete all as per specified and directed |
| 82 | Supply and fix in replacement of Spare coil contact MNX40/MO40 of L&T complete all as per specified and directed |
| 83 | Supply and fix in replacement of Time switches Type FMT/Quartz daily for 110VAC-24 VAC din mounted 150Hrs battery backup 50Hz for switching loads on and off repetitively in equal intervals complete all as per specified and directed |
| 84 | Supply and fix in replacement of Castell type Panel door lock set stainless steel surface mounted using suitable fasteners single key operated complete as per specified and dirtected |
| 85 | Supply and fix in replacement of Tear drop Knobs upto 400Amp suitable as per exisiting complete |
| 86 | Supply and fix in replacement of Aluminium cable lugs for size Pin/bottle type 6 to 16 sqmm as per sepcified as dirtected |
| 87 | Supply and fix in replacement of Aluminium cable lugs for size Pin/bottle type 25sqmm to 35 sqmm complete all as per specified and directed |
| 88 | Supply and fix in replacement of Aluminium cable lugs for size Pin/bottle 50 sqmm to 120 sqmm complete all as per specified and directed |
| 89 | Supply and fix in replacement of cable gland for different size per site requirement complete all as per specified and directed |
| 90 | M & L for painting with two coats of synthetic enamel paint over a coat of cross arms, bracing supports clamps,ms sheet from structural steel sections including steel poles and mud clay on RCC pole( 2 Pole & 4 Pole also including) complete all as per specified and directed.Note :- The item included in the painting 3 Nos 30 cm wide bands black & White synthetic enamel paint in alternate layer upto 1.0 mtr high above foundation and writing the pole Nos in 5 cm wide on base of Black colour with HT/LT as per direction of Engr-in-Charge. |
| 91 | Supply and fixing stay assembly complete with accessories as shown in electrical plate No. 1 of MES schedule part I with and including 16 mm bore stay rod, stay clamp and galvanized stay strand of size 7/4 mm including necessary clamps, nut, bolts etc complete all as per specified and directed |
| 92 | Dismantling of unserviceable insulators of any type/size and Supply and fix shackle type vitreous white, brown or green insulators for working pressure 1100 volt of 90 mm bore and 75 mm height including galvanized mild steel straps of 31x3 mm size 12 mm bore insulator bolts, nuts & washers as per specification complete all as per specified and directed |
| 93 | Dismantling of unserviceable insulators of any type/size and Supply and fixing pin type porcelain, vitreous, white, brown or green insulators including galvanized mild steel spindle, two galvanised iron washers and one galvanized iron nuts, 100 mm height 65 mm bore for 1100 volts grade as per specification complete all as per specified and directed |
| 94 | Dismantling of unserviceable insulators of any type/size and Supply and fixing loop type insulators vitreous, porcelain white, brown or green large size with over all dimensions of 90 x 140 mm clearance or hole 25.5 mm as per specification complete all as per specified and directed |
| 95 | Perventive maintance of LT panels/feeder pillar box/Electric meter panel box comprissing of following works to be carried out as under:- (i) Cleaning of panel boards by hand/air blower after switching off main supply.(ii) tighting of all electrical termination joints (iii) Dresing of internal control wiring and repairs of minor defects on the spot as directed by Engr-in-Charge. |
| 96 | Supply only white soft cotton clothes for cleaning of electrical equipments complete all as per specified and directed |
| 97 | Supply and laying for 12.5 to 40mm Graded stone aggregate in area of installation arround the panel area and substation or as dirtected after cleaning the existing ground surface and removing grass and unorganic particales all as reqd and as directed at site complete all as specified and as directed by Engr-in-Charge |
| 98 | M & L for trenches Cutting of road, hard standing, PCC in section size 45cm X 45 cm X 30cm use to laying of cable and making good surface in top layer with 100mm thick PCC 1:2:4 type B1 with sub base hard core 100mm thick size of stone boulder 40mm to 63mm complete all as per specified and directed |
| 99 | Cutting of tree branches of any type / size of trees, touching / approaching the electric OH lines / poles structures etc., by climbing on trees, cutting required number of branches of any size / girth protruding towards OH lines so as to keep tree branches clear / off not less than 1.5mtr away from any side of conductors on poles, removing cut branches from site and throwiing out at a place, where directed, not more than 250mtr away from the site all as specified and as directed. Note :- 1. Suitable ropes shall be used to hold the branches while cutting in progress to prevent branches falling on OH lines and causing damages. 2. In case of any damages to the OH lines / poles or any other structures, the same shall be repaired / rectified / made good by the contractor with out any extra cost. 3. Shut down of electric supply shall be taken before climbing trees. 4. The cut branches shall be removed from site and deposited at a distance not exceeding 250 mtr as directed. |
| 100 | Dismantling of unserviceable LT Panel of any type/size and removal from site. and Supply, Installing,testing and commissioning of LT Panel factory made Outdoor type (CPRI) as per latest IS mark with following minimum thickness - Load bearing member/Doors - 3mm, Non-load bearing member/internal partitions - 3mm, Glandplate/Base channel-3MM , board floor mounted, dust and vermin proof, 3 phase 4 wire with rated operational voltage 415V, rated insulation voltage of 1000V and Impulse withstand of 12kV and minimum internal Arc with-stand of 65kA, 500mSec as per latest IS mark, weather proof, with separate hinge door for each compartment with Operating handle & locking arrangement with back door common openable(screwed/Lockable), grouted in PCC 1:2:4 Complete. Painting as per defined 7 Tank process with epoxy powder polymerized at high temperature and aluminium busbar (TPN) suitable for 300A with double compression aluminium cable glands with the following accessories with IP 53 rating :- (a) Incoming -(i) MCCB 250 Amp 4 pole 415 V 35 kA rating (ii) Onload Changeover 4 Pole 250Amps 415V(b) Outgoing - (i) MCCB 160Amp 4 Pole 415V 18 kA - 01 Nos(ii) MCCB 100 Amp 4 pole 415V 18 kA - 02 Nos(iii) MCCB 63 Amp 4 Pole 415V 18kA - 01 Nos .(iv) Spare compartment for MCB - 01 nos . (v) LED indicating lamps for main supply (R-Y-B)(vi) Amp meter(vii) Volt meter(viii) Power Contractor |
| 101 | Dismantling of unserviceable LT Panel of any type/size and removal from site. and Supply, Installing,testing and commissioning of LT Panel factory made Outdoor type (CPRI) as per latest IS mark with following minimum thickness - Load bearing member/Doors - 3mm, Non-load bearing member/internal partitions - 3mm, Glandplate/Base channel-3MM , board floor mounted, dust and vermin proof, 3 phase 4 wire with rated operational voltage 415V, rated insulation voltage of 1000V and Impulse withstand of 12kV and minimum internal Arc with-stand of 65kA, 500mSec as per latest IS mark, weather proof, with separate hinge door for each compartment with Operating handle & locking arrangement with back door common openable(screwed/Lockable), grouted in PCC 1:2:4 Complete. Painting as per defined 7 Tank process with epoxy powder polymerized at high temperature and aluminium busbar (TPN) suitable for 300A with double compression aluminium cable glands with the following accessories with IP 53 rating :- (a) Incoming - (i) MCCB 200 Amp 4 pole 415 V 18 kA rating (ii) Onload Changeover 200 Amp (b) Outgoing - (i) MCCB 100 Amp 4 Pole 415V 16 kA - 02 Nos.(ii) MCCB 63 Amp 4 Pole 415V 16 kA - 02 Nos(ii) SPN 16Amp - 01 Nos (iii) Spare compartment for MCCB - 01 nos . (iv) ED indicating lamps for main supply (R-Y-B)(v) Amp meter(vi) Volt meter(vii) Contractor Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 04, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysAug 29, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender