Power Government Departments Closing in 17 days TDR #56821930

Tender For Creation Of 6.3 Mva 33/11 Kv Receiving Station At Chassanatehsil Mahore Block Chassana Of District Reasi .Scheme Code : Pddss2627100648important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Wor

Issued by Government Departments · Udhampur, Jammu and Kashmir
Tender Value
Ref. Documents
Estimated cost
Bid Submission
24 Aug 2026
17 days left
EMD
10.92 Lakhs
Bank guarantee accepted
Document Fee
5000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Udhampur → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Creation Of 6.3 Mva 33/11 Kv Receiving Station At Chassanatehsil Mahore Block Chassana Of District Reasi .Scheme Code : Pddss2627100648important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Works Including Testing And Energisation , Specifically Mentioned Or Not In Above Description But Required At Site Shall Be Deemed To Be Included And Covered In The Quoted Rates.

BOQ

Name of Work:- Creation of 6.3 MVA 33/11 KV Receiving Station at ChassanaTehsil Mahore Block Chassana of District Reasi .Scheme Code : PDDSS2627100648Important Note : All allied and associated works required for successful execution of above items of works including testing and energisation , specifically mentioned or not in above description but required at site shall be deemed to be included and covered in the quoted rates.
Sl. No. Item Description
1Survey, Supply, Installation , Testing and Commissioning for 33 kV Line BAY (LILO) of existing Darmarhi Line at Receiving Station SarBagha
233 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Crompton Greaves,Pascal,Stelmec,Yamuna etc .
333kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ).
433kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ).
533 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase
630 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less
733 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc .
833 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m station type
9CONTROL CABLES : i) 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. a
10ii) 4 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
11iii) 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
12Galvanised Steel Structures
13Galvanised Nuts & Bolts
1433 KV yard concreting and metalling providing supply and laying 100 mm thick PCC1:4:8 using 20 mm normal course aggregating and spreading 100 mm three layer of 20 mm single size crushed / broken stone (One Line Bay) along with Foundation of all Electrical equipments of LILO
15Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay)
16Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat.
17Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering
18Survey, Supply, Installation , Testing and Commissioning for 33 kV LINE BAY at Receiving Station Chassana
1933 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m
2033KV Lightening Arrestors(33 KV 10 KA Polymer, ZnO, Gapless)
2133 KV voltage transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase
2233kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
2333kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
2412 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
254 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
262 core 2.5mm2 Control Cable copper Armoured, 1.1KV Grade, ISI, FRLS of make Havells, Polycab, KEI etc.
27Galvanised Steel Structures
28Galvanised Nuts & Bolts
29Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay+ One No Transformer Bay)
30Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat.
31Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering
32Survey, Supply, Installation , Testing and Commissioning for TRANSFORMER BAY at Receiving Station Chassana
3333kV VCB (36KV,1250 A,26.2 KA, outdoor type Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc .
3433kv C&R Panel along with O/C, E/F relays , mimic diagram, Voltmeter, Ammeter, Annunciation windows with annunciation relays, 3-Phase Tri-Vector Smart meter- % amps, DLMS Compliant including earthing. Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc .
3533KV Current Transformer (CTR 250/125-5A,1- phase multi-core, outdoor,1No. Per phase) on along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
3633 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m
3733KV Lightening Arrestors(33 KV 10 KA Polymer, ZnO, Gapless)
3833kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
3912 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
404 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
412 core 2.5mm2 Control Cable copper Armoured, 1.1KV Grade, ISI, FRLS of make Havells, Polycab, KEI etc.
42Galvanised Steel Structures
43Galvanised Nuts & Bolts
44Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay+ One No Transformer Bay)
45Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat.
46Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering
47SITC of POWER TRANSFORMER (6.3 MVA)
4833/11kV, 3 phase ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections (6.3 MVA) as per latest IS Standards
4912 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
506 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
512 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
52SITC of 11 kV INDOOR SWITCHGEAR OF 33/11 kV SUBSTATION
5311 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Seimens, Megawin, Pascal etc,:- For 6.3 MVA Power Transformer (1+4) including Smart meters Trivector.
5411kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (5Sets Station type 1 for Power Tx))
5511 kV 3- Core XLPE 185 mm² armoured, FRLS
5611 kV 3- Core XLPE 300 mm² armoured, FRLS
5711 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core(Indoor)
5811 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core (outdoor )
5911 kV Indoor Heat Shrinkable Cable Termination Kits for 300 sq mm Cable (indoor)
6011 kV Indoor Heat Shrinkable Cable Termination Kits for 300 sq mm Cable (outdoor)
6111 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch.
6211kV DO set , AB Switch 3-Phase, 3-Pole, 200 Amp
63Galvanised iron of sorts
6409 Mtr. Long Pole(ST-410 SP33)
6595 mm² PVC LT Cable 4 Core, armoured, FRLS
66Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole
67Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip for ST poles
68100 KVA Auxillary Transformer
69Earthing for Auxillary Transformer (complete as per REC standards)
70MCCB 200 Amp with box
71COMMON MISCELLANEOUS WORKS
72HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room
73Providing & Laying of Earthmat by Using G.I. Flat of Size 50 mm x 8mm as grounding Conductor.The mesh Size shall 2 m x 2 m.The Burial Depth of G.I. Flat Shall be minimum 600 mm.The work involves the excavation of trenches for burial of grounding flat,Laying of G.I.Flat including welding & Backfilling of Trenches
74Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip.
75Supply, Errection, Testing & commisioning of Battery Bank 32v 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant of make Exide Amaron or Tata etc.
76Supply, Errection, Testing & commisioning of Float-Cum-boost Charger with full wave rectification for 220v, 1 Phase 50HZ AC input supply suitable for charging of Battery Bank 32V, 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant.
77Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories
78Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A),Rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories
79Fire Extingiusher Co₂ Type of 4.5 kg capacity for control room (with ISI mark)
803 Sand Bucket Fire Extingiusher including MS stand
81Civil /Misc Works
82Earthfilling/Cutting upto desired FGL (As decieded by Engineer incharge during detailed Engineering)by Way of Removing Weeds,Wild Grass and endulation if any including disposal of surplus material
83Construction of 3000 mm wide Road,with 300 mm thick dry well compacted local soil of 95% Procter density ,with 100 mm thk P.C.C. 1:4:8 Layer in middle,with 100 mm thk R.C.C. (1:2:4) in top layer with 8 mm tor steel @ 300 mm c/c bothways in middle of top layer shall be provided.Polythene sheet of thk 125 micron shall be provided between middle & Top Layer.Expansion joint shall be provided at every 3000 m length.115 MM Thk side brick masonary shall be provided on both sides of road. (Reference Drawing Enclosed)
84Development of Side drains of road 300 mm x 300 mm section with side walls & floor 150 thk P.C.C. 1:3:6 & 12 mm thk plaster 1:4 complete finished job
85Ornamental Landscapping of Free land/space along with Plantation of ornamental trees & Grass complete job to the satisfaction of engineer in charge
86Compound Walling of identified land by way of Mass Concrete in Foundations and 228 mm bricks of 2 metre height and plastering. (150 RM)
871. Construction of R.C.C. Pillars (M-20) with square footing of size 1300 x 1300 x 200 mm & Pedastal of Size 230 x 300 x 2800 mm.The reinforcement in footing shall be 10 mm dia tor steel steel at 200 c/c bothways in bottom of raft & 8 mm dia tor steel at 200 c/c both ways at top of raft.4 no 12 dia tor steel rods shall be provided in pedastal with 8 mm dia stirups at 200 c/c.The rates shall include cost of excavation,all material,Shuttering etc. R.C.C. Pillars shall be spaced @ 3000 mm c/c.
882. Plinth Beam of size 230mm x 300 mm with four 12 mm dia tor steel members with 8 mm dia stirups at 200 c/c including cost of form work
893. Brick Masonary work (Cement sand mortar 1:5) 230 mm thk & 2000 mm high.
904. 12 mm thk Cement plaster 1:4 on both sides of Brick wall
915. Providing & Fixing of M.S.Angle 50mm x 50mmx 6mm Y shaped Posts embeded in R.C.C. Pockets of size 100 mm x 100 mm x 300 mm
926. Providing & Fixing of 3 rows of Barbed wire on Angular Posts
93Galvanized Chain link Fencing of 33 kV Yard of Substation by way of Mass Concrete in Foundations and chain link fencing of 6 ft height (Size 75 mm x 75 mm made of G.I.Wire 3.15 mm in diamond pattern) using Fencing posts of M.S.angle size 65x65x6mm embedded in 1:2:4 C.C. Block of Size 400 mm x 400 mm x1000m at an average spacing of 2.5 m c/c.The chain Link mesh fencing shall be secured to M.S.Angle post with flat iron strip of size 50x6 mm on both sides.There shall be a provision of 3 rows of 2 strand Barbed wire on top of fencing post. at GMC Receiving Station and dairy Farm Receiving Station Line bay.
94Trench Excavation between C.C.Blocks holding angle Posts of size 300 mm x 400 mm ,Laying of 75 mm Thk lean Pad 1:4:8 ,Plum Mass concrete in 1:3:6(30% Boulders) of height 425 mm & width 400 mm with 50 mm Band Coping on Top in C.C.1:2:4 complete job including cost of shuttering & Curing.
95Providing & Fixing of double frame Gate(Min 4000 mm wide & 2000 m high) with 50 dia G.I.Tube in outer frame & 10mm/20 mm Sq rods welded to tubular frame (Final Design to be approved by Engineer incharge).There shall be provision of drop Bolts of 16 mm dia M.S. Rod & suitable Concrete Pockets for holding Bolts.Wheels at bottom & flat arrangement for smooth opening & closing shall be provided
96Construction of R.C.C. Pillars for holding of gate including cost of material & labour.(Design of Reinforcement & sizing shall be finalised by Enginer incharge
97RCC Cable trench (1:2:4) including excavation and disposal of un-wanted soil. for laying of 11 KV XLPE Power Cable and control cable from power transformer, VCB and other equipments to control room and for outgoing cables from control room to outgoing structures including cable duct covers (cable duct covers should be covered with Angle Frames using angle 45x45x5 mm and 8 mm Tar Steel @ 200 c/c & M-20 Concrete)
98BUILDING: A. Control Room Buildingon ground floor complete with Column and Beam structures with 1 no J.E. Room , 1 Store room, 1 Battery Room and a main hall including aluminium windows, cable ducts for power and control cable, Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures)White Washing of entire building , painting of doors and windows etc. Overhead /undergroung water Storage tanks . 2 nos of office tables and 6 nos of chairs , staircase . Water Supply . Septic Tank complete with Sanitary Fittings including kota stone floor .complete in all respects
99BUILDING:B .Staff Quarters on 1st floor with Column and Beam structures including Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures) White Washing of entire building Complete in all respectsainting of doors and windows etc. Overhead water Storage tanks . Pantry Room with all the Fittings. Water Supply . including marble flooring ,Furniture(including 2 single Beds, 4 Chairs, 2 table, Matress, Curtains)(Note: The Contractor shall submit the building drawing in all respects i.e. structral / architechural prepared by authorised Architect for approval from the dept for execution of works.)
10033/11 kV Power Transformer Foundation as per REC standards
101Auxillary Transformer Foundation as per REC standards
10233 kV Equipment Foundation & Gantry foundation as per REC standards
10333 KV Yard Concreting and metalling with 1: 4 :8 with 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick.
10433 kV Yard Lightening ( 100 Wt LEDs on 9 mtr ST poles ) complete with earthing , cement bottoming GI brackets, control box , cable etc (5 Nos.)
105Safety Tool kit
106Rubber Mats( 2 mtr x 2 mtr x 25 mm)
107Main Gate
108Conventional Earthing -GI Plate Earthing with 600mm X 600 mm X 6 mm, GI Plate, GI Flat 50 x 6 mm, GI Pipe, 40 mm Dia with Charcoal salt & good earth 10 ft deep pit etc. as per REC standards . Complete job
10933 KV Hand Gloves(set of 2)
11011 KV Hand Gloves(set of 2)
111RainCoats
112Safety Belt
113Gum boots
114Safety Helmet for electrician
115Digital Meggar 5000 mega Ohm
116Emergency light/ Torch 5 Watt chargeable
117Multimeter
11833KV high voltage live phase detector
119Extendable Aluminium Ladder 25 feet
120Aluminium Bus Bar 75 x 10 mm
121GI Flat 50 x 6 mm and 20 x 5 mm for risers and earthing of cable trenches and yard fencing.
122Earthing Rod (set of 3)
123Survey, Supply, Installation , Testing and Commissioning for ERECTION OF 33 kV LINE ON 11 Mtr. ST POLES ( 12 KM approx)
124Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
125GI Channel iron X-arm of different sizes including clamps,Ties and braces for multi pole structures
126GI Channel iron V cross-arm with top bracket of different sizes including clamps,Ties and braces for single pole structures
12733kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
12833kV Polymeric composite Disc Insulator with fitting 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
129PG clamps for 100 mm2 ACSR Conductor
130Galvinized Nuts and Bolts
131Danger Plates with Clamps
132Anti-Climbing Device with Clamps
133Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip.
134Painting of Poles with Red Oxide and aluminium paint (min 2 coats each)
135Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) including 5 No existing Poles
136Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
137100 mm2 ACSR conductor
138Guard netting
139Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job.
140Out Sourcing of Manpower for Manning and operation of 33/11 KV R/Stn. Along with allied 33 KV Line for 3 Years
141Survey, Supply, Installation , Testing and Commissioning for ERECTION OF 11 kV LINE ON 8 METER ST POLES ( 2 KM approx) To be vetted by AEE Sub Div. Darmarhi ED- Reasi
142Supply, Transportation, Erection of 8 Mtr Long ST Poles (ST410-SP15) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
143GI Channel iron X-arm of different sizes including clamps,Ties and braces
144GI Channel iron V cross-arm including clamps
14511kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
14611V Polymeric composite Disc Insulator with fitting 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
147PG clamps for 50 mm2 ACSR Conductor
148Galvinized Nuts and Bolts
149Anti-Climbing Device with Clamps
150Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip.
151Painting of Poles with Red Oxide and aluminium paint (min 2 coats each)
152Cement bottoming 1:2:4 mix as per REC standards .45cum/pole (to be done during erection of poles)
153Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
15450 mm2 ACSR conductor
155Guard netting
156Creation of Isolation points along the line Complete job. Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0

AI Tender Summary

OUR REF NO 56821930
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 24-08-2026
Authority
Authority Name Power Development Department
Work Description Tender for Creation Of 6.3 Mva 33/11 Kv Receiving Station At Chassanatehsil Mahore Block Chassana Of District Reasi .Scheme Code : Pddss2627100648important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Works Including Testing And Energisation , Specifically Mentioned Or Not In Above Description But Required At Site Shall Be Deemed To Be Included And Covered In The Quoted Rates.
Basic Detail
Tender No 18A of 2026-27
Bidding Type Tender
Location
City Udhampur
State Jammu and Kashmir
Key Dates
Publish Date 04 Aug 2026
Submission Date 24 Aug 2026
Open Date 25 Aug 2026
Finance
Tender Value Ref. Documents
Tender Fee 5000
EMD 10.92 Lakhs
Exemption Not Available
Document List
75064739-5f2f-4726-9203-fcde1833e549.html
BOQ_1056512.xls
Checklist.pdf
enitChasana.pdf
SBDnew.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 04, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Aug 25, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 18 days

Tender Documents

Download All (ZIP) ↓
html

75064739-5f2f-4726-9203-fcde1833e549.html

xls

BOQ_1056512.xls

pdf

Checklist.pdf

pdf

enitChasana.pdf

pdf

SBDnew.pdf

pdf

Tendernotice_1.pdf