Defence Statutory Bodies & Commissions/Committees Closing in 18 days TDR #56819441

Tender For Rep/Repl Of E/M Installations Earthing Lightening Protection System And Allied Works And Rep/Repl Of Electrical Wiring Incl All Connected Electricial Fittings And Fixtures At Takshasila, Aima, Sree Kumar Hall And Other Trg Area Under Ge(I)

Issued by Statutory Bodies & Commissions/Committees · Ganjam, Odisha
Tender Value
Ref. Documents
Estimated cost
Bid Submission
27 Aug 2026
18 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ganjam → Odisha
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Rep/Repl Of E/M Installations Earthing Lightening Protection System And Allied Works And Rep/Repl Of Electrical Wiring Incl All Connected Electricial Fittings And Fixtures At Takshasila, Aima, Sree Kumar Hall And Other Trg Area Under Ge(I) Gos.

BOQ

Name of Work:- REP/REPL OF E/M INSTALLATIONS EARTHING LIGHTENING PROTECTION SYSTEM AND ALLIED WORKS AND REP/REPL OF ELECTRICAL WIRING INCL ALL CONNECTED ELECTRICIAL FITTINGS AND FIXTURES AT TAKSHASILA, AIMA, SREE KUMAR HALL AND OTHER TRG AREA UNDER GE(I) GOS.
Sl. No. Item Description
1M&L for Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x6mm thick burried directly in ground (earth pit not less than 2.25 m deep below normal ground level, connecting to the Galvanised iron earth lead 32x6mm size, by means of bolts, nuts, check nuts and washers of galvanised iron and 32x6 mm earth lead protected by provision of GI light grade pipe 40 mm bore including provision of concrete pit in PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregates with 40 mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4kg/Sqm) and frame of angle iron 25x25x3 mm with lugs-02 Nos and with 6 mm dia MS bar handle made to shape, GI medium grade 20 mm bore pipe for watering perforated at bottom 1.5 meter long placed on top edge of earth plate common salt and charcoal filling, test point with fixing arrangements, funnel wire mesh and earth work in hard/dence soil returning filling in and removal of surplus soil to a distance not exceeding 50 m, all as per electrical plate No 5 of SSR-2010 Part-I and connecting to earth test point all as specified and directed.
2Supply and fix Single pointed air termination aluminium rod , 12 mm dia, 300mm long with necessary fixing arrangements as per site requirements complete all as specified and directed.
3Supply and Fixing aluminium strip 25 mm x 3.15 mm complete with saddles and fixing screws as roof conductor complete all as specified and directed.
4Supply and fix Tubes light grade galvanised of size 32 mm with all fittings and fixed complete for suuporting the air temination rod and protection of GI strip complete all as directed
5M & L for Test point terminal block made of gun or phosphorus bronze size 75 x 75 x 25 mm, drilled and secrewed including 3 nos 8 mm dia 25 mm long hex. Head screw including removal old extg unsv one complete all as directed complete.
6Supply and fixing of earthing pit cover made out of cast iron painted with black colour with weight upto 3.5 Kg of suitable size complete all as specified and directed
7Supply and fixing of earthing pit cover made out of 40 mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4kg/Sqm) with handle of any suitable size as per site requirement complete all as specified and directed
8Supply and fixing of concrete earthing pit in PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate complete all as specified and directed
9M&L for Galvanised iron strip 32 x 6 mm buried in ground or fixed on walls/poles with fixing arrangement of nut bolt as required complete all as specified and directed
10M&L for testing of earthing pit, noted down the reading and if desired value does not come pouring of salt water by mixing common salt in water and retesting the earthing value, painting to the earthing pit, writting the earthing value and date of testing over the earthing pit cover complete all as specified and directed
11Supply and fix procelain insulators suitable for fixing of earthing strip of any size to caryy lightning resistance complete all as specified and directed.
12M&L replacement of Air Circuit Breaker Mannual fixed type 630 Amp 50 KA connecting up to the LT panel complete all as specified and directed.
13M&L in repairs danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete
14M & L for removing vegitation, grass, scrubs and bushes growing in Sub station yard along with fancing by mannually / mechanically and keep the sub station yard neat and clean complete all as specified and as directed. Note :- Unit rate quoted deemed to include to keep the installation neat and clean through out the period of contract and each cleaning will be measured and paid separately.
15M & L for graded coarse aggregate (broken stone or boulders) of size 40 mm in sub - station yard for laying all as directed and specified.
16Supply/ Lay dry river sand /m -sand in trenches for cable protection all as directed.Note : Punned thickness only will be measured & Paid
17Taking out old UNSV and Supply, laying, jointing and testing of XLPE insulated, armoured, heavy duty LT under ground cable 1100 Volts grade with aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed :-(a)10 Sqmm 2 Core
18All as per item no 17 but for 16 Sqmm 4 Core.
19All as per item no 17 but for 120 Sqmm 3.5 Core
20All as per item no 17 but for 150 Sqmm 3.5 Core
21All as per item no 17 but for 185 Sqmm 3.5 Core
22All as per item no 17 but for 240 Sqmm 3.5 Core
23Taking out old unserviceable PCC/steel tubular pole 9 mtrs long and supply and fixing Galvanised steel tubular double swan neck poles with base plate , bolts, nuts, screws as specifed 9 mtr long and erecting in position all as specified and directed with and including marking of pole number with black paint in yellow circle, complete, all as specified and directed.
24Excavation in trenches n .exc 1.5 mtr wide and not exec 1.5 mtr depth and getting out in looses/soft soil complete all as specified
25Returing filling in incl spreading leveling, watering and well ramming in layer not less than 25 cum each layer all as specified.
26Removing excavated material to a distance not exc 50M and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified
27Supply and laying double wall corrugated (DWC) HDPE pipe 50 mm outer dia for protection of UG cable as per IS: 16205 (part 24) of 2017 complete all as specified.
28Supply and laying double wall corrugated (DWC) HDPE pipe 63 mm outer dia for protection of UG cable as per IS: 16205 (part 24) of 2017 complete all as specified
29Supply and laying double wall corrugated (DWC) HDPE pipe 90 mm outer dia for protection of UG cable as per IS: 16205 (part 24) of 2017 complete all as specified
30M & L for tube light grade galvanised with all fittings laid along the pole/in trenches / under road or floor of 50 mm bore including removing the rusted old one complete all as specified and directed.
31M & L for tube light grade galvanised with all fittings laid along the pole/in trenches / under road or floor of 80 mm bore including removing the rusted old one complete all as specified and directed.
32M&L Checking /finding out or locating fault of existing LT UG cable laid in under ground /on poles/ walls or any situvations or location inside Gopalpur Mil station up to Vijaya dhar gate and restoring power supply within 4 Hrs period after receiving the call/ Msg from concerned JE E/M or in chain of command.The job includes excavation,Earth work, returning filling and removal, Meggaring /insulation resistance checking ,intermittant jointing of existing cables with new cables with proper LT straighjt through joints etc to restore power supply in all respect including cutting of road path and making good etc all as directed. Note:- 1:- Excavation / earth work ,new cable,cable protection pipes, filling will be measured and paid seperately.Note ;- 2 :- If the fault not rectified in the specified time limit double the rate of job as penality will be debited to contr.(3) Break down will be attended any time round the clock including sunday/ holidays and any weather conditions,(4) Excavation more than 5 cum only will be measured and paid seperately
33Supply and fixing earth test resistance clamp type Current Range 0–600 A True RMS Yes AC Or DC Measurement AC/DC Jaw Opening 55 mm Max Voltage Range 0–1000 V Safety Category CAT III 600 V Display Type Digital all as specified and directed by Eng-in-charge.
34M&L for Chemical earthing complete for earthing test point with copper earth plate 90X60cmX5mm and copper earth strip 50X6mm electrode in ground (Earth pit not less than 2.25 metre below normal ground level ) with top edge of the plate not less than 1.5 meters below normal ground level, connected and including copper strip 25mm x 4mm (upto the body of euipment ) by means of copper bolts, nuts, check nuts and washers, earth plate surrounded by picked layers of earthing chemical 15 cm thick, all ground top and bottom and watering pipe 20mm bore of GI pipe medium grade with funnel, testing on completeion including PCC chamber (1:3:6) using 20mm grade stone aggregate and 50mm thick cover with RCC 1:2:4 type B-1 using 20mm grade stone aggregate and 8mm dia deformed TMT bars @ 10 cm C/C both way including form work and MS frame using MS angle of size 45mm x 4 mm x 5mm complete all as shown in electrical plate No. 3 of MES schedule 1991 Part-I
35Supply and fix copper strip of size 20 x 3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground level complete all as specified and directed
36Supply and fix Air Termination, single pointed copper rod 12mm dia and 300mm long complete all as specified and directed
37Taking down carefully copper/aluminium point wiring (light,fan,bell, socket or power) complete,including fixtures and fittings such as switches, ceiling roses, holders,regulators, sockets, tube light fittings i.e removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made for conditions separately ) and including making good the disturbed surfaces to match with existing surface and colour shade with proper putty for smooth finishing without andulations complete all as specified and directed.( Note:- All credit materials should be deposited in MES yard as available on work site the same materials should be issued to contractor through gate pass as per contract schedule of credit materials against contract agreement or taken on ledger with approval by accepting officer).
38Material and labour for cutting chasing,pinning of brick/ stone/concrete wall at any height wall cutting and chases for concealed wiring for 20/25 mm PVC conduit dia pipe,water tubing,etc and making good to facings where required and pointing in cement motor 1:3 to ends or edges of landigs,wall surfaces etc,cutting not exc 10 cm girth and including making good the disturbed surfaces to match with existing surface and colour shade with proper putty for smooth finishing with existing wall complete all as specified and directed
39M&L for point wiring using approved colour coding incl providing circuit wiring with 1.5 sqmm PVC insulated, FRLSH type, ISI marked,conf to IS-694/1990 unsheathed, multistranded, single core, copper cable 1100 volts grade cables drawn through in PVC Conduit 20/25 mm dia medium grade ISI marked (MMS) at any height/places and all accessories are concealed in walls / roofs / floors / ceiling etc. including suitable arrangements for flush mounting modular MS/GI boxes as per site requirement/suitable for modular top cover and frame for fixing of modular switches,sockets,fan regulators, blank plate etc and including 1.5 Sqmm PVC insulated multistranded FRLSH type unsheathed(Green colour),single core cable with copper cable as earth continuity conductor and connecting to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour shade with necessary putty for smooth finishing complete all as specified and directed for the following:- One light point controlled by one 10amps switch.
40All as per item no 39 but for One fan point controlled by one switch 10 amps, and one regulator.
41All as per item no 39 but for One exhaust fan point controlled by one 10 amps switch .
42All as per item no 39 but for One 5 pin 6 amps socket point controlled by one 10 amps switch on independent board .
43All as per item no 39 but for One 5 pin 6 amps socket point controlled by one 10 amps switch on same board .
44All as per item no 39 but for One bell/buzzer point controlled by one bell push.
45All as per item no 39 but for One light point controlled by two 2 way switches/bed switch point
46All as per item No.39 above,but point wiring with 2.5 sqmm and earth conductor of size 2.5 sqmm incl circuit wiring complete all as specified and directed for the following:- One 6 pin 16/6 amps socket outlet point controlled by one 16/20 amps switch on independent board.
47All as per item no 39 but for One 6 pin 16/6 amps socket outlet point controlled by one 16/20 amps switch on same board.
48All as per item No.39 above ,but point wiring with 4.0 sqmm and earth conductor of size 4 sqmm incl circuit wiring complete all as specified and directed.
49M&L for point wiring using approved colour coding incl providing circuit wiring with 1.5 sqmm PVC insulated, FRLSH type, ISI marked,conf to IS-694/1990 unsheathed, multistranded, single core, copper cable 1100 volts grade cables drawn through PVC casing and caping 20/25 mm width double locking medium grade ISI marked (MMS) at any height and all accessories such as Tee,bend,short piece & elbow on surface on walls / roofs / floors / ceiling etc. including providing suitable arrangements for flush mounting modular MS boxes as per site requirement/suitable for modular top cover and frame for fixing of modular switches,sockets,fan regulators, blank plate etc and including 1.5 Sqmm PVC insulated multistranded FRLSH type unsheathed(Green colour),single core cable with copper cable as earth continuity conductor and connecting to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour shade with necessary putty for smooth finishing complete all as specified and directed for the following: One light point controlled by on switch
50All as per item no 49 but for One fan point controlled by one switch and regulator
51All as per item no 49 but for One exhaust fan point controlled by one switch.
52All as per item no 49 but for One 5 pin 6 amps socket point controlled by one 6 amps switch on independent board .
53All as per item no 49 but for One 5 pin 6 amps socket point controlled by one 6 amps switch on same board .
54All as per item no 49 but forOne bell point controlled by one bell push.
55All as per item no 49 but for One light point controlled by two 2 way switches.
56All as per item No.49 above,but point wiring with 2.5 sqmm and earth conductor of size 2.5 sqmm and incl providing circuit wiring complete all as specified and directed for the following:- One 6 pin 6/16 amps socket outlet point controlled by one 16 amps switch on independent board.
57All as per item no 56 but for One 6 pin 6/16 amps socket outlet point controlled by one 16 amps switch on same board.
58All as per item No.49 above ,but point wiring with 4.0 sqmm and earth conductor of size 4 sqmm incl providing circuit wiring complete all as specified and directed.
59Supply & fixing and fixing in repairs modular type switch 10 Amps, single pole,1way,1 module,240V,AC, ISI Marked complete all as specified and directed by Engr-in-Charge.
60Supply & fixing and fixing in repairs modular type switch 10 Amps ,2way,single pole,1 module,240V,AC, ISI Marked complete all as specified and directed by Engr-in-Charge.
61Supply & fixing and fixing in repairs modular type bell push 6 Amps,1 module, single pole, 240 volts,AC, ISI Marked complete all as specified and directed by Engr-in-Charge.
62Supply & fixing and fixing in repairs modular type switch 16 Amps, single pole,1way,1 module,240V,AC, ISI Marked complete all as specified and directed by Engr-in-Charge.
63Supply & fixing and fixing in repairs modular type socket shuttered type 6 Amps, 2/3 Pin combined 2 module,240V,AC ISI Marked complete all as specified and directed by Engr-in-Charge.
64Supply & fixing and fixing in repairs modular type socket 6 A/16 Amps, 6 Pin combined shuttered socket 2 module,240V,AC ISI Marked complete all as specified and directed by Engr-in-Charge
65Supply & fixing and fixing in repairs red color lighting indication lamp 6 Amps, single pole,240volts,AC,50 Hz suitable for 1 module ISI Marked complete all as specified and directed by Engr-in-Charge.
66Supply & fixing and fixing in repairs modular type step fan speed regulator 120W, 2 module,230volts,AC, 360 degree rotation 0 to 4/5 steps, ISI Marked complete all as specified and directed by Engr-in-Charge.
67Supply & fixing and fixing in repairs call bell AC, 230 Volts single pole, multi music type ISI marked, complete all as specified and directed by Engr-in-Charge.
68Supply & fixing and fixing in repairs call bell ding dong AC, 230 Volts single pole, multi music type ISI marked, complete all as specified and directed by Engr-in-Charge
69Supply & fixing and fixing in repairs angle lamp holder, insulated body with back plate for batten fittings complete all as specified and directed by Engr-in-Charge.
70Supply & fixing and fixing in repairs ceiling rose, 3 terminal ,PVC/polycarbonate body ISI marked, complete all as specified and directed by Engr-in-Charge.
71Supply & fix decorative box type 9/10 watt light fitting,blue coloured end caps, pre-wired providing single side LED tube 9 watt-01 No, and including PVC/Wooden round/square block -02 Nos and connected with LED fitting to ceiling rose and including removing old unserviceable fitting complete all as specified and directed by Engr-in-Charge.
72Supply and fixing, in repairs 20 watt LED PRIDE ULTRA batten white decorative type,high quality materials,240V,50Hz, and slim integrated body,easy to install,,PC diffuser and connected with LED fitting to ceiling rose terminal and incl removing old unserviceable fitting complete all as specified and directed by Engr-in-Charge.
73Supply & fixing, in repairs 40 watt LED PRIDE ULTRA NxT batten light fitting white lighting, high quality materials and intergrated design, PC diffuser, reliable and robust housing structure, easy to install, efficency 125 lm/w necessary arrangements for fixing with LED fitting to ceiling rose complete all as specified and directed by Engr-in-Charge.
74Supply and fixing in replacement recess mounting LED light fitting 2'x2 luminaire architectural recessed luminaire with CRCA housing and Molded PC diffuser with an unique angular optics for making the illumination easy on eyes for light comfort in office areas with UGR<=19. The luminaire should have a |color consistency SDCM< 5, CRI > 80 and choice of CCT: 5700K. Luminaire shall be designed to emit at least 3000 lumens and an efficacy of atleast 120Lm/W and maximum system wattage of 36 Watt, designed for ambient temp 45 deg C. The met allic electronic driver shall have a power factor >0.95, THD <10%, 4KV internal surge protection and the Ripple factor should be <5% to minimise the Flicker and Stroboscopic effect and Fixture should have an operating voltage range of 140-270VAC incl all as specified and directed by engineer in charge.
75S & F Energy efficient and energy saving new generation 10 watts LED bulk head light fitting IP-65 luminaire with opel diffuser pre-wired of luminaires including LED light driver and connected with LED fitting to ceiling rose terminal and incl removing old unserviceable fitting complete all as specified and directed by Engr-in-Charge.
76Supply & fixing , in repairs in sheet metal enclosure, 415 volts AC,TPN DB, 4 way,8+12 modules, flush mounting with copper busbar, 2 neutral/earth bars links and MCB incomer, and MCB SPN/SP/TPN as outgoing and complete for IP43&54 DBs protection and including removing old unserviceable DBs and incl making good the disturbed surfaces to match with existing surface and colour shade complete all as specified and as directed by Engr-in-Charge.
77Supply & fixing , in repairs in sheet metal enclosure, double door ,415 volts AC,VTPN DB, 4 way,8+12 modules, flush mounting copper busbar, 2 neutral/earth bars links and MCCB incomer, and MCB SPN/SP/TPN as outgoing and complete for IP43&54 DBs protection and including removing old unserviceable DBs and incl making good the disturbed surfaces to match with existing surface and colour shade complete all as specified and as directed by Engr-in-Charge
78Supply & fixing , in repairs sheet metal enclosure, double door, 240 volts AC,SPN,DB, 12 way, flush mounting with 100amps copper busbar,neutral bar,earth bar links and MCB incomer MCB SPN/DP and MCB SP as outgoing for IP 43& IP54 DBs protection nd including removing old unserviceable DBs and making good the disturbed surfaces to match with existing surface and colour shade acomplete all as specified and as directed by Engr-in-Charge.
79Supply & fixing in repairs sheet metal enclosure, double door, 240 volts AC,SPN,DB, 8 way, flush mounting with 100amps copper busbar,neutral bar,earth bar links and MCB incomer MCB SPN/DP and MCB SP as outgoing for IP 43& IP54 DBs protection nd including removing old unserviceable DBs and making good the disturbed surfaces to match with existing surface and colour shade acomplete all as specified and as directed by Engr-in-Charge.
80Supply & fix and fixing in repairs and sheet metal enclosure, with acrylic type double door, 240 volts AC,SPN,DB, 4 way, flush mounting with 100amps copper busbar,neutral bar,earth bar and MCB incomer,MCB SPN/DP, and MCB SP as outgoing for IP 43& IP54 DBs protection nd including removing old unserviceable DBs making good the disturbed surfaces to match with existing surface and colour shade complete all as specified and as directed by Engr-in-Charge.
81Supply & fix and fixing in repairs MCB SP 6 to 32 Amps 10 KA,\\"C\\" series,AC,240Volts,50Hz , ISI marked and including removing old unsv items complete all as specified and directed by Engr-in-Charge.
82Supply & fix and fixing in repairs MCB SPN 32 to 40 Amps 10 KA,\\"C\\" series,AC,240Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed by Engr-in-Charge.
83Supply & fix and fixing in repairs MCB SPN 40 to 63 Amps 10 KA,\\"C\\" series,AC,240Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed by Engr-in-Charge.
84Supply & fix and fixing in repairs MCB TPN 40 to 63/100 Amps 10 KA,\\"C\\" series,AC,440Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed by Engr-in-Charge.
85M & L for sub main wiring complete in repairs with 2 run of 10 sqmm single core copper conductor (ISI marked)cable 1100 volts grade, ISI marked,FRLSH type (conforming to IS-694/1990 as amended) PVC insulated, unsheathed,flexible,multi stranded colour coded cables drawn drawn through and including PVC conduit in concealed ISI marked medium grade(MMS) accessories such as Tee,corner, overlaping connector etc and including one run of 10 sqmm single core copper conductor cable flexible, PVC insulated, unsheathed, multistranded, 1100 volts grade, ISI marked,FRLSH type as earth continuity conductor connected to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour shade and complete all as specified and directed.Note : - Two run of 10 sqmm single core copper conductor cable and one run of 10 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit.
86All as per ditto item No .85, but 2 run x 6 sqmm+1 run earth wire complete all as specified and directed.
87All as per ditto item No 85, but 2 run x 4 sqmm+1 run earth wire complete all as specified and directed.
88All as per ditto item No .85, but 2 run x 2.5 sqmm+1 run earth wire complete all as specified and directed.
89All as per ditto item No .85, but 2 run x 1.5 sqmm+1 run earth wire complete all as specified and directed.
90Supply & fix and fixing in repairs suitable for flush mounting sheet steel enclosure metal clad plug and socket including MCB SP 20 Amps, 10KA 'C 'series, 230 Volts,50Hz suitable for AC's/Geysers complete all as specified and directed by Engr-in-Charge.
91Supply & fix and fixing in repairs MCCB, 125 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washers and including removing old unserviceable item complete all as specified and as directed by Engr-in-Charge.
92Material and labour for earthing complete with galvanised steel earth plate electrode 600mmX 600mmX 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 32 X 6 mm from earth electrode to test point or up to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate no 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade,GI funnel with wire mesh,including char coal, salt packed all around the earth electrode plate in layers,PCC earth pit chamber 1:3:6 type C1,RCC cover 1:2:4 type B1, including excavation,earth work in any strata and returning filling, removal of surplus soil and testing for required value complete all as specified and directed.
93S&F for PVC non-metalic rigid conduit incl boxes,junctions boxes 1 to 4 way & terminals but incl of all tees,bends,elbows,reducers,bell mouth tube ends and fixing accessories such as couplers lock nuts,saddles,pipes hookes etc ISI marked heavy duty of size 20/25 mm dia for LAN,telephone and TV connections cablesincluding cutting,chasses and making good disturbed surfaces to match with existing surfaces with plaster/putty and including removing of old unserviceable item complete all as specified and directed.
94Supply & fix and fixing in repairs copper conductor cable, PVC insulated, sheathed,flexible, multistranded,ISI marked, 1100 volts grade 3 core ;2.5 sqmm and including electric connection through PVC conduit in concealed/casing caping in surface from ceiling fan to ceiling rose and including removing old unserviceable item complete all as specified and directed.
95Supply & fix and fixing in repairs LED flood light light fitting of capacity 100 Watt LED, light fitting in aluminium PDC housing, toughened glass cover with IP-65 protection and including removing of old unserviceable item complete all as specified and directed by Engr-in-Charge
96Supply and fixing and in repairs galvanised metal flush box 1/2 module, ISI marked,and suitable for existing type as per site requirement and including removing old unserviceable item from existing loaction complete all as specified and as directed by Engr-in-Charge.
97All as per item No-96 ditto but meteal box 3 module
98All as per item No-96 ditto but meteal box 4/5 module
99All as per item No-96 ditto but meteal box 6 module
100All as per item No-96 ditto but meteal box 8/9 module
101All as per item No-96 ditto but meteal box 12 module
102All as per item No-96 ditto but meteal box 16 module
103All as per item No-96 ditto but meteal box 18 module
104Supply and fixing in repairs modular white/wood/glazed type cover plate with frame 1 module,ISI marked and suitable for existing type as per site requirement and incl screws,washears etc and including removing old unserviceable item from existing loaction complete all as specified and as directed by Engr-in-Charge.
105All as per item No-104 ditto but modular white/wood/glazed type cover plate with frame 2 module
106All as per item No-104 ditto modular white/wood/glazed type cover plate with frame 3 module
107All as per item No-104 ditto but modular white/wood/glazed type cover plate with frame 4/5 module
108All as per item No-104 ditto modular white/wood/glazed type cover plate with frame 6 module
109All as per item No-104 ditto but modular white/wood/glazed type cover plate with frame 8/9 module
110All as per item No-104 ditto but modular white/wood/glazed type cover plate with frame 12 module
111All as per item No-104 ditto but modular white/wood/glazed type cover plate with frame 16 module
112All as per item No-104 ditto butmodular white/wood/glazed type cover plate with frame 18 module
113Supply and fix in repairs of PVC/bakalite sheet round cover blanking plate as per site requirement with screws of existing fan junctions/ wiring junctions boxes etc Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56819441
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 27-08-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Rep/Repl Of E/M Installations Earthing Lightening Protection System And Allied Works And Rep/Repl Of Electrical Wiring Incl All Connected Electricial Fittings And Fixtures At Takshasila, Aima, Sree Kumar Hall And Other Trg Area Under Ge(I) Gos.
Basic Detail
Tender No GE/GOS/TOK/109 OF 2026-27
Bidding Type Tender
Location
City Ganjam
State Odisha
Key Dates
Publish Date 03 Aug 2026
Submission Date 27 Aug 2026
Open Date 03 Sep 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 80000
Exemption Not Available
Document List
6b9a9b96-060d-4c49-abd4-6f02a6eef46c.html
BOQ_876705.xls
Tendernotice_1.pdf
tender_docs.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Aug 03, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 27, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 18 days
Sep 03, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 25 days

Tender Documents

Download All (ZIP) ↓
html

6b9a9b96-060d-4c49-abd4-6f02a6eef46c.html

xls

BOQ_876705.xls

pdf

Tendernotice_1.pdf

pdf

tender_docs.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender