Tender For Capacity Addition Of 1 X 3.15 Mva Power Transformer Along With Its Switch Gear And Auxiliaries At Existing 33//11 Kv 3.15 Mva Smvd University Receiving Station Including Reconditioning Of Existing Infrastructure.Important Note : All Allied
Tender Overview
Project Description
Tender for Capacity Addition Of 1 X 3.15 Mva Power Transformer Along With Its Switch Gear And Auxiliaries At Existing 33//11 Kv 3.15 Mva Smvd University Receiving Station Including Reconditioning Of Existing Infrastructure.Important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Works Including Testing And Energisation , Specifically Mentioned Or Not In Above Description But Required At Site Shall Be Deemed To Be Included And Covered In The Quoted Rates.
BOQ
| Sl. No. | Item Description |
| 1 | Survey, Supply, Installation , Testing and Commissioning of following Equipments |
| 2 | Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories |
| 3 | Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A),Rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 4 | 11 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE- Compatible with existing Bank (Electric Field) including Smart Trivector Meters |
| 5 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 6 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type ( Station type ) |
| 7 | 33 KV Lightening Arrestors(30 KV 10 KA Polymer,Station Class ZnO, Gapless) |
| 8 | 150 mm2 ACSR conductor |
| 9 | Painting of Gantry structure along with transformer /Equipments/Mesh with Al. Paint complete job |
| 10 | Repair of 33 KV Yard Concreting /Metalling with 1: 4 :8 with additional reqd. 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick. |
| 11 | Repair of Yard Lightening along with installation of 100 Watt LED Lights |
| 12 | GI Plate Earthing with 600mmx600mmx6mm,GI Plate,GI Flat 50 x6 mm, GI pipe,40 mm Dia with Charcoal salt & good earth 10 ft. deep pit etc. as per REC Standard complete job |
| 13 | Chain link fencing by way of mass concrete in foundation and chainlink fencing of 6 Ft. height |
| 14 | Repair Work of Existing 33 KV VCB (36 KV,1250,26.2 KA Outdoor type) along with C&R Panel and 11 KV Out going VCBs of old Bank as per requirement complete job |
| 15 | Oil Topping of existing Old 3.15 MVA Power Transformer along with necessary repair works |
| 16 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards. |
| 17 | Galvanised Nuts & Bolts |
| 18 | 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 19 | 6 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 20 | 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 21 | Exaust Fan for control room |
| 22 | SUPPLY OF FOLLOWING MATERIAL |
| 23 | 11 kV Single core Heat Shrinkable Cable Termination Kits for 185 sqmm (Indoor) |
| 24 | 11 kV Single core Heat Shrinkable Cable Termination Kits for 185 sqmm (Outdoor) |
| 25 | 11 kV Single core Heat Shrinkable Cable Termination Kits for 300 sqmm (Indoor) |
| 26 | 11 kV Single core Heat Shrinkable Cable Termination Kits for 300 sqmm (Outdoor) |
| 27 | 100 mm2 ACSR conductor |
| 28 | 33 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m |
| 29 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 30 | 33kV Polymeric composite Disc Insulator with Fitting 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 31 | Crimping Tool Kit complete set for cable of different sizes upto 630 sqmm |
| 32 | RainCoats |
| 33 | Gum boots |
| 34 | Emergency light/ Torch 5 Watt chargeable |
| 35 | Multimeter |
| 36 | Extendable Aluminium Ladder 25 feet |
| 37 | Blower lamp (For fiilling cable kits) Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0 |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender