Tender For B.O.Q For Supplying And Installation Of Fire Control Panel At Lbdda Office And Fire Safety Equipments At Other Assets Of Lbdda
Tender Value
6.79 Lakhs
Estimated cost
Bid Submission
19 Aug 2026
9 days left
EMD
13594
Bank guarantee accepted
Document Fee
300
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kupwara → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for B.O.Q For Supplying And Installation Of Fire Control Panel At Lbdda Office And Fire Safety Equipments At Other Assets Of Lbdda
BOQ
| Sl. No. | Item Description |
| 1 | Part A: Main Building |
| 2 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history login the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as perspecifications. |
| 3 | Single Loop Panel. |
| 4 | Supply, installation, testing and commissioning of intelligent addressable optical smoke detector with LED indication, detector base, dust protection cover and complete mounting accessories. |
| 5 | Supply, installation, testing and commissioning of intelligent addressable heat detector complete with detector base and mounting accessories. |
| 6 | Supply, installation, testing and commissioning of addressable Manual Call Point with resettable element, weather-resistant housing and complete accessories. |
| 7 | Supply, installation, testing and commissioning of addressable electronic hooter/sounder suitable for 24V DC operation with minimum sound output of 90 dB at 1 metre complete with mounting accessories. |
| 8 | Supply, installation, testing and commissioning of LED response indicator for concealed detector locations complete with wiring and accessories. |
| 9 | Supply, laying, testing and commissioning of 2 Core x 1.5 Sq.mm FRLSH shielded fire survival Cu cable in conduit/tray including termination, ferruling and dressing complete. |
| 10 | Supply and laying of heavy-duty ISI marked PVC conduit of suitable size including bends, couplers, junction boxes, saddles and accessories complete. |
| 11 | Supply, installation, testing and commissioning of sealed maintenance-free batteries suitable for minimum 24-hour standby and 30-minute alarm operation complete with interconnections. |
| 12 | Providing proper earthing of Fire Alarm Control Panel complete with earth electrode, earth wire and accessories as required.(GI Pipe erathing with 40 mm Dia , 3 m Long) |
| 13 | Supplying, Installation, Testing and Commissioning of ABC type Fire Extinguisher 4.Kg. Capacity ISI Mark(IS:15683) and dully certified |
| 14 | Supplying, Installation, Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical fires |
| 15 | Part B: Officers Building |
| 16 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history login the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as perspecifications. |
| 17 | Single Loop Panel. |
| 18 | Supply, installation, testing and commissioning of intelligent addressable optical smoke detector with LED indication, detector base, dust protection cover and complete mounting accessories. |
| 19 | Supply, installation, testing and commissioning of intelligent addressable heat detector complete with detector base and mounting accessories. |
| 20 | Supply, installation, testing and commissioning of addressable Manual Call Point with resettable element, weather-resistant housing and complete accessories. |
| 21 | Supply, installation, testing and commissioning of addressable electronic hooter/sounder suitable for 24V DC operation with minimum sound output of 90 dB at 1 metre complete with mounting accessories. |
| 22 | Supply, installation, testing and commissioning of LED response indicator for concealed detector locations complete with wiring and accessories. |
| 23 | Supply, laying, testing and commissioning of 2 Core x 1.5 Sq.mm FRLSH shielded fire survival Cu cable in conduit/tray including termination, ferruling and dressing complete. |
| 24 | Supply and laying of heavy-duty ISI marked PVC conduit of suitable size including bends, couplers, junction boxes, saddles and accessories complete. |
| 25 | Supply, installation, testing and commissioning of sealed maintenance-free batteries suitable for minimum 24-hour standby and 30-minute alarm operation complete with interconnections. |
| 26 | Providing proper earthing of Fire Alarm Control Panel complete with earth electrode, earth wire and accessories as required.(GI Pipe erathing with 40 mm Dia , 3 m Long) |
| 27 | Supplying, Installation, Testing and Commissioning of ABC type Fire Extinguisher 4.Kg. Capacity ISI Mark(IS:15683) and dully certified |
| 28 | Supplying, Installation, Testing and Commissioning of CO2 Type Fire Extinguisher 4.5 Kg. Capacity ISI Mark(IS:15683)suitable for 'B' and 'C' class fires - inflammable liquids, gaseous fires like L.P.G. and acetylene, and electrical fires Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 03, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 19, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysAug 20, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender