Tender For Addition/ Alteration/ Conversion Of Lt Overhead Conductor To Ug Cable And Connected Works At Jodhpur Military Station
Tender Value
6.50 Crore
Estimated cost
Bid Submission
31 Aug 2026
19 days left
EMD
6.50 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jodhpur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Addition/ Alteration/ Conversion Of Lt Overhead Conductor To Ug Cable And Connected Works At Jodhpur Military Station
BOQ
| Sl. No. | Item Description |
| 1 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 300 sq mm 3.5 core complete all as specified and directed. |
| 2 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 240 sq mm 3.5 core complete all as specified and directed. |
| 3 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 185 sq mm 3.5 core complete all as specified and directed. |
| 4 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 120 sq mm 3.5 core complete all as specified and directed. |
| 5 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 150 sq mm 3.5 core complete all as specified and directed. |
| 6 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 95 sq mm 3.5 core complete all as specified and directed. |
| 7 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 70 sq mm 3.5 core complete all as specified and directed. |
| 8 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 50 sq mm 3.5 core complete all as specified and directed. |
| 9 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 35 sq mm 3.5 core complete all as specified and directed. |
| 10 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 25 sq mm 4 core complete all as specified and directed. |
| 11 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 16 sq mm 4 core complete all as specified and directed. |
| 12 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminimum conductor of size 10 sq mm 4 core complete all as specified and directed. Note for Ser Items Nos 1.00 to 12.00 :- Contractor may be visit the site and location before quoting the rate and cable should be CTL tested from approved govt lab/Jodhpur discom lab. Test certificate to be provided. |
| 13 | Earthing complete with galvanized steel earth plate electrodes 600mmx600mmx6 mm thick buried directly in ground earth (earth pit not less 2.25 m deep below ground level) with top edge of the plate not less then 1.5 mtr below normal ground level connected to galvanised iron earthing strip 32mm x 6mm thick by means of bolt nuts check nuts and washers of galvanized iron or steel all as specified & shown in electrical plate No.3 of MES SSR part-I 2020 connected to earth test point as specified and testing on completion including provision of 40 mm dia light grade pipe up to 7.5 mtr length as protection & watering pipe shall be 20 mm bore medium grade including all excavation & earth work in any type of strata including PCC pit (1:3:6) type C-1 with RCC cover including charcoal , salt, funnel, all as directed at site complete all as specified and directed.Note :- GI strip 32 mm x 6 mm and 40 mm dia protection pipe upto 7.5 mtr from earth plate is deemed to be included in rate quoted. |
| 14 | Dismantling of unserviceable ACSR conductor of any type and size from existing poles at various location at site complete all as specified and directed. |
| 15 | Dismantling of cross arms (Clamp, nut bolts ),care fully from site complete all as specified and directed. |
| 16 | Dismantling of insulators any type any size from existing poles complete all as specified and directed. |
| 17 | Taking out serviceable LT cable of any type and size for re-use and relaying in ground/along wall at site complete all as specified and directed.Note : Earth work shall be measured and paid separately of relavent items and, sand & PCC covers/stone slab shall reused all as directed. |
| 18 | Supply and fixing of security light junction boxes of dimension 240×130×110 mm, with shockproof, rustproof, termite resistant, weather proof, cable entry from bottom, pole mounting arrangement along with 3 phase 4 wire 100 amps almunium busbar with insulators and MCB SP-0.5 amps rating with including Cable Glands input & output, lugs, conforming to IP 65 etc complete all as specified and directed. |
| 19 | Supply and fixing of three core copper wire 1.5 sqmm FRSH PVC insulated copper conductor, cable in surface/ recessed in PVC conduit as required inclusive of all tees, bends, elbows. Reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, MS clamps for fixing with pole etc of size 25 mm dia complete all as specified and directed. |
| 20 | Dismantling of stay assembly complete all as specified and directed. |
| 21 | Supply and fixing of cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, Al conductor cable of size 50 sqmm complete all as specified and directed. |
| 22 | Supply and fixing of cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed. |
| 23 | Supply and fixing of cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, Al conductor cable of size 150 sqmm complete all as specified and directed. |
| 24 | Supply and fixing of cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, Al conductor cable of size 185 sqmm complete all as specified and directed. |
| 25 | Supply and fixing of cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, Al conductor cable of size 240 sqmm complete all as specified and directed. |
| 26 | Supply and fixing of cable jointing kit for 1.1 KV grade cable for end joint indoor type complete with Jointing material heat Shrink type and accessories suitable for 3.5 / 4 core XLPE, armoured, Al conductor cable of size 50 sqmm complete all as specified and directed. |
| 27 | All as per Item No 26.00 above but size of cable 95 sqmm 3.5/4 core |
| 28 | All as per Item No 26.00 above but size of cable 120 sqmm 3.5/4 core |
| 29 | All as per Item No 26.00 above but size of cable 150 sqmm 3.5/4 core |
| 30 | All as per Item No 26.00 above but size of cable 185 sqmm 3.5/4 core |
| 31 | All as per Item No 26.00 here-in-before but size of cable 240 sqmm 3.5/4 core |
| 32 | Material and labour Cement concrete (1:2:4) type B -1 using 20 mm graded stone aggregate for pedestal of poles / copping / road cutting filling / pcc cutting filling including necessary frame work ,fair finishing to exposed surfaces using extra cement complete all as specified and directed. |
| 33 | M&L for GI tubing 40 mm dia light grade (ISI marked) with all fitting /accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc complete all as specified and directed. |
| 34 | M&L for GI tubing 50 mm dia light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc complete all as specified and directed. |
| 35 | M&L for GI tubing 80 mm dia light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc complete all as specified and directed. |
| 36 | M&L for GI tubing 100 mm dia light grade (ISI marked) with all fitting/accessories for protection of cable on pole/wall and under road crossing including clamps, nuts bolts etc complete all as specified and directed. |
| 37 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1/ HB |
| 38 | (A) IN COMING(a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No(b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No.(c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No.(B) OUT GOING(a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -09 Nos(b)street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 39 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 2/ HB |
| 40 | (A) IN COMING(a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No(b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No.(c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 63 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 Nos (b) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -09 Nos |
| 41 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1200x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 3,28 / HB |
| 42 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -03 Nos |
| 43 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 6,7,27,30 / HB |
| 44 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -06 Nos |
| 45 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 5/ HB |
| 46 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -08 Nos |
| 47 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 8,15,17,19,23,25 / HB |
| 48 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 250 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -06 Nos (b) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magneticadjustable release type(Icu=Ics=100%) -01 No |
| 49 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1200x1000x450mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 9,13,14,16,18,20,21,22,24,26 / HB |
| 50 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -06 Nos |
| 51 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 29, 4 / HB |
| 52 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -06 Nos (c) street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 53 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel 11 / HB |
| 54 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -05 Nos (b) MCCB 4 Pole 415 Volts 16 KA, 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No |
| 55 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1200x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 12 / HB |
| 56 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%)-04 Nos |
| 57 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 10 /HB |
| 58 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 125 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%)-06 Nos (b) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 59 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 21A/ HB |
| 60 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No.(c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No (b) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%)-03 Nos (c) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 61 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. MPA / HB |
| 62 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (c) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 63 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1,2,11,12,16 / SHIK |
| 64 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -06 Nos |
| 65 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel 3,6 / SHIK |
| 66 | (A) IN COMING(a) MCCB 4 Pole 415 Volts 16 KA 63 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 Nos (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -04 Nos |
| 67 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel 4,10 / SHIK |
| 68 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -05 Nos |
| 69 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 5 / SHIK |
| 70 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -10 Nos |
| 71 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 7 / SHIK |
| 72 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -11 Nos |
| 73 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following : - Panel No. 17,18/SHIK |
| 74 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -12 Nos |
| 75 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 21 / SHIK |
| 76 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 No (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -10 No |
| 77 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No.8,19/SHIK |
| 78 | (A) INCOMING(a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type (Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 79 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 9,15/SHIK |
| 80 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -09 Nos Make : Legrand /Indoasian/ABB (b) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 81 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 13/SHIK |
| 82 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -09 Nos Make : Legrand /Indoasian/ABB |
| 83 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 14/ SHIK |
| 84 | (a) MCCB 4 Pole 415 Volts 36 KA 250 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b)MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -09 Nos Make : Legrand /Indoasian/ABB |
| 85 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 20/ SHIK |
| 86 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a)MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos Make : Legrand /Indoasian/ABB |
| 87 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 22/ SHIK |
| 88 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos Make : Legrand /Indoasian/ABB |
| 89 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel MP2/SHIK |
| 90 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type (Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type (Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type (Icu=Ics=100%) -01 No (c) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type (Icu=Ics=100%) -01 No |
| 91 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1/ 73 ASC |
| 92 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 25 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos (c) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 93 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 2/ 73 ASC |
| 94 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos |
| 95 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1200x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 3 / 73 ASC |
| 96 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -03 Nos Make : Legrand /Indoasian/ABB |
| 97 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 4 / 73 ASC |
| 98 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -03 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No |
| 99 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- P1(FOL DEPOT) |
| 100 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) Change over switch 300A 4P 414V AC SS Enclosure Extened handle-01 No (c) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (d) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (TO P2) (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -03 No (TO KSP1,KSP2,KSP3) (c) MCCB 4 Pole 415 Volts 16 KA 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -03 No (TO SLT1,SLT2,POST1) (d) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 101 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- P2(FOL DEPOT) |
| 102 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amps rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No (TO OFFICE DB,P5) (b) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (TO P3) |
| 103 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- P3(FOL DEPOT) |
| 104 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 25 KA 100 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING(a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (TO P4) (b) MCCB 4 Pole 415 Volts 16 KA 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No (TO POST 3,FIRE STN) |
| 105 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- P4(FOL DEPOT) |
| 106 | (A) IN COMING(a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No(TO POST2, WELDING STN) |
| 107 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- P5(FOL DEPOT) |
| 108 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) -02 No (TO HM,SL) |
| 109 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 2000x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1 / ALSS1 |
| 110 | (a)MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 40 Amp rating thermal magnetic release type(Icu=Ics=100%) -08 No Make : Legrand /Indoasian/ABB |
| 111 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 2 / ALSS1 |
| 112 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos Make : Legrand /Indoasian/ABB |
| 113 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 3,11 / ALSS1 |
| 114 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos (b) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 115 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 4,7 / ALSS1 |
| 116 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos (b) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 117 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 5,15 / ALSS1 |
| 118 | (a) MCCB 4 Pole 415 Volts 36 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB(b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 119 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 2000x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 15 / ALSS4 |
| 120 | (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -12 Nos |
| 121 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 6, 8, 16,17/ ALSS1 |
| 122 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos Make : Legrand /Indoasian/ABB |
| 123 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 9,12 / ALSS1 |
| 124 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -01 Nos (b) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic release type(Icu=Ics=100%) -04 No Make : Legrand /Indoasian/ABB |
| 125 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 10,13 / ALSS1 |
| 126 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -03 Nos Make : Legrand /Indoasian/ABB |
| 127 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 14 / ALSS1 |
| 128 | (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos (b) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 129 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1 / ALSS2 |
| 130 | (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (c) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 131 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1100x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 2,4A,14 / ALSS2 |
| 132 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type (Icu=Ics=100%) -01 NoMake : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos |
| 133 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following- Panel No. 3 / ALSS2 |
| 134 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 225 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -08 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 135 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 4 / ALSS2 |
| 136 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos Make : Legrand /Indoasian/ABB |
| 137 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 2000x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 5 / ALSS2 |
| 138 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -09 Nos (b) MCCB 4 Pole 415 Volts 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -01 Nos (c) MCCB 4 Pole 415 Volts 16 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No |
| 139 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 6 / ALSS2 |
| 140 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos (b) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 141 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 7,9A,13 / ALSS2 |
| 142 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos Make : Legrand /Indoasian/ABB |
| 143 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 8 / ALSS2 |
| 144 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 225 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -01 Nos (b) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos Make : Legrand /Indoasian/ABB |
| 145 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 9 / ALSS2 |
| 146 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos Make : Legrand /Indoasian/ABB |
| 147 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 10 / ALSS2 |
| 148 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -08 Nos (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -01 Nos Make : Legrand /Indoasian/ABB |
| 149 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 11 / ALSS2 |
| 150 | (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos Make : Legrand /Indoasian/ABB |
| 151 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 2000x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 12 / ALSS2 |
| 152 | (a) MCCB 4 Pole 415 Volts 36 KA 250 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -09 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (c) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 153 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1 / ALSS3 |
| 154 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens.(B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -01 Nos (b) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -01 Nos (c) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic release type(Icu=Ics=100%) -07 No Make : Legrand /Indoasian/ABB (d) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 155 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 2 / ALSS3 |
| 156 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos Make : Legrand /Indoasian/ABB |
| 157 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 3 / ALSS3 |
| 158 | (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 159 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 4,6,8 / ALSS3 |
| 160 | (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -03 Nos Make : Legrand /Indoasian/ABB |
| 161 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 5 / ALSS3 |
| 162 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (c) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos |
| 163 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1300x1000x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following- Panel No. 7 / ALSS3 |
| 164 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -03 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 165 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 9 / ALSS3 |
| 166 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos Make : Legrand /Indoasian/ABB |
| 167 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 10 / ALSS3 |
| 168 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos Make : Legrand /Indoasian/ABB |
| 169 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 2000x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 11,14 / ALSS3 |
| 170 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -10 Nos (b) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 171 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 12,19 / ALSS3 |
| 172 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos (b) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 173 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 13,20 / ALSS3 |
| 174 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -08 Nos Make : Legrand /Indoasian/ABB |
| 175 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 15 / ALSS3 |
| 176 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 NoMake : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -08 Nos (b) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No |
| 177 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 16 / ALSS3 |
| 178 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos |
| 179 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 17 / ALSS3 |
| 180 | (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 181 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 18 / ALSS3 |
| 182 | (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos Make : Legrand /Indoasian/ABB |
| 183 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 1 / ALSS4 |
| 184 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 125 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos Make : Legrand /Indoasian/ABB |
| 185 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 2,9 / ALSS4 |
| 186 | (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -08 Nos Make : Legrand /Indoasian/ABB (b) Street light timer switch using digital timer switch for switching of street lights based on timing set manually on digital timer - 01Nos |
| 187 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following- Panel No. 3,7 / ALSS4 |
| 188 | (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos Make : Legrand /Indoasian/ABB |
| 189 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 4 / ALSS4 |
| 190 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos |
| 191 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 5 / ALSS4 |
| 192 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 225 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -05 Nos Make : Legrand /Indoasian/ABB (b) MCCB 4 Pole 415 Volts 16 KA 63 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (c) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 193 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 6 / ALSS4 |
| 194 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -06 Nos Make : Legrand /Indoasian/ABB |
| 195 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 8 / ALSS4 |
| 196 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -07 Nos Make : Legrand /Indoasian/ABB |
| 197 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following- Panel No. 10 / ALSS4 |
| 198 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 400 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -3 Nos (b) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -02 No (c) MCCB 4 Pole 415 Volts 36 KA 250 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 199 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the followin:- Panel No. 11 / ALSS4 |
| 200 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 100 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -08 Nos Make : Legrand /Indoasian/ABB |
| 201 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1500x1200x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the followin:- Panel No. 12 / ALSS4 |
| 202 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 250 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -04 Nos (b) MCCB 4 Pole 415 Volts 16 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB |
| 203 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 1800x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 13 / ALSS4 |
| 204 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 16 KA 200 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No Make : Legrand /Indoasian/ABB (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -12 Nos Make : Legrand /Indoasian/ABB |
| 205 | Supply, install, testing and commissioning CPRI approved of outdoor cubical type LT Panel board, gable roof, floor mounted, factory made suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with aluminium bus bars of suitable rating duly insulated by insulation of RYB colour on SMC insulators with short circuit withstand capacity 35 MVA. The panels shall be factory made, double door made outer side of 3.15 mm thick and inner shall be of 2.00 mm thick MS Sheet totally enclosed of size not less than 2000x1500x450 mm and dust, weather, vermin and rust proof front operated, front and rear opening with locking arrangement. The bootom base chanal of MS angle section not less than 100x50x5mm. Entire panal shall have common aluminimum earth bar of size 25x5 mm at the rear with two nos earth stad, solid connection from main bas bar to switch gears with required size of bus bar and controlling wiring with minimum 1.5 sqmm pvc insulated copper conductor cable. The ground clearanc should be minimum 600 mm. MS angle section 50x 50x6 mm frame with front & back openable double door system lockable / opnable by keys from both sides having flush pattern fancy locks with louvers & air vent gasket for natural flow of air. and duly painted with two coats of synthetic enamel paint over a coat of red oxide primer with colour as directed including internal wiring with multistranded copper conductor cable of suitable size incl lugs and cable gland to incoming and outgoing cable with 3 butt hinges to panel doors and locking arrangement and should be of IP 54 and complete all as directed by Engr-in-charge and comprising of the following:- Panel No. 14 / ALSS4 |
| 206 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -10 Nos Make : Legrand /Indoasian/ABB Please Enable Macros to View BoQ information |
| 207 | (A) IN COMING (a) MCCB 4 Pole 415 Volts 36 KA 320 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (b) RYB indicating lamp LED type suitable for panel mounting (Set of three) - 01 No. (c) Panel mounted multi function energy meter of accuracy PF,KWH, KVAH, CL-1.0 rating - 01 NoL&T/Siemens. (B) OUT GOING (a) MCCB 4 Pole 415 Volts 36 KA 160 Amp rating thermal magnetic release type(Icu=Ics=100%) -01 No (a) MCCB 4 Pole 415 Volts 40 Amp rating thermal magnetic adjustable release type(Icu=Ics=100%) rating -10 Nos Make : Legrand /Indoasian/ABB Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Aug 03, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 31, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysSep 07, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 26 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender