Tender For Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X6.30Va, 33/11Kv Receiving Station Along With 33Kv Line At Mohalla, Battal-Kareli. In District Doda Under The Jurisdiction Of Executive
Tender Overview
Project Description
Tender for Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X6.30Va, 33/11Kv Receiving Station Along With 33Kv Line At Mohalla, Battal-Kareli. In District Doda Under The Jurisdiction Of Executive Engineer, Sub Transmission Division Doda, Jpdcl Jammu .
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation,Design, Survey, Engineering, Testing, Commissioning of 6.3MVA receiving station at Mohallah-Battal-Kareli |
| 2 | 33 KV LINE BAY AT PREMNAGAR (INCLUDING ALL CIVIL WORKS) |
| 3 | SITC of 33 KV VCB (36 KV, 1250 A, 26.2 KA, outdoor type) along with Pad Calm & allied items as per approved Drawings by Department/GTP |
| 4 | SITC of 33 KV Isolator with earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) as per approved Drawings by Department/GTP |
| 5 | SITC of 33 KV Isolator without earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) as per approved Drawings by Department/GTP |
| 6 | SITC of 33 KV Current Transformer (400-200/5-5-5, Outdoor) along with Bimettalic CT Clamp and allied items as per approved Drawings by Department/GTP |
| 7 | SITC of 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless along with clamp & allied items as per approved Drawings by Department/GTP |
| 8 | SITC of 33 KV C&R panel along with 03 O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port SCADA Compatible as per approved Drawings by Department/GTP |
| 9 | SITC of 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm. along with clamp and allied items as per approved Drawings by Department/GTP |
| 10 | SITC of 33 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase) along with bimettalic PT clamp & allied items as per approved Drawings by Department/GTP |
| 11 | Equipments/Gantry foundations as per approved Drawings by Department |
| 12 | 33kv Yard Concreting & Metalling with Washed, Uniformly graded crushed stones 40mm size thickness typically ranging between 100mm to 150 mm as per site In-Charge. |
| 13 | SITC of Earthing through GI Plate (600*600*8mm) & GI pipe ( 3 meters long, 40 mm dia) through GI strips & . The Earth Pit Size shall be 1.5Mtr*1.5Mtr*3Mtr. The Quantity of Salt & Charcoal shall form the layer of thickness 150mm each as per approved drawings by department |
| 14 | SITC of Earthing Spikes of GI Rod 20mm 2.5 mtr long through GI Strip as per approved drawings by department/GTPs |
| 15 | Cable Duct (30cm*30cm*30cm) with Cover & finishing, PVC Pipe for Dressing of Cables from equipments and Cable Trayes for Cable Duct as per approved drawings by department |
| 16 | Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height as per site-incharge. 65*6mm G.I Angle at a Distance of 6Ft. And topping of mesh with same GI Angle |
| 17 | Earthing Mat Complete job GI flat 50x8 mm as per approved Drawings/GTPs/REC |
| 18 | STEEL STRUCTURES |
| 19 | Pipe Nominal bore 200, 5.9 mm thick |
| 20 | Hot Dip Galvanised steel structures |
| 21 | Hot Dip Galvanized nuts and bolts |
| 22 | CONTROL CABLES |
| 23 | SITC of 12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
| 24 | SITC of 8 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 25 | SITC of 2 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 26 | Lugs & Ferrules etc. |
| 27 | CONDUCTOR AND HARDWARE |
| 28 | SITC of ACSR Conductor Panther (200sqmm) |
| 29 | SITC of T-Clamp |
| 30 | SITC of Single Tension fitting |
| 31 | SITC of Polymer Composit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load 70 KN |
| 32 | Earth Wire 7/4 sqmm |
| 33 | G.I Flat 50*6 mm |
| 34 | SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY (INCLUDING ALL CIVIL WORKS) |
| 35 | SITC of 33 KV VCB (36 KV, 1250 A, 26.2 KA, outdoor type) alongwith Pad Clamp and othe allied items as per approved Drawings by Department/GTPs |
| 36 | SITC of 33 KV Isolator without earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA) as per approved Drawings by Department/GTPs |
| 37 | SITC of 33 KV Current Transformer (Single Phase,400-200/5-5-5,Outdoor) with Bimetallic CT Clamp & allied items as per approved Drawings by Department/GTPs |
| 38 | SITC of 30 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless with Clamp & allied items as per approved Drawings by Department/GTPs |
| 39 | SITC of 33 KV C&R panel along with 03 O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port as per approved Drawings by Department/GTPs |
| 40 | SITC of 33 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm with Clamp & allied items as per approved Drawings by Department/GTPs |
| 41 | Equipments/Gantry foundations as per approved Drawings by Department |
| 42 | 33kv Yard Concreting & Metalling with Washed, Uniformly graded crushed stones 40mm size thickness typically ranging between 100mm to 150 mm as per site In-Charge. |
| 43 | SITC of Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips & GI Plate (600*600*8mm). The Earth Pit Size shall be 1.5Mtr*1.5Mtr*3Mtr. The Quantity of Salt & Charcoal shall form the layer of thickness 150mm each as per approved drawings by department |
| 44 | SITC of Earthing Spikes of GI Rod 20mm 2.5 mtr long through GI Strip as per approved drawings by department/GTPs |
| 45 | Cable Duct (30cm*30cm*30cm) withCover & finishing, PVC Pipe for Dressing of Cables from equipments and Cable Trayes for Cable Duct as per approved drawings by department |
| 46 | Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height as per site-incharge. |
| 47 | Earthing Mat complete job GI flat 50x8 mm as per approved Drawings/GTPs |
| 48 | Cable Duct (1Mtr*1Mtr*1Mtr) with cover& finishing & Supporting GI Angle (50*8mm) at a Distance of 2ft.each for Power Cables (XLPE), 1) Incommer Cable, 2) Outgoing 11kV feeders Cables (04 Nos) 3) Auxiliary Cable as per approved Drawings |
| 49 | STEEL STRUCTURES |
| 50 | Pipe Nominal bore 200, 5.9 mm thick |
| 51 | Galvanised steel structures |
| 52 | Galvanized nuts and bolts |
| 53 | CONTROL CABLES |
| 54 | 10 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS |
| 55 | 8 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 56 | 2 core 2.5 mm2 copper armoured, 1.1 kv grade, ISI FRLS |
| 57 | Lugs & Ferrules etc. |
| 58 | CONDUCTOR AND HARDWARE |
| 59 | SITC of ACSR Conductor Panther |
| 60 | SITC of T-Clamp |
| 61 | SITC of Single Tension fitting |
| 62 | SITC of Polymer Composit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load 70 KN |
| 63 | Earth Wire 7/4 sqmm |
| 64 | G.I Flat 50*6 mm |
| 65 | 33/11 KV, 6.30 MVA Power Transformer |
| 66 | SITC of 33/11KV ONAN,Copper wound,outdoor type,6.30 MVA Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections and spare 5 Barrells transformer oil, 01 No HV Bush, 01 No LV Bush, 01 No HV Bush Rod, 01 No LV Bush Rod as per approved Drawings by Department/GTP |
| 67 | SITC of 10 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 68 | SITC of 6 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 69 | SITC of 2 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS |
| 70 | Lugs & Ferrules etc. |
| 71 | Single Bus system 11 KV(Transformer Bay Scheme) |
| 72 | SITC of 11 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector Smart meter-5A,DLMS Compliant with RS-485 Port 1 Incoming & 4 outgoings with two year warranty as per approved Drawings by Department/GTPs |
| 73 | SITC of 11KV Gapless Surge Arrestor,9KV,10KA LA With polymer Housing Station Type with Clamp & allied items as per approved Drawings by Department/GTPs |
| 74 | 11KV (UE) XLPE Power Cable 3 core armoured |
| 75 | I. 400 mm square three core |
| 76 | II. 185 mm square three core |
| 77 | 11KV Heat shrink termination Cable Kits (Indoor) 400 mm square (3-core) |
| 78 | 11KV Heat shrink termination Cable Kits (Outdoor)400 mm square (3-core) |
| 79 | 11KV Heat shrink termination Cable Kits (Indoor) 185 mm square(one spare)(3-core) |
| 80 | 11KV Heat shrink termination Cable Kits (Outdoor) 185 mm square (one spare)(3-core) |
| 81 | 11 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch as per approved Drawings by Department/GTPs |
| 82 | 11KV Go Set AB switch 3 phase, 3 pole, 400 Amps. |
| 83 | 100 KVA, 11/.433 KV, Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound with spare 01 No HV Bush, 01 No. LV Bush, 01 No HV Bush Rod, 01 No LV Bush Rod as per approved Drawings by Department/GTPs |
| 84 | ST Poles 9 mtrs long with Channel piece for earthing as per approved Drawings by Department/GTPs |
| 85 | Galvanised iron of sorts |
| 86 | 120 mm2 PVC 4 core cable,Armoured FRLS |
| 87 | MCCB 200 Amp |
| 88 | Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole |
| 89 | Earthing of 100 KVA Sub Station As per Standard |
| 90 | Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long |
| 91 | COMMON MISCELLANEOUS EQUIPMENTS |
| 92 | a) SITC of Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand as per approved Drawings by Department/GTPs |
| 93 | b) SITC of 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply as per approved Drawings by Department/GTPs |
| 94 | SITC of Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supply with 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories as per approved Drawings by Department/GTPs |
| 95 | SITC of Distribution panel (415 V, AC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories as per approved Drawings by Department/GTPs |
| 96 | Telecommunication facilities including Handset/Mobile set with latest features, CCTV set (4nos cameras ) LED Display (32\\") specifications as per department. |
| 97 | CIVIL WORKS |
| 98 | Compound walling with finishing of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height along with Y-Post of GI Angle (50*6mm) with Barbed wire as per site-incharge |
| 99 | Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (10000 ltr) and fixing of water lifting motor (2HP) |
| 100 | 33/11kV Power Transformer Foundation as per approved Drawings |
| 101 | Cable Duct (1Mtr*1Mtr*1Mtr) with finishing & Supporting GI Angle (50*8mm) at a Distance of 2ft.each for Power Cables (XLPE) in the Control room building |
| 102 | Earthing of Control room Building/ JE/SBAs Quarters as per Site Engineer/Approved Drawings |
| 103 | Wooden Almirah for SBAs (Shift Duty Room) in Controol room as per Site Engineer (Size shall be for Four Shifts) |
| 104 | Wooden/Aluminium/Steel Table (6ft*3ft) & Chairs (06 Nos) of High Quality for Control room |
| 105 | Water tank 2000 Ltrs.( overhead) |
| 106 | Control room Building with wash room ,pantry room, Shift Duty room.sanitary fittings tile works ,kota stone in control room internal wiring,painting and fixing of electrical appliances like lights ,fans,geysers job complete finish as per approved Drawings & Site-Engineer. |
| 107 | Shift Quarters for Je and SBA including wash room ,pantry room sanitary fittings tile works ,internal wiring,painting and fixing of electrical appliances like lights ,fans,geysers job complete finish as per approved Drawings & Site Engineer. |
| 108 | Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing as per approved Drawings. |
| 109 | Development of land (as per available site ) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas, Earth work by exacvation and development of road along with surface drain. Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates). |
| 110 | Construction of semi Pucca B/Wall of 2.0 Mtr/4.0Mtr (as per site) Height (Length=200 mtr) |
| 111 | Dry random rubble masonry with hard stone in foundation and plinth: Without bond stone |
| 112 | Construction of Pucca Drain |
| 113 | Yard Lighting ( 4 Nos yard and 02 Nos CR back side) |
| 114 | OPERATION & MAINTENACE |
| 115 | Operation & Maintenance of receiving station along with 33kV Line as per Norms in vogue. Each duty Shift must have 02 Nos of employees and 03 nos of Shifts in a month. Staff must be technical and insured as per rules in vogue. All the resposibilities shall be of Contractor |
| 116 | 33 KV LINE FROM RECEIVING STATION PREMNAGAR |
| 117 | 11 Mtr. Long ST Pole (For new line) ST-410 SP56 |
| 118 | Hot Dip GI Channel (100*50*6)mm, including clamps and braces GI Angle (50*6)mm |
| 119 | 100 mm² ACSR Dog Conductor |
| 120 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 121 | 33kV Polymeric composite Disc Insulator WITH FITTINGS 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with Disc fittings |
| 122 | Galvinized Nuts and Bolts. |
| 123 | Danger Plates with Clamps |
| 124 | Anti-Climbing Device with Clamps |
| 125 | Earthing Complete by Hot Dip GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip as per approved drawings by department/GTPs |
| 126 | Red Oxide |
| 127 | Aluminium Paint |
| 128 | Cement bottoming 1:2:4 mix as per REC standards .6cum /pole as per approved Drawings |
| 129 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 130 | Guard netting |
| 131 | 33 KV Isolator without earthing blade |
| 132 | CONTENGENCIES/T&P |
| 133 | Hiring of Vehicle (Scorpio/Bolero/Innova/Tavera or equivalent) to be used by the Engineer Incharge for supervision of the project including Fuel/Toll Taxes/Driver/ or any other maintenace charges of the vehicle. The max. Kms to be driven per day is 100KM. In case the vehicle is utilized less than 100KM on any given day, the payment shall be subject to deduction on account of actual fuel savings. Such Deduction shall be worked out Proportionately based on the approved mileage (KM/Ltr) of the vehicle and the prevailing fuel rates., |
| 134 | Fire Extinguisher CO2 type of 4.5 Kg capacity for control room as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 135 | 3-Sand Bucket Fire Extinguisher as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 136 | Helmet with LED torch as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 137 | Rubber Gloves for 33 KV Level as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 138 | Rubber Gloves for 11 KV Level as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 139 | 33KV DISC INSULATORS |
| 140 | 33KV PIN INSULATORS |
| 141 | 33KV DOG CONDUCTOR FIITINGS 70/90KN |
| 142 | Safety Belt as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 143 | Safety Shoes as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 144 | Earthing rod (set of 3 rods) as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. |
| 145 | HV Detector all Voltages as per ISI/BIS latest specifications. High Quality of Standard shall be maintained. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender